Hospital zoning
Hospital · geometric LOD study drop 5 · atlas inputs release 2.4.0 · BEMGen 99c0b0adcd44
- Prototype
- Hospital
- Cells
- 24: 6 climate zones × 2 vintages × 2 orientations
- Cells with a recommended zoning
- 24 of 24
- Robust across orientations
- 12 of 12 cell pairs: Conditioned merge + Stack (7)
- Reference zoning
- No simplification + Stack
- Reference zones
- 54
- Most often recommended
- Conditioned merge + Stacked floor zone multiplier (20 of 24 cells)
- Serial cost (R5)
- timed in 2 of 24 cells (3C 90.1-2019 0°, 5A 90.1-2019 0°)
Robust across orientations
Robust across orientations in 12 of 12 cell pairs (0° and 45°).
| Climate zone | Vintage | Robust zoning | Zones | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Area change % | CPU ratio | Wall ratio | Memory ratio | Per orientation |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 2A | 90.1-2007 | Conditioned merge + Stack (tie: Conditioned merge + Stacked floor zone multiplier) | 24 | – | -0.8 | – | 1.0 | – | 0.8 | 0.00 | not timed | recommended at both orientations | ||
| 2A | 90.1-2019 | Conditioned merge + Stack (tie: Conditioned merge + Stacked floor zone multiplier) | 24 | – | -0.9 | – | 1.2 | – | 0.9 | 0.00 | not timed | recommended at both orientations | ||
| 2B | 90.1-2007 | Conditioned merge + Stack (tie: Conditioned merge + Stacked floor zone multiplier) | 24 | -39.1 | -0.9 | 182.9 | 1.3 | 39.1 | 0.9 | 0.00 | not timed | recommended at both orientations | ||
| 2B | 90.1-2019 | Conditioned merge + Stack (tie: Conditioned merge + Stacked floor zone multiplier) | 24 | – | -1.0 | – | 1.3 | – | 1.0 | 0.00 | not timed | recommended at both orientations | ||
| 3C | 90.1-2007 | Conditioned merge + Stack (tie: Conditioned merge + Stacked floor zone multiplier) | 24 | -33.5 | -1.4 | 151.8 | 1.7 | 33.5 | 1.4 | 0.00 | not timed | recommended at both orientations | ||
| 3C | 90.1-2019 | Conditioned merge + Stack (tie: Conditioned merge + Stacked floor zone multiplier) | 24 | – | -1.4 | – | 1.8 | – | 1.4 | 0.00 | 0.539 | 0.544 | 1.057 | recommended at both orientations |
| 4A | 90.1-2007 | Semantic merge + Stack | 51 | -0.0 | -0.0 | 0.1 | 0.0 | 0.0 | 0.0 | 0.00 | not timed | 0°: Conditioned merge + Stacked floor zone multiplier (24 zones) · 45°: Semantic merge + Stack (51 zones) | ||
| 4A | 90.1-2019 | Conditioned merge + Stack (tie: Conditioned merge + Stacked floor zone multiplier) | 24 | -56.4 | -1.4 | 145.9 | 1.8 | 56.4 | 1.4 | 0.00 | not timed | recommended at both orientations | ||
| 5A | 90.1-2007 | Semantic merge + Stack | 51 | -0.0 | -0.0 | 0.1 | 0.0 | 0.0 | 0.0 | 0.00 | not timed | 0°: Conditioned merge + Stacked floor zone multiplier (24 zones) · 45°: Semantic merge + Stack (51 zones) | ||
| 5A | 90.1-2019 | Conditioned merge + Stacked floor zone multiplier | 24 | 6.2 | 1.8 | 25.7 | 2.2 | -6.2 | -1.8 | 0.00 | 0.491 | 0.490 | 0.965 | recommended at both orientations |
| 7A | 90.1-2007 | Semantic merge + Stack | 51 | -0.0 | -0.0 | 0.1 | 0.0 | 0.0 | 0.0 | 0.00 | not timed | recommended at both orientations | ||
| 7A | 90.1-2019 | Conditioned merge + Stacked floor zone multiplier | 24 | -3.1 | 1.8 | 18.3 | 2.3 | 3.1 | -1.8 | 0.00 | not timed | recommended at both orientations | ||
For each prototype, climate zone and vintage, the robust zoning is the coarsest (fewest modelled zones) that meets the threshold at every orientation of the cell pair, by the writer's own verdict on each zoning at each orientation, with at most the reference's zone count, as the writer bounds a recommendation (D-220); a duplicate never meets, as the writer lists it. Ties at the fewest zones go to a zoning both orientations recommend, else to the first in the study's zoning order (simplifier, join pieces, perimeter depth, stacker, IWHT, FHT); the tied zonings are named. The errors reported are the worse of the orientations' values for each metric, so the row is a bound, not a mean; the cost ratios are the medians over the timed sites of that zoning in the pair. Where both orientations recommend the same zoning it is the robust one. A pair where no zoning meets the threshold at both orientations says so and names each orientation's own recommendation; the per-orientation rows below stay the reading for one orientation. The cost ratios are the median over the timed sites of the robust zoning in the pair (in this drop one orientation at most is timed, so the ratio is that site's); not timed where none is. The rule and its limits.
Recommended zonings
| Climate zone | Vintage | Orientation | Reference zones | Heating kWh/m² | Cooling kWh/m² | Recommended zoning | Zones | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Area change % | CPU ratio | Wall ratio | Memory ratio |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 2A | 90.1-2007 | 0° | 54 | 0.0 | 178.5 | Conditioned merge + Stack | 24 | – | -0.8 | – | 1.0 | – | 0.8 | 0.00 | not timed | ||
| 2A | 90.1-2007 | 0° | 54 | 0.0 | 178.5 | Conditioned merge + Stacked floor zone multiplier | 24 | – | 0.4 | – | 0.9 | – | -0.4 | 0.00 | not timed | ||
| 2A | 90.1-2007 | 45° | 54 | 0.0 | 178.2 | Conditioned merge + Stack | 24 | – | -0.8 | – | 1.0 | – | 0.8 | 0.00 | not timed | ||
| 2A | 90.1-2007 | 45° | 54 | 0.0 | 178.2 | Conditioned merge + Stacked floor zone multiplier | 24 | – | 0.5 | – | 0.9 | – | -0.5 | 0.00 | not timed | ||
| 2A | 90.1-2019 | 0° | 54 | 0.0 | 183.6 | Conditioned merge + Stack | 24 | – | -0.9 | – | 1.1 | – | 0.9 | 0.00 | not timed | ||
| 2A | 90.1-2019 | 0° | 54 | 0.0 | 183.6 | Conditioned merge + Stacked floor zone multiplier | 24 | – | 0.5 | – | 1.0 | – | -0.5 | 0.00 | not timed | ||
| 2A | 90.1-2019 | 45° | 54 | 0.0 | 183.2 | Conditioned merge + Stack | 24 | – | -0.9 | – | 1.2 | – | 0.9 | 0.00 | not timed | ||
| 2A | 90.1-2019 | 45° | 54 | 0.0 | 183.2 | Conditioned merge + Stacked floor zone multiplier | 24 | – | 0.6 | – | 1.0 | – | -0.6 | 0.00 | not timed | ||
| 2B | 90.1-2007 | 0° | 54 | 0.2 | 174.9 | Conditioned merge + Stack | 24 | -38.7 | -0.9 | 182.9 | 1.3 | 38.7 | 0.9 | 0.00 | not timed | ||
| 2B | 90.1-2007 | 0° | 54 | 0.2 | 174.9 | Conditioned merge + Stacked floor zone multiplier | 24 | -35.5 | 0.5 | 159.8 | 0.9 | 35.5 | -0.5 | 0.00 | not timed | ||
| 2B | 90.1-2007 | 45° | 54 | 0.1 | 174.6 | Conditioned merge + Stack | 24 | -39.1 | -0.9 | 174.3 | 1.2 | 39.1 | 0.9 | 0.00 | not timed | ||
| 2B | 90.1-2007 | 45° | 54 | 0.1 | 174.6 | Conditioned merge + Stacked floor zone multiplier | 24 | -39.0 | 0.5 | 172.8 | 0.9 | 39.0 | -0.5 | 0.00 | not timed | ||
| 2B | 90.1-2019 | 0° | 54 | 0.1 | 180.5 | Conditioned merge + Stack | 24 | – | -0.9 | – | 1.3 | – | 0.9 | 0.00 | not timed | ||
| 2B | 90.1-2019 | 0° | 54 | 0.1 | 180.5 | Conditioned merge + Stacked floor zone multiplier | 24 | – | 0.6 | – | 1.1 | – | -0.6 | 0.00 | not timed | ||
| 2B | 90.1-2019 | 45° | 54 | 0.1 | 180.1 | Conditioned merge + Stack | 24 | – | -1.0 | – | 1.3 | – | 1.0 | 0.00 | not timed | ||
| 2B | 90.1-2019 | 45° | 54 | 0.1 | 180.1 | Conditioned merge + Stacked floor zone multiplier | 24 | – | 0.7 | – | 1.1 | – | -0.7 | 0.00 | not timed | ||
| 3C | 90.1-2007 | 0° | 54 | 0.1 | 151.4 | Conditioned merge + Stack | 24 | -33.5 | -1.4 | 151.8 | 1.7 | 33.5 | 1.4 | 0.00 | not timed | ||
| 3C | 90.1-2007 | 0° | 54 | 0.1 | 151.4 | Conditioned merge + Stacked floor zone multiplier | 24 | -32.0 | 0.9 | 135.4 | 1.3 | 32.0 | -0.9 | 0.00 | not timed | ||
| 3C | 90.1-2007 | 45° | 54 | 0.1 | 151.8 | Conditioned merge + Stack | 24 | – | -1.4 | – | 1.6 | – | 1.4 | 0.00 | not timed | ||
| 3C | 90.1-2007 | 45° | 54 | 0.1 | 151.8 | Conditioned merge + Stacked floor zone multiplier | 24 | – | 0.9 | – | 1.2 | – | -0.9 | 0.00 | not timed | ||
| 3C | 90.1-2019 | 0° | 54 | 0.0 | 160.1 | Conditioned merge + Stack | 24 | – | -1.4 | – | 1.8 | – | 1.4 | 0.00 | 0.539 | 0.544 | 1.057 |
| 3C | 90.1-2019 | 0° | 54 | 0.0 | 160.1 | Conditioned merge + Stacked floor zone multiplier | 24 | – | 1.1 | – | 1.5 | – | -1.1 | 0.00 | 0.493 | 0.492 | 0.965 |
| 3C | 90.1-2019 | 45° | 54 | 0.0 | 160.0 | Conditioned merge + Stack | 24 | – | -1.4 | – | 1.8 | – | 1.4 | 0.00 | not timed | ||
| 3C | 90.1-2019 | 45° | 54 | 0.0 | 160.0 | Conditioned merge + Stacked floor zone multiplier | 24 | – | 1.2 | – | 1.5 | – | -1.2 | 0.00 | not timed | ||
| 4A | 90.1-2007 | 0° | 54 | 1.6 | 150.7 | Conditioned merge + Stacked floor zone multiplier | 24 | -8.4 | 1.1 | 25.9 | 1.7 | 8.4 | -1.1 | 0.00 | not timed | ||
| 4A | 90.1-2007 | 45° | 54 | 1.4 | 150.4 | Semantic merge + Stack | 51 | -0.0 | -0.0 | 0.1 | 0.0 | 0.0 | 0.0 | 0.00 | not timed | ||
| 4A | 90.1-2019 | 0° | 54 | 0.8 | 158.2 | Conditioned merge + Stack | 24 | -56.4 | -1.3 | 145.9 | 1.8 | 56.4 | 1.3 | 0.00 | not timed | ||
| 4A | 90.1-2019 | 0° | 54 | 0.8 | 158.2 | Conditioned merge + Stacked floor zone multiplier | 24 | 6.0 | 1.4 | 39.4 | 1.8 | -6.0 | -1.4 | 0.00 | not timed | ||
| 4A | 90.1-2019 | 45° | 54 | 0.8 | 157.6 | Conditioned merge + Stack | 24 | -52.9 | -1.4 | 140.0 | 1.8 | 52.9 | 1.4 | 0.00 | not timed | ||
| 4A | 90.1-2019 | 45° | 54 | 0.8 | 157.6 | Conditioned merge + Stacked floor zone multiplier | 24 | 0.7 | 1.5 | 34.1 | 1.8 | -0.7 | -1.5 | 0.00 | not timed | ||
| 5A | 90.1-2007 | 0° | 54 | 3.3 | 140.2 | Conditioned merge + Stacked floor zone multiplier | 24 | -6.4 | 1.1 | 19.1 | 2.3 | 6.4 | -1.1 | 0.00 | not timed | ||
| 5A | 90.1-2007 | 45° | 54 | 2.9 | 140.4 | Semantic merge + Stack | 51 | -0.0 | -0.0 | 0.1 | 0.0 | 0.0 | 0.0 | 0.00 | not timed | ||
| 5A | 90.1-2019 | 0° | 54 | 1.7 | 148.9 | Conditioned merge + Stacked floor zone multiplier | 24 | 6.2 | 1.6 | 25.7 | 2.1 | -6.2 | -1.6 | 0.00 | 0.491 | 0.490 | 0.965 |
| 5A | 90.1-2019 | 45° | 54 | 1.6 | 148.6 | Conditioned merge + Stacked floor zone multiplier | 24 | 3.2 | 1.8 | 23.7 | 2.2 | -3.2 | -1.8 | 0.00 | not timed | ||
| 7A | 90.1-2007 | 0° | 54 | 5.4 | 138.0 | Semantic merge + Stack | 51 | -0.0 | -0.0 | 0.1 | 0.0 | 0.0 | 0.0 | 0.00 | not timed | ||
| 7A | 90.1-2007 | 45° | 54 | 4.9 | 137.9 | Semantic merge + Stack | 51 | -0.0 | -0.0 | 0.1 | 0.0 | 0.0 | 0.0 | 0.00 | not timed | ||
| 7A | 90.1-2019 | 0° | 54 | 2.9 | 147.3 | Conditioned merge + Stacked floor zone multiplier | 24 | 0.0 | 1.6 | 16.6 | 2.3 | -0.0 | -1.6 | 0.00 | not timed | ||
| 7A | 90.1-2019 | 45° | 54 | 2.7 | 146.9 | Conditioned merge + Stacked floor zone multiplier | 24 | -3.1 | 1.8 | 18.3 | 2.3 | 3.1 | -1.8 | 0.00 | not timed | ||
The coarsest zonings (fewest modelled zones) meeting the threshold; ties are all listed. Errors are the test zoning against the reference: annual sensible load, hourly CV(RMSE) and NMBE, and the change of conditioned floor area. A muted value belongs to a load the threshold does not judge; a dash is a value the runner did not store; a flagged value carries the runner's own flag. The cost ratios are the serial timing pass (R5): the zoning's processor time, wall clock and peak committed memory over its reference's, each the median of its repeats; not timed marks a cell outside the timed ones. Cost protocol.
Every zoning by cell
2A · 90.1-2007 · 0°
Reference 559595d8cdb00e39/R: No simplification + Stack, 54 zones, 18,683 m² conditioned; annual sensible heating 0.0 and cooling 178.5 kWh/m²; peak heating 16.3 and cooling 679.8 kW. Sensible heating is below 1 kWh/m² and is not judged. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Stack | 24 | 0.00 | – | -0.8 | – | 1.0 | – | 0.8 | -47.7 | -0.7 | yes, recommended |
| Conditioned merge + Stacked floor zone multiplier | 24 | 0.00 | – | 0.4 | – | 0.9 | – | -0.4 | -36.1 | 0.2 | yes, recommended |
| Semantic merge + Stack | 51 | 0.00 | – | -0.0 | – | 0.0 | – | 0.0 | -0.0 | -0.0 | yes |
| Semantic merge + Stacked floor zone multiplier | 51 | 0.00 | – | 1.7 | – | 1.8 | – | -1.7 | 58.3 | 0.6 | yes |
| No simplification + Stacked floor zone multiplier | 54 | 0.00 | – | 1.7 | – | 1.9 | – | -1.7 | 58.3 | 0.7 | yes |
18 zonings not generated: the generator refuses them by a documented limit, so they were never simulated
- Conditioned merge + Single zone building: the zoning does not support the prototype's multiplied rooms
- Conditioned merge + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- No simplification + Single zone building: the zoning does not support the prototype's multiplied rooms
- No simplification + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Single zone building: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Stack: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Stacked floor zone multiplier: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Single zone building: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Stack: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Stacked floor zone multiplier: the zoning does not support the prototype's multiplied rooms
- Semantic merge + Single zone building: the zoning does not support the prototype's multiplied rooms
- Semantic merge + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Single zone building: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Stack: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Stacked floor zone multiplier: the zoning does not support the prototype's multiplied rooms
2A · 90.1-2007 · 45°
Reference 1a61d27a7e2b783c/R: No simplification + Stack, 54 zones, 18,683 m² conditioned; annual sensible heating 0.0 and cooling 178.2 kWh/m²; peak heating 14.3 and cooling 672.0 kW. Sensible heating is below 1 kWh/m² and is not judged. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Stack | 24 | 0.00 | – | -0.8 | – | 1.0 | – | 0.8 | -35.7 | -0.6 | yes, recommended |
| Conditioned merge + Stacked floor zone multiplier | 24 | 0.00 | – | 0.5 | – | 0.9 | – | -0.5 | -35.4 | 0.3 | yes, recommended |
| Semantic merge + Stack | 51 | 0.00 | – | -0.0 | – | 0.0 | – | 0.0 | 0.0 | -0.0 | yes |
| Semantic merge + Stacked floor zone multiplier | 51 | 0.00 | – | 1.8 | – | 2.0 | – | -1.8 | 69.0 | 0.6 | yes |
| No simplification + Stacked floor zone multiplier | 54 | 0.00 | – | 1.8 | – | 2.0 | – | -1.8 | 69.0 | 0.6 | yes |
18 zonings not generated: the generator refuses them by a documented limit, so they were never simulated
- Conditioned merge + Single zone building: the zoning does not support the prototype's multiplied rooms
- Conditioned merge + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- No simplification + Single zone building: the zoning does not support the prototype's multiplied rooms
- No simplification + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Single zone building: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Stack: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Stacked floor zone multiplier: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Single zone building: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Stack: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Stacked floor zone multiplier: the zoning does not support the prototype's multiplied rooms
- Semantic merge + Single zone building: the zoning does not support the prototype's multiplied rooms
- Semantic merge + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Single zone building: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Stack: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Stacked floor zone multiplier: the zoning does not support the prototype's multiplied rooms
2A · 90.1-2019 · 0°
Reference 1f431c9d05b3d958/R: No simplification + Stack, 54 zones, 18,683 m² conditioned; annual sensible heating 0.0 and cooling 183.6 kWh/m²; peak heating 7.3 and cooling 660.8 kW. Sensible heating is below 1 kWh/m² and is not judged. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Stack | 24 | 0.00 | – | -0.9 | – | 1.1 | – | 0.9 | -54.9 | -0.6 | yes, recommended |
| Conditioned merge + Stacked floor zone multiplier | 24 | 0.00 | – | 0.5 | – | 1.0 | – | -0.5 | -37.1 | 0.4 | yes, recommended |
| Semantic merge + Stack | 51 | 0.00 | – | -0.0 | – | 0.0 | – | 0.0 | -0.0 | -0.0 | yes |
| Semantic merge + Stacked floor zone multiplier | 51 | 0.00 | – | 2.0 | – | 2.2 | – | -2.0 | 130.2 | 1.1 | yes |
| No simplification + Stacked floor zone multiplier | 54 | 0.00 | – | 2.0 | – | 2.2 | – | -2.0 | 130.2 | 1.1 | yes |
18 zonings not generated: the generator refuses them by a documented limit, so they were never simulated
- Conditioned merge + Single zone building: the zoning does not support the prototype's multiplied rooms
- Conditioned merge + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- No simplification + Single zone building: the zoning does not support the prototype's multiplied rooms
- No simplification + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Single zone building: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Stack: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Stacked floor zone multiplier: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Single zone building: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Stack: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Stacked floor zone multiplier: the zoning does not support the prototype's multiplied rooms
- Semantic merge + Single zone building: the zoning does not support the prototype's multiplied rooms
- Semantic merge + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Single zone building: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Stack: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Stacked floor zone multiplier: the zoning does not support the prototype's multiplied rooms
2A · 90.1-2019 · 45°
Reference dfbd24ff36e4752c/R: No simplification + Stack, 54 zones, 18,683 m² conditioned; annual sensible heating 0.0 and cooling 183.2 kWh/m²; peak heating 6.5 and cooling 655.8 kW. Sensible heating is below 1 kWh/m² and is not judged. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Stack | 24 | 0.00 | – | -0.9 | – | 1.2 | – | 0.9 | -47.5 | -0.7 | yes, recommended |
| Conditioned merge + Stacked floor zone multiplier | 24 | 0.00 | – | 0.6 | – | 1.0 | – | -0.6 | -47.5 | 0.3 | yes, recommended |
| Semantic merge + Stack | 51 | 0.00 | – | -0.0 | – | 0.0 | – | 0.0 | -0.0 | -0.0 | yes |
| Semantic merge + Stacked floor zone multiplier | 51 | 0.00 | – | 2.1 | – | 2.3 | – | -2.1 | 146.3 | 1.3 | yes |
| No simplification + Stacked floor zone multiplier | 54 | 0.00 | – | 2.1 | – | 2.3 | – | -2.1 | 146.3 | 1.3 | yes |
18 zonings not generated: the generator refuses them by a documented limit, so they were never simulated
- Conditioned merge + Single zone building: the zoning does not support the prototype's multiplied rooms
- Conditioned merge + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- No simplification + Single zone building: the zoning does not support the prototype's multiplied rooms
- No simplification + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Single zone building: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Stack: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Stacked floor zone multiplier: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Single zone building: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Stack: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Stacked floor zone multiplier: the zoning does not support the prototype's multiplied rooms
- Semantic merge + Single zone building: the zoning does not support the prototype's multiplied rooms
- Semantic merge + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Single zone building: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Stack: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Stacked floor zone multiplier: the zoning does not support the prototype's multiplied rooms
2B · 90.1-2007 · 0°
Reference ad8fe8294a818a0e/R: No simplification + Stack, 54 zones, 18,683 m² conditioned; annual sensible heating 0.2 and cooling 174.9 kWh/m²; peak heating 23.7 and cooling 720.0 kW. Sensible heating is below 1 kWh/m² and is not judged. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Stack | 24 | 0.00 | -38.7 | -0.9 | 182.9 | 1.3 | 38.7 | 0.9 | -37.4 | -0.7 | yes, recommended |
| Conditioned merge + Stacked floor zone multiplier | 24 | 0.00 | -35.5 | 0.5 | 159.8 | 0.9 | 35.5 | -0.5 | -23.0 | 0.1 | yes, recommended |
| Semantic merge + Stack | 51 | 0.00 | -0.0 | -0.0 | 0.1 | 0.0 | 0.0 | 0.0 | -0.0 | -0.0 | yes |
| Semantic merge + Stacked floor zone multiplier | 51 | 0.00 | 267.0 | 1.8 | 642.3 | 2.0 | -267.0 | -1.8 | 41.2 | 0.7 | yes |
| No simplification + Stacked floor zone multiplier | 54 | 0.00 | 267.1 | 1.8 | 642.5 | 2.0 | -267.1 | -1.8 | 41.2 | 0.7 | yes |
18 zonings not generated: the generator refuses them by a documented limit, so they were never simulated
- Conditioned merge + Single zone building: the zoning does not support the prototype's multiplied rooms
- Conditioned merge + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- No simplification + Single zone building: the zoning does not support the prototype's multiplied rooms
- No simplification + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Single zone building: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Stack: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Stacked floor zone multiplier: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Single zone building: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Stack: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Stacked floor zone multiplier: the zoning does not support the prototype's multiplied rooms
- Semantic merge + Single zone building: the zoning does not support the prototype's multiplied rooms
- Semantic merge + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Single zone building: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Stack: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Stacked floor zone multiplier: the zoning does not support the prototype's multiplied rooms
2B · 90.1-2007 · 45°
Reference 54a8de10204d42b8/R: No simplification + Stack, 54 zones, 18,683 m² conditioned; annual sensible heating 0.1 and cooling 174.6 kWh/m²; peak heating 23.1 and cooling 711.0 kW. Sensible heating is below 1 kWh/m² and is not judged. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Stack | 24 | 0.00 | -39.1 | -0.9 | 174.3 | 1.2 | 39.1 | 0.9 | -30.2 | -0.7 | yes, recommended |
| Conditioned merge + Stacked floor zone multiplier | 24 | 0.00 | -39.0 | 0.5 | 172.8 | 0.9 | 39.0 | -0.5 | -30.2 | 0.2 | yes, recommended |
| Semantic merge + Stack | 51 | 0.00 | -0.0 | -0.0 | 0.1 | 0.0 | 0.0 | 0.0 | -0.0 | -0.0 | yes |
| Semantic merge + Stacked floor zone multiplier | 51 | 0.00 | 297.0 | 1.9 | 685.8 | 2.1 | -297.0 | -1.9 | 41.4 | 0.7 | yes |
| No simplification + Stacked floor zone multiplier | 54 | 0.00 | 297.0 | 1.9 | 685.8 | 2.1 | -297.0 | -1.9 | 41.4 | 0.7 | yes |
18 zonings not generated: the generator refuses them by a documented limit, so they were never simulated
- Conditioned merge + Single zone building: the zoning does not support the prototype's multiplied rooms
- Conditioned merge + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- No simplification + Single zone building: the zoning does not support the prototype's multiplied rooms
- No simplification + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Single zone building: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Stack: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Stacked floor zone multiplier: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Single zone building: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Stack: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Stacked floor zone multiplier: the zoning does not support the prototype's multiplied rooms
- Semantic merge + Single zone building: the zoning does not support the prototype's multiplied rooms
- Semantic merge + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Single zone building: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Stack: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Stacked floor zone multiplier: the zoning does not support the prototype's multiplied rooms
2B · 90.1-2019 · 0°
Reference 5a09a9729344d8d5/R: No simplification + Stack, 54 zones, 18,683 m² conditioned; annual sensible heating 0.1 and cooling 180.5 kWh/m²; peak heating 9.1 and cooling 693.9 kW. Sensible heating is below 1 kWh/m² and is not judged. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Stack | 24 | 0.00 | – | -0.9 | – | 1.3 | – | 0.9 | -54.1 | -0.7 | yes, recommended |
| Conditioned merge + Stacked floor zone multiplier | 24 | 0.00 | – | 0.6 | – | 1.1 | – | -0.6 | -27.3 | 0.2 | yes, recommended |
| Semantic merge + Stack | 51 | 0.00 | – | -0.0 | – | 0.0 | – | 0.0 | -0.0 | -0.0 | yes |
| Semantic merge + Stacked floor zone multiplier | 51 | 0.00 | – | 2.1 | – | 2.3 | – | -2.1 | 107.5 | 0.7 | yes |
| No simplification + Stacked floor zone multiplier | 54 | 0.00 | – | 2.1 | – | 2.3 | – | -2.1 | 107.5 | 0.7 | yes |
18 zonings not generated: the generator refuses them by a documented limit, so they were never simulated
- Conditioned merge + Single zone building: the zoning does not support the prototype's multiplied rooms
- Conditioned merge + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- No simplification + Single zone building: the zoning does not support the prototype's multiplied rooms
- No simplification + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Single zone building: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Stack: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Stacked floor zone multiplier: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Single zone building: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Stack: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Stacked floor zone multiplier: the zoning does not support the prototype's multiplied rooms
- Semantic merge + Single zone building: the zoning does not support the prototype's multiplied rooms
- Semantic merge + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Single zone building: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Stack: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Stacked floor zone multiplier: the zoning does not support the prototype's multiplied rooms
2B · 90.1-2019 · 45°
Reference 53ad7e17f812954b/R: No simplification + Stack, 54 zones, 18,683 m² conditioned; annual sensible heating 0.1 and cooling 180.1 kWh/m²; peak heating 9.4 and cooling 687.9 kW. Sensible heating is below 1 kWh/m² and is not judged. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Stack | 24 | 0.00 | – | -1.0 | – | 1.3 | – | 1.0 | -48.7 | -0.6 | yes, recommended |
| Conditioned merge + Stacked floor zone multiplier | 24 | 0.00 | – | 0.7 | – | 1.1 | – | -0.7 | -37.6 | 0.4 | yes, recommended |
| Semantic merge + Stack | 51 | 0.00 | – | -0.0 | – | 0.0 | – | 0.0 | -0.0 | -0.0 | yes |
| Semantic merge + Stacked floor zone multiplier | 51 | 0.00 | – | 2.2 | – | 2.4 | – | -2.2 | 98.5 | 1.0 | yes |
| No simplification + Stacked floor zone multiplier | 54 | 0.00 | – | 2.2 | – | 2.4 | – | -2.2 | 98.5 | 1.0 | yes |
18 zonings not generated: the generator refuses them by a documented limit, so they were never simulated
- Conditioned merge + Single zone building: the zoning does not support the prototype's multiplied rooms
- Conditioned merge + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- No simplification + Single zone building: the zoning does not support the prototype's multiplied rooms
- No simplification + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Single zone building: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Stack: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Stacked floor zone multiplier: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Single zone building: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Stack: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Stacked floor zone multiplier: the zoning does not support the prototype's multiplied rooms
- Semantic merge + Single zone building: the zoning does not support the prototype's multiplied rooms
- Semantic merge + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Single zone building: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Stack: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Stacked floor zone multiplier: the zoning does not support the prototype's multiplied rooms
3C · 90.1-2007 · 0°
Reference 79673fdc7713c383/R: No simplification + Stack, 54 zones, 18,683 m² conditioned; annual sensible heating 0.1 and cooling 151.4 kWh/m²; peak heating 11.1 and cooling 603.8 kW. Sensible heating is below 1 kWh/m² and is not judged. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Stack | 24 | 0.00 | -33.5 | -1.4 | 151.8 | 1.7 | 33.5 | 1.4 | -45.3 | -0.7 | yes, recommended |
| Conditioned merge + Stacked floor zone multiplier | 24 | 0.00 | -32.0 | 0.9 | 135.4 | 1.3 | 32.0 | -0.9 | -19.7 | 0.3 | yes, recommended |
| Semantic merge + Stack | 51 | 0.00 | -0.0 | -0.0 | 0.1 | 0.0 | 0.0 | 0.0 | -0.0 | -0.0 | yes |
| Semantic merge + Stacked floor zone multiplier | 51 | 0.00 | 780.1 | 2.7 | 1,344.1 | 2.8 | -780.1 | -2.7 | 79.3 | 1.3 | yes |
| No simplification + Stacked floor zone multiplier | 54 | 0.00 | 780.2 | 2.7 | 1,344.2 | 2.8 | -780.2 | -2.7 | 79.3 | 1.3 | yes |
18 zonings not generated: the generator refuses them by a documented limit, so they were never simulated
- Conditioned merge + Single zone building: the zoning does not support the prototype's multiplied rooms
- Conditioned merge + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- No simplification + Single zone building: the zoning does not support the prototype's multiplied rooms
- No simplification + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Single zone building: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Stack: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Stacked floor zone multiplier: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Single zone building: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Stack: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Stacked floor zone multiplier: the zoning does not support the prototype's multiplied rooms
- Semantic merge + Single zone building: the zoning does not support the prototype's multiplied rooms
- Semantic merge + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Single zone building: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Stack: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Stacked floor zone multiplier: the zoning does not support the prototype's multiplied rooms
3C · 90.1-2007 · 45°
Reference be5a63ffa7c14c27/R: No simplification + Stack, 54 zones, 18,683 m² conditioned; annual sensible heating 0.1 and cooling 151.8 kWh/m²; peak heating 10.5 and cooling 599.0 kW. Sensible heating is below 1 kWh/m² and is not judged. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Stack | 24 | 0.00 | – | -1.4 | – | 1.6 | – | 1.4 | -36.4 | -0.6 | yes, recommended |
| Conditioned merge + Stacked floor zone multiplier | 24 | 0.00 | – | 0.9 | – | 1.2 | – | -0.9 | -36.6 | 0.1 | yes, recommended |
| Semantic merge + Stack | 51 | 0.00 | – | -0.0 | – | 0.0 | – | 0.0 | -0.0 | -0.0 | yes |
| Semantic merge + Stacked floor zone multiplier | 51 | 0.00 | – | 2.6 | – | 2.8 | – | -2.6 | 83.5 | 1.7 | yes |
| No simplification + Stacked floor zone multiplier | 54 | 0.00 | – | 2.6 | – | 2.8 | – | -2.6 | 83.5 | 1.7 | yes |
18 zonings not generated: the generator refuses them by a documented limit, so they were never simulated
- Conditioned merge + Single zone building: the zoning does not support the prototype's multiplied rooms
- Conditioned merge + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- No simplification + Single zone building: the zoning does not support the prototype's multiplied rooms
- No simplification + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Single zone building: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Stack: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Stacked floor zone multiplier: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Single zone building: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Stack: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Stacked floor zone multiplier: the zoning does not support the prototype's multiplied rooms
- Semantic merge + Single zone building: the zoning does not support the prototype's multiplied rooms
- Semantic merge + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Single zone building: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Stack: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Stacked floor zone multiplier: the zoning does not support the prototype's multiplied rooms
3C · 90.1-2019 · 0°
Reference 1c52309d4baa237d/R: No simplification + Stack, 54 zones, 18,683 m² conditioned; annual sensible heating 0.0 and cooling 160.1 kWh/m²; peak heating 6.6 and cooling 599.4 kW. Sensible heating is below 1 kWh/m² and is not judged. Serial cost (R5): processor time 20.9 s, wall clock 21.2 s, peak committed memory 237 MiB, each the median of 3 repeats (processor-time CV 0.3 %); a zoning's ratios are its own medians over the reference's.
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | CPU ratio | Wall ratio | Memory ratio | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Stack | 24 | 0.00 | – | -1.4 | – | 1.8 | – | 1.4 | -48.6 | -0.6 | 0.539 | 0.544 | 1.057 | yes, recommended |
| Conditioned merge + Stacked floor zone multiplier | 24 | 0.00 | – | 1.1 | – | 1.5 | – | -1.1 | -12.0 | 0.1 | 0.493 | 0.492 | 0.965 | yes, recommended |
| Semantic merge + Stack | 51 | 0.00 | – | -0.0 | – | 0.0 | – | 0.0 | -0.0 | -0.0 | 0.965 | 0.964 | 0.997 | yes |
| Semantic merge + Stacked floor zone multiplier | 51 | 0.00 | – | 2.8 | – | 3.0 | – | -2.8 | 130.2 | 2.1 | 0.873 | 0.871 | 1.045 | yes |
| No simplification + Stacked floor zone multiplier | 54 | 0.00 | – | 2.8 | – | 3.0 | – | -2.8 | 130.2 | 2.1 | 0.905 | 0.901 | 0.969 | yes |
18 zonings not generated: the generator refuses them by a documented limit, so they were never simulated
- Conditioned merge + Single zone building: the zoning does not support the prototype's multiplied rooms
- Conditioned merge + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- No simplification + Single zone building: the zoning does not support the prototype's multiplied rooms
- No simplification + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Single zone building: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Stack: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Stacked floor zone multiplier: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Single zone building: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Stack: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Stacked floor zone multiplier: the zoning does not support the prototype's multiplied rooms
- Semantic merge + Single zone building: the zoning does not support the prototype's multiplied rooms
- Semantic merge + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Single zone building: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Stack: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Stacked floor zone multiplier: the zoning does not support the prototype's multiplied rooms
3C · 90.1-2019 · 45°
Reference d70ced7841b1af48/R: No simplification + Stack, 54 zones, 18,683 m² conditioned; annual sensible heating 0.0 and cooling 160.0 kWh/m²; peak heating 6.1 and cooling 596.5 kW. Sensible heating is below 1 kWh/m² and is not judged. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Stack | 24 | 0.00 | – | -1.4 | – | 1.8 | – | 1.4 | -45.3 | -0.9 | yes, recommended |
| Conditioned merge + Stacked floor zone multiplier | 24 | 0.00 | – | 1.2 | – | 1.5 | – | -1.2 | -31.7 | -0.4 | yes, recommended |
| Semantic merge + Stack | 51 | 0.00 | – | -0.0 | – | 0.0 | – | 0.0 | -0.0 | -0.0 | yes |
| Semantic merge + Stacked floor zone multiplier | 51 | 0.00 | – | 2.9 | – | 3.0 | – | -2.9 | 138.2 | 2.2 | yes |
| No simplification + Stacked floor zone multiplier | 54 | 0.00 | – | 2.9 | – | 3.0 | – | -2.9 | 138.2 | 2.2 | yes |
18 zonings not generated: the generator refuses them by a documented limit, so they were never simulated
- Conditioned merge + Single zone building: the zoning does not support the prototype's multiplied rooms
- Conditioned merge + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- No simplification + Single zone building: the zoning does not support the prototype's multiplied rooms
- No simplification + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Single zone building: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Stack: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Stacked floor zone multiplier: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Single zone building: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Stack: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Stacked floor zone multiplier: the zoning does not support the prototype's multiplied rooms
- Semantic merge + Single zone building: the zoning does not support the prototype's multiplied rooms
- Semantic merge + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Single zone building: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Stack: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Stacked floor zone multiplier: the zoning does not support the prototype's multiplied rooms
4A · 90.1-2007 · 0°
Reference c33f8469b176be43/R: No simplification + Stack, 54 zones, 18,683 m² conditioned; annual sensible heating 1.6 and cooling 150.7 kWh/m²; peak heating 70.8 and cooling 685.3 kW. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Stack | 24 | 0.00 | -39.6 | -1.5 | 101.7 | 2.0 | 39.6 | 1.5 | -29.6 | -0.7 | no |
| Conditioned merge + Stacked floor zone multiplier | 24 | 0.00 | -8.4 | 1.1 | 25.9 | 1.7 | 8.4 | -1.1 | -9.0 | 0.2 | yes, recommended |
| Semantic merge + Stack | 51 | 0.00 | -0.0 | -0.0 | 0.1 | 0.0 | 0.0 | 0.0 | -0.0 | -0.0 | yes |
| Semantic merge + Stacked floor zone multiplier | 51 | 0.00 | 89.5 | 2.9 | 145.6 | 3.2 | -89.5 | -2.9 | 24.5 | 0.7 | no |
| No simplification + Stacked floor zone multiplier | 54 | 0.00 | 89.5 | 2.9 | 145.6 | 3.2 | -89.5 | -2.9 | 24.5 | 0.7 | no |
18 zonings not generated: the generator refuses them by a documented limit, so they were never simulated
- Conditioned merge + Single zone building: the zoning does not support the prototype's multiplied rooms
- Conditioned merge + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- No simplification + Single zone building: the zoning does not support the prototype's multiplied rooms
- No simplification + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Single zone building: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Stack: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Stacked floor zone multiplier: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Single zone building: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Stack: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Stacked floor zone multiplier: the zoning does not support the prototype's multiplied rooms
- Semantic merge + Single zone building: the zoning does not support the prototype's multiplied rooms
- Semantic merge + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Single zone building: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Stack: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Stacked floor zone multiplier: the zoning does not support the prototype's multiplied rooms
4A · 90.1-2007 · 45°
Reference db011b6aab90e077/R: No simplification + Stack, 54 zones, 18,683 m² conditioned; annual sensible heating 1.4 and cooling 150.4 kWh/m²; peak heating 64.8 and cooling 673.6 kW. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Stack | 24 | 0.00 | -35.4 | -1.5 | 92.7 | 2.0 | 35.4 | 1.5 | -32.0 | -0.6 | no |
| Conditioned merge + Stacked floor zone multiplier | 24 | 0.00 | -14.2 | 1.1 | 35.0 | 1.6 | 14.2 | -1.1 | -10.7 | 0.3 | no |
| Semantic merge + Stack | 51 | 0.00 | -0.0 | -0.0 | 0.1 | 0.0 | 0.0 | 0.0 | -0.1 | -0.0 | yes, recommended |
| Semantic merge + Stacked floor zone multiplier | 51 | 0.00 | 96.4 | 3.0 | 155.3 | 3.2 | -96.4 | -3.0 | 26.2 | 0.9 | no |
| No simplification + Stacked floor zone multiplier | 54 | 0.00 | 96.4 | 3.0 | 155.3 | 3.2 | -96.4 | -3.0 | 26.2 | 0.9 | no |
18 zonings not generated: the generator refuses them by a documented limit, so they were never simulated
- Conditioned merge + Single zone building: the zoning does not support the prototype's multiplied rooms
- Conditioned merge + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- No simplification + Single zone building: the zoning does not support the prototype's multiplied rooms
- No simplification + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Single zone building: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Stack: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Stacked floor zone multiplier: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Single zone building: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Stack: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Stacked floor zone multiplier: the zoning does not support the prototype's multiplied rooms
- Semantic merge + Single zone building: the zoning does not support the prototype's multiplied rooms
- Semantic merge + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Single zone building: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Stack: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Stacked floor zone multiplier: the zoning does not support the prototype's multiplied rooms
4A · 90.1-2019 · 0°
Reference de2210d5223bd44d/R: No simplification + Stack, 54 zones, 18,683 m² conditioned; annual sensible heating 0.8 and cooling 158.2 kWh/m²; peak heating 40.4 and cooling 666.6 kW. Sensible heating is below 1 kWh/m² and is not judged. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Stack | 24 | 0.00 | -56.4 | -1.3 | 145.9 | 1.8 | 56.4 | 1.3 | -40.5 | -0.6 | yes, recommended |
| Conditioned merge + Stacked floor zone multiplier | 24 | 0.00 | 6.0 | 1.4 | 39.4 | 1.8 | -6.0 | -1.4 | -1.4 | 0.3 | yes, recommended |
| Semantic merge + Stack | 51 | 0.00 | -0.0 | -0.0 | 0.1 | 0.0 | 0.0 | 0.0 | -0.0 | -0.0 | yes |
| Semantic merge + Stacked floor zone multiplier | 51 | 0.00 | 218.9 | 3.0 | 311.6 | 3.2 | -218.9 | -3.0 | 28.2 | 1.0 | yes |
| No simplification + Stacked floor zone multiplier | 54 | 0.00 | 218.9 | 3.0 | 311.6 | 3.2 | -218.9 | -3.0 | 28.2 | 1.0 | yes |
18 zonings not generated: the generator refuses them by a documented limit, so they were never simulated
- Conditioned merge + Single zone building: the zoning does not support the prototype's multiplied rooms
- Conditioned merge + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- No simplification + Single zone building: the zoning does not support the prototype's multiplied rooms
- No simplification + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Single zone building: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Stack: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Stacked floor zone multiplier: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Single zone building: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Stack: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Stacked floor zone multiplier: the zoning does not support the prototype's multiplied rooms
- Semantic merge + Single zone building: the zoning does not support the prototype's multiplied rooms
- Semantic merge + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Single zone building: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Stack: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Stacked floor zone multiplier: the zoning does not support the prototype's multiplied rooms
4A · 90.1-2019 · 45°
Reference c4214f97756a68ff/R: No simplification + Stack, 54 zones, 18,683 m² conditioned; annual sensible heating 0.8 and cooling 157.6 kWh/m²; peak heating 37.3 and cooling 656.8 kW. Sensible heating is below 1 kWh/m² and is not judged. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Stack | 24 | 0.00 | -52.9 | -1.4 | 140.0 | 1.8 | 52.9 | 1.4 | -41.0 | -0.6 | yes, recommended |
| Conditioned merge + Stacked floor zone multiplier | 24 | 0.00 | 0.7 | 1.5 | 34.1 | 1.8 | -0.7 | -1.5 | -3.0 | 0.3 | yes, recommended |
| Semantic merge + Stack | 51 | 0.00 | -0.0 | -0.0 | 0.1 | 0.0 | 0.0 | 0.0 | -0.0 | -0.0 | yes |
| Semantic merge + Stacked floor zone multiplier | 51 | 0.00 | 247.2 | 3.1 | 336.6 | 3.3 | -247.2 | -3.1 | 31.0 | 1.6 | yes |
| No simplification + Stacked floor zone multiplier | 54 | 0.00 | 247.2 | 3.1 | 336.6 | 3.3 | -247.2 | -3.1 | 31.0 | 1.6 | yes |
18 zonings not generated: the generator refuses them by a documented limit, so they were never simulated
- Conditioned merge + Single zone building: the zoning does not support the prototype's multiplied rooms
- Conditioned merge + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- No simplification + Single zone building: the zoning does not support the prototype's multiplied rooms
- No simplification + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Single zone building: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Stack: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Stacked floor zone multiplier: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Single zone building: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Stack: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Stacked floor zone multiplier: the zoning does not support the prototype's multiplied rooms
- Semantic merge + Single zone building: the zoning does not support the prototype's multiplied rooms
- Semantic merge + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Single zone building: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Stack: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Stacked floor zone multiplier: the zoning does not support the prototype's multiplied rooms
5A · 90.1-2007 · 0°
Reference c21fd95e3205b0bc/R: No simplification + Stack, 54 zones, 18,683 m² conditioned; annual sensible heating 3.3 and cooling 140.2 kWh/m²; peak heating 97.7 and cooling 670.3 kW. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Stack | 24 | 0.00 | -36.6 | -2.1 | 79.3 | 2.9 | 36.6 | 2.1 | -26.1 | -0.6 | no |
| Conditioned merge + Stacked floor zone multiplier | 24 | 0.00 | -6.4 | 1.1 | 19.1 | 2.3 | 6.4 | -1.1 | -13.1 | 0.3 | yes, recommended |
| Semantic merge + Stack | 51 | 0.00 | -0.0 | -0.0 | 0.1 | 0.0 | 0.0 | 0.0 | -0.0 | -0.0 | yes |
| Semantic merge + Stacked floor zone multiplier | 51 | 0.00 | 61.8 | 3.6 | 93.4 | 4.0 | -61.8 | -3.6 | 24.4 | 0.7 | no |
| No simplification + Stacked floor zone multiplier | 54 | 0.00 | 61.8 | 3.6 | 93.4 | 4.0 | -61.8 | -3.6 | 24.4 | 0.7 | no |
18 zonings not generated: the generator refuses them by a documented limit, so they were never simulated
- Conditioned merge + Single zone building: the zoning does not support the prototype's multiplied rooms
- Conditioned merge + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- No simplification + Single zone building: the zoning does not support the prototype's multiplied rooms
- No simplification + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Single zone building: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Stack: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Stacked floor zone multiplier: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Single zone building: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Stack: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Stacked floor zone multiplier: the zoning does not support the prototype's multiplied rooms
- Semantic merge + Single zone building: the zoning does not support the prototype's multiplied rooms
- Semantic merge + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Single zone building: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Stack: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Stacked floor zone multiplier: the zoning does not support the prototype's multiplied rooms
5A · 90.1-2007 · 45°
Reference 22ae911f052f805e/R: No simplification + Stack, 54 zones, 18,683 m² conditioned; annual sensible heating 2.9 and cooling 140.4 kWh/m²; peak heating 89.4 and cooling 655.2 kW. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Stack | 24 | 0.00 | -33.8 | -2.0 | 77.3 | 2.7 | 33.8 | 2.0 | -29.3 | -0.5 | no |
| Conditioned merge + Stacked floor zone multiplier | 24 | 0.00 | -10.0 | 1.2 | 24.1 | 2.1 | 10.0 | -1.2 | -14.3 | 0.4 | no |
| Semantic merge + Stack | 51 | 0.00 | -0.0 | -0.0 | 0.1 | 0.0 | 0.0 | 0.0 | -0.0 | -0.0 | yes, recommended |
| Semantic merge + Stacked floor zone multiplier | 51 | 0.00 | 67.1 | 3.6 | 100.1 | 3.9 | -67.1 | -3.6 | 24.5 | 1.3 | no |
| No simplification + Stacked floor zone multiplier | 54 | 0.00 | 67.1 | 3.6 | 100.1 | 3.9 | -67.1 | -3.6 | 24.5 | 1.3 | no |
18 zonings not generated: the generator refuses them by a documented limit, so they were never simulated
- Conditioned merge + Single zone building: the zoning does not support the prototype's multiplied rooms
- Conditioned merge + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- No simplification + Single zone building: the zoning does not support the prototype's multiplied rooms
- No simplification + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Single zone building: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Stack: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Stacked floor zone multiplier: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Single zone building: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Stack: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Stacked floor zone multiplier: the zoning does not support the prototype's multiplied rooms
- Semantic merge + Single zone building: the zoning does not support the prototype's multiplied rooms
- Semantic merge + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Single zone building: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Stack: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Stacked floor zone multiplier: the zoning does not support the prototype's multiplied rooms
5A · 90.1-2019 · 0°
Reference 3194069c6ebf0d02/R: No simplification + Stack, 54 zones, 18,683 m² conditioned; annual sensible heating 1.7 and cooling 148.9 kWh/m²; peak heating 62.6 and cooling 658.1 kW. Serial cost (R5): processor time 20.9 s, wall clock 21.4 s, peak committed memory 237 MiB, each the median of 3 repeats (processor-time CV 0.7 %); a zoning's ratios are its own medians over the reference's.
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | CPU ratio | Wall ratio | Memory ratio | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Stack | 24 | 0.00 | -52.2 | -1.6 | 113.3 | 2.2 | 52.2 | 1.6 | -25.0 | -0.6 | 0.538 | 0.535 | 1.054 | no |
| Conditioned merge + Stacked floor zone multiplier | 24 | 0.00 | 6.2 | 1.6 | 25.7 | 2.1 | -6.2 | -1.6 | -3.5 | 0.4 | 0.491 | 0.490 | 0.965 | yes, recommended |
| Semantic merge + Stack | 51 | 0.00 | -0.0 | -0.0 | 0.1 | 0.0 | 0.0 | 0.0 | -0.0 | -0.0 | 0.975 | 0.970 | 0.997 | yes |
| Semantic merge + Stacked floor zone multiplier | 51 | 0.00 | 129.3 | 3.5 | 170.3 | 3.7 | -129.3 | -3.5 | 24.5 | 1.3 | 0.877 | 0.874 | 1.044 | no |
| No simplification + Stacked floor zone multiplier | 54 | 0.00 | 129.3 | 3.5 | 170.3 | 3.7 | -129.3 | -3.5 | 24.5 | 1.3 | 0.907 | 0.905 | 0.967 | no |
18 zonings not generated: the generator refuses them by a documented limit, so they were never simulated
- Conditioned merge + Single zone building: the zoning does not support the prototype's multiplied rooms
- Conditioned merge + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- No simplification + Single zone building: the zoning does not support the prototype's multiplied rooms
- No simplification + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Single zone building: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Stack: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Stacked floor zone multiplier: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Single zone building: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Stack: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Stacked floor zone multiplier: the zoning does not support the prototype's multiplied rooms
- Semantic merge + Single zone building: the zoning does not support the prototype's multiplied rooms
- Semantic merge + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Single zone building: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Stack: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Stacked floor zone multiplier: the zoning does not support the prototype's multiplied rooms
5A · 90.1-2019 · 45°
Reference 97a83c28c015a071/R: No simplification + Stack, 54 zones, 18,683 m² conditioned; annual sensible heating 1.6 and cooling 148.6 kWh/m²; peak heating 59.8 and cooling 643.2 kW. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Stack | 24 | 0.00 | -50.6 | -1.6 | 114.0 | 2.2 | 50.6 | 1.6 | -27.8 | -0.6 | no |
| Conditioned merge + Stacked floor zone multiplier | 24 | 0.00 | 3.2 | 1.8 | 23.7 | 2.2 | -3.2 | -1.8 | -4.8 | 0.2 | yes, recommended |
| Semantic merge + Stack | 51 | 0.00 | -0.0 | -0.0 | 0.1 | 0.0 | 0.0 | 0.0 | -0.0 | -0.0 | yes |
| Semantic merge + Stacked floor zone multiplier | 51 | 0.00 | 149.1 | 3.5 | 188.2 | 3.7 | -149.1 | -3.5 | 23.9 | 1.9 | no |
| No simplification + Stacked floor zone multiplier | 54 | 0.00 | 149.1 | 3.5 | 188.1 | 3.7 | -149.1 | -3.5 | 23.9 | 1.9 | no |
18 zonings not generated: the generator refuses them by a documented limit, so they were never simulated
- Conditioned merge + Single zone building: the zoning does not support the prototype's multiplied rooms
- Conditioned merge + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- No simplification + Single zone building: the zoning does not support the prototype's multiplied rooms
- No simplification + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Single zone building: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Stack: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Stacked floor zone multiplier: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Single zone building: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Stack: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Stacked floor zone multiplier: the zoning does not support the prototype's multiplied rooms
- Semantic merge + Single zone building: the zoning does not support the prototype's multiplied rooms
- Semantic merge + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Single zone building: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Stack: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Stacked floor zone multiplier: the zoning does not support the prototype's multiplied rooms
7A · 90.1-2007 · 0°
Reference a73f9214dc9865fe/R: No simplification + Stack, 54 zones, 18,683 m² conditioned; annual sensible heating 5.4 and cooling 138.0 kWh/m²; peak heating 125.6 and cooling 690.3 kW. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Stack | 24 | 0.00 | -35.2 | -2.5 | 74.0 | 3.9 | 35.2 | 2.5 | -31.2 | -0.6 | no |
| Conditioned merge + Stacked floor zone multiplier | 24 | 0.00 | -11.9 | 0.9 | 31.1 | 3.2 | 11.9 | -0.9 | -21.0 | 0.3 | no |
| Semantic merge + Stack | 51 | 0.00 | -0.0 | -0.0 | 0.1 | 0.0 | 0.0 | 0.0 | -0.0 | -0.0 | yes, recommended |
| Semantic merge + Stacked floor zone multiplier | 51 | 0.00 | 49.4 | 4.1 | 78.0 | 4.7 | -49.4 | -4.1 | 21.4 | 0.7 | no |
| No simplification + Stacked floor zone multiplier | 54 | 0.00 | 49.4 | 4.1 | 78.0 | 4.7 | -49.4 | -4.1 | 21.4 | 0.7 | no |
18 zonings not generated: the generator refuses them by a documented limit, so they were never simulated
- Conditioned merge + Single zone building: the zoning does not support the prototype's multiplied rooms
- Conditioned merge + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- No simplification + Single zone building: the zoning does not support the prototype's multiplied rooms
- No simplification + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Single zone building: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Stack: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Stacked floor zone multiplier: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Single zone building: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Stack: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Stacked floor zone multiplier: the zoning does not support the prototype's multiplied rooms
- Semantic merge + Single zone building: the zoning does not support the prototype's multiplied rooms
- Semantic merge + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Single zone building: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Stack: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Stacked floor zone multiplier: the zoning does not support the prototype's multiplied rooms
7A · 90.1-2007 · 45°
Reference 945b4a382adfd9cb/R: No simplification + Stack, 54 zones, 18,683 m² conditioned; annual sensible heating 4.9 and cooling 137.9 kWh/m²; peak heating 117.0 and cooling 673.8 kW. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Stack | 24 | 0.00 | -34.1 | -2.4 | 75.9 | 3.7 | 34.1 | 2.4 | -34.3 | -0.6 | no |
| Conditioned merge + Stacked floor zone multiplier | 24 | 0.00 | -15.2 | 1.0 | 36.3 | 2.9 | 15.2 | -1.0 | -23.6 | 0.4 | no |
| Semantic merge + Stack | 51 | 0.00 | -0.0 | -0.0 | 0.1 | 0.0 | 0.0 | 0.0 | -0.1 | -0.0 | yes, recommended |
| Semantic merge + Stacked floor zone multiplier | 51 | 0.00 | 52.8 | 4.1 | 82.5 | 4.6 | -52.8 | -4.1 | 21.7 | 1.0 | no |
| No simplification + Stacked floor zone multiplier | 54 | 0.00 | 52.8 | 4.1 | 82.5 | 4.6 | -52.8 | -4.1 | 21.7 | 1.0 | no |
18 zonings not generated: the generator refuses them by a documented limit, so they were never simulated
- Conditioned merge + Single zone building: the zoning does not support the prototype's multiplied rooms
- Conditioned merge + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- No simplification + Single zone building: the zoning does not support the prototype's multiplied rooms
- No simplification + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Single zone building: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Stack: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Stacked floor zone multiplier: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Single zone building: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Stack: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Stacked floor zone multiplier: the zoning does not support the prototype's multiplied rooms
- Semantic merge + Single zone building: the zoning does not support the prototype's multiplied rooms
- Semantic merge + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Single zone building: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Stack: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Stacked floor zone multiplier: the zoning does not support the prototype's multiplied rooms
7A · 90.1-2019 · 0°
Reference 214e782dcd7c0fb2/R: No simplification + Stack, 54 zones, 18,683 m² conditioned; annual sensible heating 2.9 and cooling 147.3 kWh/m²; peak heating 78.1 and cooling 667.8 kW. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Stack | 24 | 0.00 | -43.6 | -1.8 | 88.8 | 2.4 | 43.6 | 1.8 | -22.6 | -0.5 | no |
| Conditioned merge + Stacked floor zone multiplier | 24 | 0.00 | 0.0 | 1.6 | 16.6 | 2.3 | -0.0 | -1.6 | -5.9 | 0.4 | yes, recommended |
| Semantic merge + Stack | 51 | 0.00 | -0.0 | -0.0 | 0.0 | 0.0 | 0.0 | 0.0 | -0.0 | -0.0 | yes |
| Semantic merge + Stacked floor zone multiplier | 51 | 0.00 | 85.4 | 3.7 | 112.4 | 3.9 | -85.4 | -3.7 | 24.0 | 1.1 | no |
| No simplification + Stacked floor zone multiplier | 54 | 0.00 | 85.4 | 3.7 | 112.4 | 3.9 | -85.4 | -3.7 | 24.0 | 1.1 | no |
18 zonings not generated: the generator refuses them by a documented limit, so they were never simulated
- Conditioned merge + Single zone building: the zoning does not support the prototype's multiplied rooms
- Conditioned merge + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- No simplification + Single zone building: the zoning does not support the prototype's multiplied rooms
- No simplification + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Single zone building: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Stack: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Stacked floor zone multiplier: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Single zone building: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Stack: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Stacked floor zone multiplier: the zoning does not support the prototype's multiplied rooms
- Semantic merge + Single zone building: the zoning does not support the prototype's multiplied rooms
- Semantic merge + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Single zone building: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Stack: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Stacked floor zone multiplier: the zoning does not support the prototype's multiplied rooms
7A · 90.1-2019 · 45°
Reference f101f4c3ac16e7c7/R: No simplification + Stack, 54 zones, 18,683 m² conditioned; annual sensible heating 2.7 and cooling 146.9 kWh/m²; peak heating 73.2 and cooling 653.6 kW. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Stack | 24 | 0.00 | -43.3 | -1.8 | 91.2 | 2.4 | 43.3 | 1.8 | -24.7 | -0.5 | no |
| Conditioned merge + Stacked floor zone multiplier | 24 | 0.00 | -3.1 | 1.8 | 18.3 | 2.3 | 3.1 | -1.8 | -7.0 | 0.3 | yes, recommended |
| Semantic merge + Stack | 51 | 0.00 | -0.0 | -0.0 | 0.0 | 0.0 | 0.0 | 0.0 | -0.0 | -0.0 | yes |
| Semantic merge + Stacked floor zone multiplier | 51 | 0.00 | 95.8 | 3.7 | 120.8 | 3.9 | -95.8 | -3.7 | 25.9 | 1.8 | no |
| No simplification + Stacked floor zone multiplier | 54 | 0.00 | 95.8 | 3.7 | 120.8 | 3.9 | -95.8 | -3.7 | 25.9 | 1.8 | no |
18 zonings not generated: the generator refuses them by a documented limit, so they were never simulated
- Conditioned merge + Single zone building: the zoning does not support the prototype's multiplied rooms
- Conditioned merge + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- No simplification + Single zone building: the zoning does not support the prototype's multiplied rooms
- No simplification + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Single zone building: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Stack: the zoning does not support the prototype's multiplied rooms
- Perimeter core 3 m + Stacked floor zone multiplier: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Single zone building: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Stack: the zoning does not support the prototype's multiplied rooms
- Perimeter core 4.57 m + Stacked floor zone multiplier: the zoning does not support the prototype's multiplied rooms
- Semantic merge + Single zone building: the zoning does not support the prototype's multiplied rooms
- Semantic merge + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Single zone building: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Single zone per floor type: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Stack: the zoning does not support the prototype's multiplied rooms
- Single zone per floor + Stacked floor zone multiplier: the zoning does not support the prototype's multiplied rooms
Atlas programs
The atlas programs each program key of the prototype takes, as the suite's saved inputs name them (release 2.4.0 IDs); the prototype's geometry and glazing are BEMGen's DOE record. Method and caveats.