Lighting controls

Release 1.5.0 records the lighting controls of the source models on every commercial program, as the lighting_controls block of Program JSON 5.4.0 (release 2.4.0 exports Program JSON 6.1.0). The decision record is ADR 0044; the release notes are docs/release-notes-atlas-v1.5.0.md.

The three parts of lighting

Part Where it is
Installed power (design level) the lighting load, W/m²; fixed by template, except IECC 2021, which lowers it in some climates (value_by_climate)
Usage, with occupancy-sensor credits the lighting schedule; from 90.1-2010 and IECC 2012 the credits are inside its fractions
Daylight dimming lighting_controls.daylighting, new in 1.5.0

Reading the block

"lighting_controls": {
  "status": "known", "source": "pnnl_prototype",
  "daylighting": {
    "controlled_floor_fraction": 0.408, "controlled_lighting_fraction": 0.213,
    "illuminance_setpoint_lux": 377.0, "control_type": "continuous_off", "method": "split_flux",
    "minimum_input_power_fraction": 0.15, "minimum_light_output_fraction": 0.15,
    "stepped_control_steps": 3, "availability": "all_days_except_design_days",
    "controlled_zones": 12, "zones": 15},
  "evidence_id": "evidence-…"
}

(IECC 2021 medium office, rounded.)

  • daylighting: null means the complete source model has no controls in these zones: a source zero. That holds for IECC 2006 and 2009, 90.1-2007, the DOE Ref templates, and the zones without windows in later editions.
  • status: unknown means no source model represents the program (construction-only types, SuperMarket); the block gives the reason.
  • controlled_lighting_fraction is the share of the program's lighting power under daylight control, the sum of the reference-point fractions weighted by zone lighting power. Multiply it by the daylight savings your simulation finds; do not apply it to the schedule.
  • daylighting_by_climate lists the climate zones that differ (6A, 6B, 7A, 8A for skylit spaces, where the prototypes have smaller skylights).
  • 90.1 programs also carry standards_rule: openstudio-standards' target illuminance for the space type and, for office whole-building types, the share of the primary and secondary sidelit areas assumed daylightable.

Where the fractions come from

From release 2.3.0, Program JSON 6.0.0 labels the origin of every known block in lighting_controls.daylighting_origin (ADR 0059):

"daylighting_origin": {
  "kind": "prototype_zone_set",
  "climates": ["0A", "0B", "1A", "…", "8A"],
  "cited_climate": "0A",
  "note": "The fractions are geometry-derived from the Daylighting:Controls of the PNNL prototype zones …"
}

(90.1-2019 medium office, whole building.)

  • kind: prototype_zone_set: the fractions are derived from the PNNL prototype's geometry: the floor fraction of the program's prototype zones with Daylighting:Controls, and the reference-point fractions weighted by zone lighting power. kind: reference_model_scan: no DOE reference model has controls, a source zero whatever the geometry.
  • climates lists the prototype climates whose model gives daylighting; the others are in daylighting_by_climate. All 19 for most programs.
  • cited_climate is the climate of the one model the evidence row cites. When all 19 climates agree, as for the climate-independent 90.1-2019 medium office whole building, it is a copy (the first in climate order, 0A), not a choice of climate.

The unoccupied lighting cap

From release 2.4.0, Program JSON 6.1.0 adds lighting_controls.unoccupied_lighting_cap to every known block (ADR 0060, ADR 0061). PNNL's ASHRAE 90.1-2019 prototypes (header comment LPD_Ctrl = 0.02) give each zone of the office, restaurant, retail and warehouse types one EMS program: while the zone's occupant count is 0 and its lighting power is at least 0.02 W/ft², its lights are set to 0.02 W/ft² (0.215 W/m²).

"unoccupied_lighting_cap": {
  "rule": {
    "cap_W_m2": 0.2153, "lighting_threshold_W_m2": 0.2151,
    "source_values": {"cap": 0.02, "threshold": 0.02, "unit": "W/ft2",
                      "cap_conversion_m2_per_ft2": 0.09290304, "threshold_conversion_m2_per_ft2": 0.093},
    "condition": "zone_occupant_count_zero",
    "comparison": "zone_lighting_power_density_at_least_threshold",
    "action": "set_lights_to_cap", "calling_point": "BeginTimestepBeforePredictor",
    "zones": 15, "controlled_zones": 15,
    "zone_conditions": [{"zone": "Perimeter_mid_ZN_2", "condition": "((DaylightSavings==0) && …"}]},
  "evidence_id": "evidence-…"
}

(90.1-2019 medium office, whole building, rounded.)

  • rule: null is a source zero: the complete source model has no such program in these zones, and nulls gives the reason. That holds for 90.1-2007, 90.1-2013 and every IECC edition (no program in any of their 304 models; the office headers say LPD_Ctrl = 0), the DOE Ref templates (no EMS program at all), the 90.1-2019 types whose prototypes carry no program (apartments, hospital, hotels, outpatient and the schools, whose headers say LPD_Ctrl = 0.02 without a program) and the large office data centers.
  • The threshold compares all of the zone's lighting; the cap sets its general Lights object. The PNNL program converts W/m² to W/ft² with 0.093 for the threshold and 0.09290304 for the cap, so the two differ in the fourth digit; both are kept as written (source_values).
  • condition: zone_occupant_count_zero reads the zone's own People object. The warehouse storage zones read the office's (other_zone_occupant_count_zero, condition_zone: "Zone1 Office").
  • The strip mall stores also set their display lighting to 0 while capped (additional_lighting_when_capped_W_m2).
  • zone_conditions keeps PNNL's own variants as written: one perimeter zone of the medium and large office is capped only outside 07:00 to 16:00 standard time, one small office zone only while the building's binary occupancy schedule is 0.
  • The rule acts per zone and per timestep, on that zone's occupant count. A consumer applies it to each zone the program is assigned to; a zone whose people are never 0 is never capped.

Limits

  • The fractions come from the prototype geometry (daylighting_origin). A model with other windows or zoning should recompute them.
  • Dwellings carry no block: none of the residential or manufactured-housing models has daylighting controls.