Outpatient zoning
Outpatient · geometric LOD study drop 5 · atlas inputs release 2.4.0 · BEMGen 99c0b0adcd44
- Prototype
- Outpatient
- Cells
- 24: 6 climate zones × 2 vintages × 2 orientations
- Cells with a recommended zoning
- 24 of 24
- Robust across orientations
- 12 of 12 cell pairs: Conditioned merge + Single zone building (6)
- Reference zoning
- No simplification + Stack
- Reference zones
- 126
- Most often recommended
- Conditioned merge + Single zone building (12 of 24 cells)
- Serial cost (R5)
- timed in 1 of 24 cells (3C 90.1-2019 0°)
Robust across orientations
Robust across orientations in 12 of 12 cell pairs (0° and 45°).
| Climate zone | Vintage | Robust zoning | Zones | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Area change % | CPU ratio | Wall ratio | Memory ratio | Per orientation |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 2A | 90.1-2007 | Conditioned merge + Single zone building (tie: Semantic merge + Single zone building) | 1 | -100.0 | -0.5 | 810.5 | 5.1 | 100.0 | 0.5 | 0.00 | not timed | recommended at both orientations | ||
| 2A | 90.1-2019 | Conditioned merge + Single zone building (tie: Semantic merge + Single zone building) | 1 | – | -1.1 | – | 4.7 | – | 1.1 | 0.00 | not timed | recommended at both orientations | ||
| 2B | 90.1-2007 | Conditioned merge + Single zone building (tie: Semantic merge + Single zone building) | 1 | -100.0 | -1.2 | 426.8 | 7.1 | 100.0 | 1.2 | 0.00 | not timed | recommended at both orientations | ||
| 2B | 90.1-2019 | Conditioned merge + Single zone building (tie: Semantic merge + Single zone building) | 1 | -100.0 | -1.7 | 456.0 | 5.9 | 100.0 | 1.7 | 0.00 | not timed | recommended at both orientations | ||
| 3C | 90.1-2007 | Conditioned merge + Single zone building (tie: Semantic merge + Single zone building) | 1 | -100.0 | -1.8 | 364.1 | 8.4 | 100.0 | 1.8 | 0.00 | not timed | recommended at both orientations | ||
| 3C | 90.1-2019 | Conditioned merge + Single zone building (tie: Semantic merge + Single zone building) | 1 | -100.0 | -3.1 | 312.5 | 8.1 | 100.0 | 3.1 | 0.00 | 0.063 | 0.065 | 0.688 | recommended at both orientations |
| 4A | 90.1-2007 | Semantic merge + Stack | 104 | -3.4 | -0.1 | 10.0 | 0.3 | 3.4 | 0.1 | 0.00 | not timed | recommended at both orientations | ||
| 4A | 90.1-2019 | Semantic merge + Stack | 104 | -5.5 | -0.1 | 14.1 | 0.4 | 5.5 | 0.1 | 0.00 | not timed | recommended at both orientations | ||
| 5A | 90.1-2007 | Semantic merge + Stack | 104 | -2.8 | -0.2 | 6.9 | 0.5 | 2.8 | 0.2 | 0.00 | not timed | recommended at both orientations | ||
| 5A | 90.1-2019 | Semantic merge + Stack | 104 | -4.5 | -0.2 | 10.9 | 0.5 | 4.5 | 0.2 | 0.00 | not timed | recommended at both orientations | ||
| 7A | 90.1-2007 | Semantic merge + Stack | 104 | -1.7 | -0.3 | 3.5 | 0.5 | 1.7 | 0.3 | 0.00 | not timed | recommended at both orientations | ||
| 7A | 90.1-2019 | Semantic merge + Stack | 104 | -2.9 | -0.3 | 6.0 | 0.6 | 2.9 | 0.3 | 0.00 | not timed | recommended at both orientations | ||
For each prototype, climate zone and vintage, the robust zoning is the coarsest (fewest modelled zones) that meets the threshold at every orientation of the cell pair, by the writer's own verdict on each zoning at each orientation, with at most the reference's zone count, as the writer bounds a recommendation (D-220); a duplicate never meets, as the writer lists it. Ties at the fewest zones go to a zoning both orientations recommend, else to the first in the study's zoning order (simplifier, join pieces, perimeter depth, stacker, IWHT, FHT); the tied zonings are named. The errors reported are the worse of the orientations' values for each metric, so the row is a bound, not a mean; the cost ratios are the medians over the timed sites of that zoning in the pair. Where both orientations recommend the same zoning it is the robust one. A pair where no zoning meets the threshold at both orientations says so and names each orientation's own recommendation; the per-orientation rows below stay the reading for one orientation. The cost ratios are the median over the timed sites of the robust zoning in the pair (in this drop one orientation at most is timed, so the ratio is that site's); not timed where none is. The rule and its limits.
Recommended zonings
| Climate zone | Vintage | Orientation | Reference zones | Heating kWh/m² | Cooling kWh/m² | Recommended zoning | Zones | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Area change % | CPU ratio | Wall ratio | Memory ratio |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 2A | 90.1-2007 | 0° | 126 | 0.1 | 182.3 | Conditioned merge + Single zone building | 1 | -100.0 | -0.5 | 810.5 | 5.1 | 100.0 | 0.5 | 0.00 | not timed | ||
| 2A | 90.1-2007 | 0° | 126 | 0.1 | 182.3 | Semantic merge + Single zone building | 1 | -100.0 | -0.5 | 810.5 | 5.1 | 100.0 | 0.5 | 0.00 | not timed | ||
| 2A | 90.1-2007 | 45° | 126 | 0.1 | 180.0 | Conditioned merge + Single zone building | 1 | -100.0 | -0.5 | 767.6 | 4.9 | 100.0 | 0.5 | 0.00 | not timed | ||
| 2A | 90.1-2007 | 45° | 126 | 0.1 | 180.0 | Semantic merge + Single zone building | 1 | -100.0 | -0.5 | 767.6 | 4.9 | 100.0 | 0.5 | 0.00 | not timed | ||
| 2A | 90.1-2019 | 0° | 126 | 0.0 | 165.9 | Conditioned merge + Single zone building | 1 | – | -1.1 | – | 4.7 | – | 1.1 | 0.00 | not timed | ||
| 2A | 90.1-2019 | 0° | 126 | 0.0 | 165.9 | Semantic merge + Single zone building | 1 | – | -1.1 | – | 4.7 | – | 1.1 | 0.00 | not timed | ||
| 2A | 90.1-2019 | 45° | 126 | 0.0 | 163.5 | Conditioned merge + Single zone building | 1 | – | -1.1 | – | 4.6 | – | 1.1 | 0.00 | not timed | ||
| 2A | 90.1-2019 | 45° | 126 | 0.0 | 163.5 | Semantic merge + Single zone building | 1 | – | -1.1 | – | 4.6 | – | 1.1 | 0.00 | not timed | ||
| 2B | 90.1-2007 | 0° | 126 | 0.6 | 175.9 | Conditioned merge + Single zone building | 1 | -100.0 | -1.2 | 426.8 | 7.1 | 100.0 | 1.2 | 0.00 | not timed | ||
| 2B | 90.1-2007 | 0° | 126 | 0.6 | 175.9 | Semantic merge + Single zone building | 1 | -100.0 | -1.2 | 426.8 | 7.1 | 100.0 | 1.2 | 0.00 | not timed | ||
| 2B | 90.1-2007 | 45° | 126 | 0.6 | 174.1 | Conditioned merge + Single zone building | 1 | -100.0 | -1.2 | 420.3 | 6.7 | 100.0 | 1.2 | 0.00 | not timed | ||
| 2B | 90.1-2007 | 45° | 126 | 0.6 | 174.1 | Semantic merge + Single zone building | 1 | -100.0 | -1.2 | 420.3 | 6.7 | 100.0 | 1.2 | 0.00 | not timed | ||
| 2B | 90.1-2019 | 0° | 126 | 0.2 | 161.2 | Conditioned merge + Single zone building | 1 | -100.0 | -1.7 | 452.8 | 5.9 | 100.0 | 1.7 | 0.00 | not timed | ||
| 2B | 90.1-2019 | 0° | 126 | 0.2 | 161.2 | Semantic merge + Single zone building | 1 | -100.0 | -1.7 | 452.8 | 5.9 | 100.0 | 1.7 | 0.00 | not timed | ||
| 2B | 90.1-2019 | 45° | 126 | 0.2 | 159.0 | Conditioned merge + Single zone building | 1 | -100.0 | -1.7 | 456.0 | 5.8 | 100.0 | 1.7 | 0.00 | not timed | ||
| 2B | 90.1-2019 | 45° | 126 | 0.2 | 159.0 | Semantic merge + Single zone building | 1 | -100.0 | -1.7 | 456.0 | 5.8 | 100.0 | 1.7 | 0.00 | not timed | ||
| 3C | 90.1-2007 | 0° | 126 | 0.4 | 136.8 | Conditioned merge + Single zone building | 1 | -100.0 | -1.8 | 364.1 | 8.4 | 100.0 | 1.8 | 0.00 | not timed | ||
| 3C | 90.1-2007 | 0° | 126 | 0.4 | 136.8 | Semantic merge + Single zone building | 1 | -100.0 | -1.9 | 364.1 | 8.3 | 100.0 | 1.9 | 0.00 | not timed | ||
| 3C | 90.1-2007 | 45° | 126 | 0.4 | 138.7 | Conditioned merge + Single zone building | 1 | -100.0 | -1.7 | 356.2 | 7.6 | 100.0 | 1.7 | 0.00 | not timed | ||
| 3C | 90.1-2007 | 45° | 126 | 0.4 | 138.7 | Semantic merge + Single zone building | 1 | -100.0 | -1.8 | 356.2 | 7.6 | 100.0 | 1.8 | 0.00 | not timed | ||
| 3C | 90.1-2019 | 0° | 126 | 0.3 | 130.5 | Conditioned merge + Single zone building | 1 | -100.0 | -3.1 | 301.0 | 8.1 | 100.0 | 3.1 | 0.00 | 0.063 | 0.065 | 0.688 |
| 3C | 90.1-2019 | 0° | 126 | 0.3 | 130.5 | Semantic merge + Single zone building | 1 | -100.0 | -3.2 | 301.0 | 8.1 | 100.0 | 3.2 | 0.00 | 0.064 | 0.067 | 0.751 |
| 3C | 90.1-2019 | 45° | 126 | 0.3 | 130.6 | Conditioned merge + Single zone building | 1 | -100.0 | -3.0 | 312.5 | 7.6 | 100.0 | 3.0 | 0.00 | not timed | ||
| 3C | 90.1-2019 | 45° | 126 | 0.3 | 130.6 | Semantic merge + Single zone building | 1 | -100.0 | -3.0 | 312.5 | 7.7 | 100.0 | 3.0 | 0.00 | not timed | ||
| 4A | 90.1-2007 | 0° | 126 | 2.9 | 136.4 | Semantic merge + Stack | 104 | -3.4 | -0.1 | 10.0 | 0.3 | 3.4 | 0.1 | 0.00 | not timed | ||
| 4A | 90.1-2007 | 45° | 126 | 2.6 | 135.6 | Semantic merge + Stack | 104 | -2.9 | -0.1 | 7.5 | 0.2 | 2.9 | 0.1 | 0.00 | not timed | ||
| 4A | 90.1-2019 | 0° | 126 | 1.7 | 129.0 | Semantic merge + Stack | 104 | -5.5 | -0.1 | 14.1 | 0.4 | 5.5 | 0.1 | 0.00 | not timed | ||
| 4A | 90.1-2019 | 45° | 126 | 1.7 | 127.2 | Semantic merge + Stack | 104 | -5.3 | -0.1 | 12.9 | 0.3 | 5.3 | 0.1 | 0.00 | not timed | ||
| 5A | 90.1-2007 | 0° | 126 | 6.5 | 118.0 | Semantic merge + Stack | 104 | -2.8 | -0.2 | 6.9 | 0.5 | 2.8 | 0.2 | 0.00 | not timed | ||
| 5A | 90.1-2007 | 45° | 126 | 5.6 | 118.9 | Semantic merge + Stack | 104 | -2.2 | -0.1 | 5.3 | 0.3 | 2.2 | 0.1 | 0.00 | not timed | ||
| 5A | 90.1-2019 | 0° | 126 | 3.4 | 114.3 | Semantic merge + Stack | 104 | -4.5 | -0.2 | 10.9 | 0.5 | 4.5 | 0.2 | 0.00 | not timed | ||
| 5A | 90.1-2019 | 45° | 126 | 3.1 | 113.7 | Semantic merge + Stack | 104 | -4.3 | -0.2 | 10.3 | 0.4 | 4.3 | 0.2 | 0.00 | not timed | ||
| 7A | 90.1-2007 | 0° | 126 | 15.2 | 109.2 | Semantic merge + Stack | 104 | -1.7 | -0.3 | 3.5 | 0.5 | 1.7 | 0.3 | 0.00 | not timed | ||
| 7A | 90.1-2007 | 45° | 126 | 13.4 | 108.6 | Semantic merge + Stack | 104 | -1.3 | -0.2 | 2.8 | 0.4 | 1.3 | 0.2 | 0.00 | not timed | ||
| 7A | 90.1-2019 | 0° | 126 | 8.4 | 105.2 | Semantic merge + Stack | 104 | -2.9 | -0.3 | 6.0 | 0.6 | 2.9 | 0.3 | 0.00 | not timed | ||
| 7A | 90.1-2019 | 45° | 126 | 7.7 | 103.7 | Semantic merge + Stack | 104 | -2.5 | -0.2 | 5.3 | 0.5 | 2.5 | 0.2 | 0.00 | not timed | ||
The coarsest zonings (fewest modelled zones) meeting the threshold; ties are all listed. Errors are the test zoning against the reference: annual sensible load, hourly CV(RMSE) and NMBE, and the change of conditioned floor area. A muted value belongs to a load the threshold does not judge; a dash is a value the runner did not store; a flagged value carries the runner's own flag. The cost ratios are the serial timing pass (R5): the zoning's processor time, wall clock and peak committed memory over its reference's, each the median of its repeats; not timed marks a cell outside the timed ones. Cost protocol.
Every zoning by cell
2A · 90.1-2007 · 0°
Reference 37d67e4d513256b9/R: No simplification + Stack, 126 zones, 3,915 m² conditioned; annual sensible heating 0.1 and cooling 182.3 kWh/m²; peak heating 13.6 and cooling 176.3 kW. Sensible heating is below 1 kWh/m² and is not judged. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Single zone building | 1 | 0.00 | -100.0 | -0.5 | 810.5 | 5.1 | 100.0 | 0.5 | -100.0 | 2.7 | yes, recommended |
| Semantic merge + Single zone building | 1 | 0.00 | -100.0 | -0.5 | 810.5 | 5.1 | 100.0 | 0.5 | -100.0 | 2.7 | yes, recommended |
| Conditioned merge + Single zone per floor type | 3 | 0.00 | -98.3 | -0.5 | 775.9 | 2.1 | 98.3 | 0.5 | -71.1 | -1.2 | yes |
| Conditioned merge + Stacked floor zone multiplier | 3 | 0.00 | -88.7 | -0.4 | 653.8 | 1.8 | 88.7 | 0.4 | -28.6 | -0.3 | yes |
| Semantic merge + Single zone per floor type | 3 | 0.00 | -98.3 | -0.5 | 775.9 | 2.1 | 98.3 | 0.5 | -71.1 | -1.2 | yes |
| Semantic merge + Stack | 104 | 0.00 | -3.8 | -0.0 | 41.5 | 0.1 | 3.8 | 0.0 | -2.2 | -0.0 | yes |
| Semantic merge + Stacked floor zone multiplier | 104 | 0.00 | 36.1 | 0.1 | 301.7 | 1.1 | -36.1 | -0.1 | 35.8 | 0.9 | yes |
| No simplification + Stacked floor zone multiplier | 126 | 0.00 | 42.5 | 0.1 | 337.7 | 1.1 | -42.5 | -0.1 | 39.1 | 0.9 | yes |
8 zonings not generated: the generator refuses them by a documented limit, so they were never simulated
- Perimeter core 3 m + Single zone building: a wing is narrower than twice the perimeter depth
- Perimeter core 3 m + Single zone per floor type: a wing is narrower than twice the perimeter depth
- Perimeter core 3 m + Stack: a wing is narrower than twice the perimeter depth
- Perimeter core 3 m + Stacked floor zone multiplier: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Single zone building: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Single zone per floor type: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Stack: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Stacked floor zone multiplier: a wing is narrower than twice the perimeter depth
7 zonings write the same model as a listed one and are not shown
- Conditioned merge + Stack → Conditioned merge + Single zone per floor type
- No simplification + Single zone building → Conditioned merge + Single zone building
- No simplification + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Single zone building → Conditioned merge + Single zone building
- Single zone per floor + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Stack → Conditioned merge + Single zone per floor type
- Single zone per floor + Stacked floor zone multiplier → Conditioned merge + Stacked floor zone multiplier
2A · 90.1-2007 · 45°
Reference 0864799c6de45322/R: No simplification + Stack, 126 zones, 3,915 m² conditioned; annual sensible heating 0.1 and cooling 180.0 kWh/m²; peak heating 11.6 and cooling 171.9 kW. Sensible heating is below 1 kWh/m² and is not judged. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Single zone building | 1 | 0.00 | -100.0 | -0.5 | 767.6 | 4.9 | 100.0 | 0.5 | -100.0 | 2.4 | yes, recommended |
| Semantic merge + Single zone building | 1 | 0.00 | -100.0 | -0.5 | 767.6 | 4.9 | 100.0 | 0.5 | -100.0 | 2.4 | yes, recommended |
| Conditioned merge + Single zone per floor type | 3 | 0.00 | -99.6 | -0.5 | 759.2 | 2.1 | 99.6 | 0.5 | -91.0 | -1.2 | yes |
| Conditioned merge + Stacked floor zone multiplier | 3 | 0.00 | -95.5 | -0.5 | 696.6 | 1.8 | 95.5 | 0.5 | -43.2 | -0.4 | yes |
| Semantic merge + Single zone per floor type | 3 | 0.00 | -99.6 | -0.5 | 759.2 | 2.1 | 99.6 | 0.5 | -91.0 | -1.2 | yes |
| Semantic merge + Stack | 104 | 0.00 | -5.0 | -0.0 | 31.6 | 0.1 | 5.0 | 0.0 | -1.6 | -0.0 | yes |
| Semantic merge + Stacked floor zone multiplier | 104 | 0.00 | 30.3 | 0.1 | 245.1 | 1.0 | -30.3 | -0.1 | 34.3 | 0.7 | yes |
| No simplification + Stacked floor zone multiplier | 126 | 0.00 | 37.9 | 0.1 | 267.2 | 1.0 | -37.9 | -0.1 | 36.3 | 0.8 | yes |
8 zonings not generated: the generator refuses them by a documented limit, so they were never simulated
- Perimeter core 3 m + Single zone building: a wing is narrower than twice the perimeter depth
- Perimeter core 3 m + Single zone per floor type: a wing is narrower than twice the perimeter depth
- Perimeter core 3 m + Stack: a wing is narrower than twice the perimeter depth
- Perimeter core 3 m + Stacked floor zone multiplier: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Single zone building: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Single zone per floor type: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Stack: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Stacked floor zone multiplier: a wing is narrower than twice the perimeter depth
7 zonings write the same model as a listed one and are not shown
- Conditioned merge + Stack → Conditioned merge + Single zone per floor type
- No simplification + Single zone building → Conditioned merge + Single zone building
- No simplification + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Single zone building → Conditioned merge + Single zone building
- Single zone per floor + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Stack → Conditioned merge + Single zone per floor type
- Single zone per floor + Stacked floor zone multiplier → Conditioned merge + Stacked floor zone multiplier
2A · 90.1-2019 · 0°
Reference 21623b36d829628e/R: No simplification + Stack, 126 zones, 3,915 m² conditioned; annual sensible heating 0.0 and cooling 165.9 kWh/m²; peak heating 4.4 and cooling 183.8 kW. Sensible heating is below 1 kWh/m² and is not judged. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Single zone building | 1 | 0.00 | – | -1.1 | – | 4.7 | – | 1.1 | -100.0 | -3.3 | yes, recommended |
| Semantic merge + Single zone building | 1 | 0.00 | – | -1.1 | – | 4.7 | – | 1.1 | -100.0 | -3.3 | yes, recommended |
| Conditioned merge + Single zone per floor type | 3 | 0.00 | – | -0.9 | – | 3.2 | – | 0.9 | -100.0 | -2.8 | yes |
| Conditioned merge + Stacked floor zone multiplier | 3 | 0.00 | – | -0.9 | – | 3.3 | – | 0.9 | -100.0 | -2.7 | yes |
| Semantic merge + Single zone per floor type | 3 | 0.00 | – | -0.9 | – | 3.2 | – | 0.9 | -100.0 | -2.8 | yes |
| Semantic merge + Stack | 104 | 0.00 | – | -0.0 | – | 0.1 | – | 0.0 | -2.8 | -0.1 | yes |
| Semantic merge + Stacked floor zone multiplier | 104 | 0.00 | – | 0.0 | – | 0.7 | – | -0.0 | 33.3 | -0.5 | yes |
| No simplification + Stacked floor zone multiplier | 126 | 0.00 | – | 0.1 | – | 0.7 | – | -0.1 | 41.2 | -0.4 | yes |
8 zonings not generated: the generator refuses them by a documented limit, so they were never simulated
- Perimeter core 3 m + Single zone building: a wing is narrower than twice the perimeter depth
- Perimeter core 3 m + Single zone per floor type: a wing is narrower than twice the perimeter depth
- Perimeter core 3 m + Stack: a wing is narrower than twice the perimeter depth
- Perimeter core 3 m + Stacked floor zone multiplier: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Single zone building: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Single zone per floor type: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Stack: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Stacked floor zone multiplier: a wing is narrower than twice the perimeter depth
7 zonings write the same model as a listed one and are not shown
- Conditioned merge + Stack → Conditioned merge + Single zone per floor type
- No simplification + Single zone building → Conditioned merge + Single zone building
- No simplification + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Single zone building → Conditioned merge + Single zone building
- Single zone per floor + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Stack → Conditioned merge + Single zone per floor type
- Single zone per floor + Stacked floor zone multiplier → Conditioned merge + Stacked floor zone multiplier
2A · 90.1-2019 · 45°
Reference 9f1850eb5127ef51/R: No simplification + Stack, 126 zones, 3,915 m² conditioned; annual sensible heating 0.0 and cooling 163.5 kWh/m²; peak heating 4.4 and cooling 181.5 kW. Sensible heating is below 1 kWh/m² and is not judged. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Single zone building | 1 | 0.00 | – | -1.1 | – | 4.6 | – | 1.1 | -100.0 | -3.5 | yes, recommended |
| Semantic merge + Single zone building | 1 | 0.00 | – | -1.1 | – | 4.6 | – | 1.1 | -100.0 | -3.6 | yes, recommended |
| Conditioned merge + Single zone per floor type | 3 | 0.00 | – | -1.0 | – | 3.2 | – | 1.0 | -100.0 | -3.7 | yes |
| Conditioned merge + Stacked floor zone multiplier | 3 | 0.00 | – | -0.9 | – | 3.3 | – | 0.9 | -100.0 | -4.2 | yes |
| Semantic merge + Single zone per floor type | 3 | 0.00 | – | -1.0 | – | 3.2 | – | 1.0 | -100.0 | -3.7 | yes |
| Semantic merge + Stack | 104 | 0.00 | – | -0.0 | – | 0.1 | – | 0.0 | -3.0 | -0.1 | yes |
| Semantic merge + Stacked floor zone multiplier | 104 | 0.00 | – | 0.0 | – | 0.7 | – | -0.0 | 14.5 | -0.5 | yes |
| No simplification + Stacked floor zone multiplier | 126 | 0.00 | – | 0.1 | – | 0.7 | – | -0.1 | 22.4 | -0.4 | yes |
8 zonings not generated: the generator refuses them by a documented limit, so they were never simulated
- Perimeter core 3 m + Single zone building: a wing is narrower than twice the perimeter depth
- Perimeter core 3 m + Single zone per floor type: a wing is narrower than twice the perimeter depth
- Perimeter core 3 m + Stack: a wing is narrower than twice the perimeter depth
- Perimeter core 3 m + Stacked floor zone multiplier: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Single zone building: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Single zone per floor type: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Stack: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Stacked floor zone multiplier: a wing is narrower than twice the perimeter depth
7 zonings write the same model as a listed one and are not shown
- Conditioned merge + Stack → Conditioned merge + Single zone per floor type
- No simplification + Single zone building → Conditioned merge + Single zone building
- No simplification + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Single zone building → Conditioned merge + Single zone building
- Single zone per floor + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Stack → Conditioned merge + Single zone per floor type
- Single zone per floor + Stacked floor zone multiplier → Conditioned merge + Stacked floor zone multiplier
2B · 90.1-2007 · 0°
Reference 433442b2c7800bcd/R: No simplification + Stack, 126 zones, 3,915 m² conditioned; annual sensible heating 0.6 and cooling 175.9 kWh/m²; peak heating 22.1 and cooling 185.1 kW. Sensible heating is below 1 kWh/m² and is not judged. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Single zone building | 1 | 0.00 | -100.0 | -1.2 | 426.8 | 7.1 | 100.0 | 1.2 | -100.0 | 2.5 | yes, recommended |
| Semantic merge + Single zone building | 1 | 0.00 | -100.0 | -1.2 | 426.8 | 7.1 | 100.0 | 1.2 | -100.0 | 2.5 | yes, recommended |
| Conditioned merge + Single zone per floor type | 3 | 0.00 | -97.8 | -1.1 | 402.6 | 2.9 | 97.8 | 1.1 | -61.5 | -1.0 | yes |
| Conditioned merge + Stacked floor zone multiplier | 3 | 0.00 | -86.8 | -0.9 | 336.7 | 2.7 | 86.8 | 0.9 | -25.0 | -0.3 | yes |
| Semantic merge + Single zone per floor type | 3 | 0.00 | -97.8 | -1.1 | 402.6 | 2.9 | 97.8 | 1.1 | -61.5 | -1.0 | yes |
| Semantic merge + Stack | 104 | 0.00 | -3.7 | -0.0 | 20.0 | 0.1 | 3.7 | 0.0 | -3.2 | -0.0 | yes |
| Semantic merge + Stacked floor zone multiplier | 104 | 0.00 | 32.0 | 0.2 | 153.6 | 1.2 | -32.0 | -0.2 | 28.3 | 0.8 | yes |
| No simplification + Stacked floor zone multiplier | 126 | 0.00 | 37.5 | 0.3 | 172.2 | 1.2 | -37.5 | -0.3 | 29.5 | 0.8 | yes |
8 zonings not generated: the generator refuses them by a documented limit, so they were never simulated
- Perimeter core 3 m + Single zone building: a wing is narrower than twice the perimeter depth
- Perimeter core 3 m + Single zone per floor type: a wing is narrower than twice the perimeter depth
- Perimeter core 3 m + Stack: a wing is narrower than twice the perimeter depth
- Perimeter core 3 m + Stacked floor zone multiplier: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Single zone building: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Single zone per floor type: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Stack: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Stacked floor zone multiplier: a wing is narrower than twice the perimeter depth
7 zonings write the same model as a listed one and are not shown
- Conditioned merge + Stack → Conditioned merge + Single zone per floor type
- No simplification + Single zone building → Conditioned merge + Single zone building
- No simplification + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Single zone building → Conditioned merge + Single zone building
- Single zone per floor + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Stack → Conditioned merge + Single zone per floor type
- Single zone per floor + Stacked floor zone multiplier → Conditioned merge + Stacked floor zone multiplier
2B · 90.1-2007 · 45°
Reference 3803b314f15579ea/R: No simplification + Stack, 126 zones, 3,915 m² conditioned; annual sensible heating 0.6 and cooling 174.1 kWh/m²; peak heating 18.2 and cooling 184.0 kW. Sensible heating is below 1 kWh/m² and is not judged. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Single zone building | 1 | 0.00 | -100.0 | -1.2 | 420.3 | 6.7 | 100.0 | 1.2 | -100.0 | 2.2 | yes, recommended |
| Semantic merge + Single zone building | 1 | 0.00 | -100.0 | -1.2 | 420.3 | 6.7 | 100.0 | 1.2 | -100.0 | 2.2 | yes, recommended |
| Conditioned merge + Single zone per floor type | 3 | 0.00 | -99.2 | -1.1 | 410.2 | 2.9 | 99.2 | 1.1 | -72.1 | -1.1 | yes |
| Conditioned merge + Stacked floor zone multiplier | 3 | 0.00 | -94.1 | -1.0 | 372.8 | 2.7 | 94.1 | 1.0 | -39.5 | -0.3 | yes |
| Semantic merge + Single zone per floor type | 3 | 0.00 | -99.2 | -1.1 | 410.2 | 2.9 | 99.2 | 1.1 | -72.1 | -1.1 | yes |
| Semantic merge + Stack | 104 | 0.00 | -4.1 | -0.0 | 15.8 | 0.1 | 4.1 | 0.0 | -2.9 | -0.0 | yes |
| Semantic merge + Stacked floor zone multiplier | 104 | 0.00 | 28.0 | 0.2 | 135.4 | 1.1 | -28.0 | -0.2 | 30.0 | 0.7 | yes |
| No simplification + Stacked floor zone multiplier | 126 | 0.00 | 33.2 | 0.2 | 145.4 | 1.1 | -33.2 | -0.2 | 32.2 | 0.7 | yes |
8 zonings not generated: the generator refuses them by a documented limit, so they were never simulated
- Perimeter core 3 m + Single zone building: a wing is narrower than twice the perimeter depth
- Perimeter core 3 m + Single zone per floor type: a wing is narrower than twice the perimeter depth
- Perimeter core 3 m + Stack: a wing is narrower than twice the perimeter depth
- Perimeter core 3 m + Stacked floor zone multiplier: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Single zone building: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Single zone per floor type: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Stack: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Stacked floor zone multiplier: a wing is narrower than twice the perimeter depth
7 zonings write the same model as a listed one and are not shown
- Conditioned merge + Stack → Conditioned merge + Single zone per floor type
- No simplification + Single zone building → Conditioned merge + Single zone building
- No simplification + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Single zone building → Conditioned merge + Single zone building
- Single zone per floor + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Stack → Conditioned merge + Single zone per floor type
- Single zone per floor + Stacked floor zone multiplier → Conditioned merge + Stacked floor zone multiplier
2B · 90.1-2019 · 0°
Reference 0d64f9ccb96c659a/R: No simplification + Stack, 126 zones, 3,915 m² conditioned; annual sensible heating 0.2 and cooling 161.2 kWh/m²; peak heating 8.9 and cooling 189.5 kW. Sensible heating is below 1 kWh/m² and is not judged. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Single zone building | 1 | 0.00 | -100.0 | -1.7 | 452.8 | 5.9 | 100.0 | 1.7 | -100.0 | -2.6 | yes, recommended |
| Semantic merge + Single zone building | 1 | 0.00 | -100.0 | -1.7 | 452.8 | 5.9 | 100.0 | 1.7 | -100.0 | -2.6 | yes, recommended |
| Conditioned merge + Single zone per floor type | 3 | 0.00 | -100.0 | -1.5 | 452.8 | 4.3 | 100.0 | 1.5 | -100.0 | -1.4 | yes |
| Conditioned merge + Stacked floor zone multiplier | 3 | 0.00 | -99.1 | -1.4 | 440.7 | 4.3 | 99.1 | 1.4 | -50.6 | -1.8 | yes |
| Semantic merge + Single zone per floor type | 3 | 0.00 | -100.0 | -1.5 | 452.8 | 4.3 | 100.0 | 1.5 | -100.0 | -1.4 | yes |
| Semantic merge + Stack | 104 | 0.00 | -4.8 | -0.0 | 22.7 | 0.2 | 4.8 | 0.0 | -7.8 | 0.0 | yes |
| Semantic merge + Stacked floor zone multiplier | 104 | 0.00 | 20.9 | 0.1 | 107.1 | 0.8 | -20.9 | -0.1 | 47.9 | -0.5 | yes |
| No simplification + Stacked floor zone multiplier | 126 | 0.00 | 30.8 | 0.1 | 141.7 | 0.9 | -30.8 | -0.1 | 54.7 | -0.5 | yes |
8 zonings not generated: the generator refuses them by a documented limit, so they were never simulated
- Perimeter core 3 m + Single zone building: a wing is narrower than twice the perimeter depth
- Perimeter core 3 m + Single zone per floor type: a wing is narrower than twice the perimeter depth
- Perimeter core 3 m + Stack: a wing is narrower than twice the perimeter depth
- Perimeter core 3 m + Stacked floor zone multiplier: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Single zone building: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Single zone per floor type: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Stack: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Stacked floor zone multiplier: a wing is narrower than twice the perimeter depth
7 zonings write the same model as a listed one and are not shown
- Conditioned merge + Stack → Conditioned merge + Single zone per floor type
- No simplification + Single zone building → Conditioned merge + Single zone building
- No simplification + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Single zone building → Conditioned merge + Single zone building
- Single zone per floor + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Stack → Conditioned merge + Single zone per floor type
- Single zone per floor + Stacked floor zone multiplier → Conditioned merge + Stacked floor zone multiplier
2B · 90.1-2019 · 45°
Reference 2041ca8bbbcfbedf/R: No simplification + Stack, 126 zones, 3,915 m² conditioned; annual sensible heating 0.2 and cooling 159.0 kWh/m²; peak heating 7.6 and cooling 185.9 kW. Sensible heating is below 1 kWh/m² and is not judged. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Single zone building | 1 | 0.00 | -100.0 | -1.7 | 456.0 | 5.8 | 100.0 | 1.7 | -100.0 | -3.4 | yes, recommended |
| Semantic merge + Single zone building | 1 | 0.00 | -100.0 | -1.7 | 456.0 | 5.8 | 100.0 | 1.7 | -100.0 | -3.4 | yes, recommended |
| Conditioned merge + Single zone per floor type | 3 | 0.00 | -100.0 | -1.5 | 456.0 | 4.3 | 100.0 | 1.5 | -100.0 | -2.2 | yes |
| Conditioned merge + Stacked floor zone multiplier | 3 | 0.00 | -99.9 | -1.4 | 453.9 | 4.2 | 99.9 | 1.4 | -87.3 | -2.5 | yes |
| Semantic merge + Single zone per floor type | 3 | 0.00 | -100.0 | -1.5 | 456.0 | 4.3 | 100.0 | 1.5 | -100.0 | -2.2 | yes |
| Semantic merge + Stack | 104 | 0.00 | -6.2 | -0.0 | 24.9 | 0.1 | 6.2 | 0.0 | -8.3 | -0.0 | yes |
| Semantic merge + Stacked floor zone multiplier | 104 | 0.00 | 18.8 | 0.1 | 80.9 | 0.8 | -18.8 | -0.1 | 33.4 | -0.7 | yes |
| No simplification + Stacked floor zone multiplier | 126 | 0.00 | 31.6 | 0.1 | 120.9 | 0.8 | -31.6 | -0.1 | 36.2 | -0.6 | yes |
8 zonings not generated: the generator refuses them by a documented limit, so they were never simulated
- Perimeter core 3 m + Single zone building: a wing is narrower than twice the perimeter depth
- Perimeter core 3 m + Single zone per floor type: a wing is narrower than twice the perimeter depth
- Perimeter core 3 m + Stack: a wing is narrower than twice the perimeter depth
- Perimeter core 3 m + Stacked floor zone multiplier: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Single zone building: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Single zone per floor type: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Stack: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Stacked floor zone multiplier: a wing is narrower than twice the perimeter depth
7 zonings write the same model as a listed one and are not shown
- Conditioned merge + Stack → Conditioned merge + Single zone per floor type
- No simplification + Single zone building → Conditioned merge + Single zone building
- No simplification + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Single zone building → Conditioned merge + Single zone building
- Single zone per floor + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Stack → Conditioned merge + Single zone per floor type
- Single zone per floor + Stacked floor zone multiplier → Conditioned merge + Stacked floor zone multiplier
3C · 90.1-2007 · 0°
Reference 22f556b310266f14/R: No simplification + Stack, 126 zones, 3,915 m² conditioned; annual sensible heating 0.4 and cooling 136.8 kWh/m²; peak heating 10.1 and cooling 146.7 kW. Sensible heating is below 1 kWh/m² and is not judged. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Single zone building | 1 | 0.00 | -100.0 | -1.8 | 364.1 | 8.4 | 100.0 | 1.8 | -100.0 | 3.7 | yes, recommended |
| Semantic merge + Single zone building | 1 | 0.00 | -100.0 | -1.9 | 364.1 | 8.3 | 100.0 | 1.9 | -100.0 | 3.7 | yes, recommended |
| Conditioned merge + Single zone per floor type | 3 | 0.00 | -99.9 | -1.7 | 363.0 | 2.7 | 99.9 | 1.7 | -90.3 | -1.1 | yes |
| Conditioned merge + Stacked floor zone multiplier | 3 | 0.00 | -98.0 | -1.5 | 344.8 | 2.9 | 98.0 | 1.5 | -40.7 | 0.0 | yes |
| Semantic merge + Single zone per floor type | 3 | 0.00 | -99.9 | -1.7 | 363.0 | 2.8 | 99.9 | 1.7 | -90.3 | -1.2 | yes |
| Semantic merge + Stack | 104 | 0.00 | -3.5 | -0.1 | 15.0 | 0.2 | 3.5 | 0.1 | -3.0 | -0.0 | yes |
| Semantic merge + Stacked floor zone multiplier | 104 | 0.00 | 32.7 | 0.3 | 159.5 | 1.1 | -32.7 | -0.3 | 59.7 | 1.1 | yes |
| No simplification + Stacked floor zone multiplier | 126 | 0.00 | 39.7 | 0.4 | 175.5 | 1.1 | -39.7 | -0.4 | 50.7 | 1.1 | yes |
8 zonings not generated: the generator refuses them by a documented limit, so they were never simulated
- Perimeter core 3 m + Single zone building: a wing is narrower than twice the perimeter depth
- Perimeter core 3 m + Single zone per floor type: a wing is narrower than twice the perimeter depth
- Perimeter core 3 m + Stack: a wing is narrower than twice the perimeter depth
- Perimeter core 3 m + Stacked floor zone multiplier: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Single zone building: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Single zone per floor type: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Stack: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Stacked floor zone multiplier: a wing is narrower than twice the perimeter depth
7 zonings write the same model as a listed one and are not shown
- Conditioned merge + Stack → Conditioned merge + Single zone per floor type
- No simplification + Single zone building → Conditioned merge + Single zone building
- No simplification + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Single zone building → Conditioned merge + Single zone building
- Single zone per floor + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Stack → Conditioned merge + Single zone per floor type
- Single zone per floor + Stacked floor zone multiplier → Conditioned merge + Stacked floor zone multiplier
3C · 90.1-2007 · 45°
Reference 4176838c890be51e/R: No simplification + Stack, 126 zones, 3,915 m² conditioned; annual sensible heating 0.4 and cooling 138.7 kWh/m²; peak heating 9.0 and cooling 144.5 kW. Sensible heating is below 1 kWh/m² and is not judged. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Single zone building | 1 | 0.00 | -100.0 | -1.7 | 356.2 | 7.6 | 100.0 | 1.7 | -100.0 | 3.0 | yes, recommended |
| Semantic merge + Single zone building | 1 | 0.00 | -100.0 | -1.8 | 356.2 | 7.6 | 100.0 | 1.8 | -100.0 | 3.0 | yes, recommended |
| Conditioned merge + Single zone per floor type | 3 | 0.00 | -100.0 | -1.6 | 356.2 | 2.6 | 100.0 | 1.6 | -100.0 | -1.1 | yes |
| Conditioned merge + Stacked floor zone multiplier | 3 | 0.00 | -99.7 | -1.5 | 352.2 | 2.8 | 99.7 | 1.5 | -71.8 | -0.1 | yes |
| Semantic merge + Single zone per floor type | 3 | 0.00 | -100.0 | -1.7 | 356.2 | 2.7 | 100.0 | 1.7 | -100.0 | -1.2 | yes |
| Semantic merge + Stack | 104 | 0.00 | -4.6 | -0.0 | 16.6 | 0.1 | 4.6 | 0.0 | -0.5 | -0.0 | yes |
| Semantic merge + Stacked floor zone multiplier | 104 | 0.00 | 25.7 | 0.3 | 126.2 | 1.0 | -25.7 | -0.3 | 47.7 | 0.9 | yes |
| No simplification + Stacked floor zone multiplier | 126 | 0.00 | 33.9 | 0.3 | 138.8 | 1.0 | -33.9 | -0.3 | 49.1 | 0.9 | yes |
8 zonings not generated: the generator refuses them by a documented limit, so they were never simulated
- Perimeter core 3 m + Single zone building: a wing is narrower than twice the perimeter depth
- Perimeter core 3 m + Single zone per floor type: a wing is narrower than twice the perimeter depth
- Perimeter core 3 m + Stack: a wing is narrower than twice the perimeter depth
- Perimeter core 3 m + Stacked floor zone multiplier: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Single zone building: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Single zone per floor type: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Stack: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Stacked floor zone multiplier: a wing is narrower than twice the perimeter depth
7 zonings write the same model as a listed one and are not shown
- Conditioned merge + Stack → Conditioned merge + Single zone per floor type
- No simplification + Single zone building → Conditioned merge + Single zone building
- No simplification + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Single zone building → Conditioned merge + Single zone building
- Single zone per floor + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Stack → Conditioned merge + Single zone per floor type
- Single zone per floor + Stacked floor zone multiplier → Conditioned merge + Stacked floor zone multiplier
3C · 90.1-2019 · 0°
Reference 09e2c5a5a43363a4/R: No simplification + Stack, 126 zones, 3,915 m² conditioned; annual sensible heating 0.3 and cooling 130.5 kWh/m²; peak heating 5.3 and cooling 158.1 kW. Sensible heating is below 1 kWh/m² and is not judged. Serial cost (R5): processor time 49.3 s, wall clock 49.6 s, peak committed memory 303 MiB, each the median of 3 repeats (processor-time CV 2.7 %); a zoning's ratios are its own medians over the reference's.
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | CPU ratio | Wall ratio | Memory ratio | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Single zone building | 1 | 0.00 | -100.0 | -3.1 | 301.0 | 8.1 | 100.0 | 3.1 | -100.0 | 1.0 | 0.063 | 0.065 | 0.688 | yes, recommended |
| Semantic merge + Single zone building | 1 | 0.00 | -100.0 | -3.2 | 301.0 | 8.1 | 100.0 | 3.2 | -100.0 | 0.9 | 0.064 | 0.067 | 0.751 | yes, recommended |
| Conditioned merge + Single zone per floor type | 3 | 0.00 | -100.0 | -2.8 | 301.0 | 7.0 | 100.0 | 2.8 | -100.0 | 1.0 | 0.062 | 0.064 | 0.694 | yes |
| Conditioned merge + Stacked floor zone multiplier | 3 | 0.00 | -100.0 | -2.6 | 301.0 | 6.4 | 100.0 | 2.6 | -100.0 | 1.0 | 0.063 | 0.063 | 0.692 | yes |
| Semantic merge + Single zone per floor type | 3 | 0.00 | -100.0 | -2.8 | 301.0 | 7.0 | 100.0 | 2.8 | -100.0 | 1.0 | 0.064 | 0.064 | 0.753 | yes |
| Semantic merge + Stack | 104 | 0.00 | -4.4 | -0.1 | 14.6 | 0.2 | 4.4 | 0.1 | -6.7 | 0.0 | 0.869 | 0.878 | 1.031 | yes |
| Semantic merge + Stacked floor zone multiplier | 104 | 0.00 | 20.7 | 0.2 | 51.7 | 0.9 | -20.7 | -0.2 | 19.5 | 0.2 | 0.785 | 0.799 | 1.043 | yes |
| No simplification + Stacked floor zone multiplier | 126 | 0.00 | 32.0 | 0.3 | 83.6 | 1.0 | -32.0 | -0.3 | 30.8 | 0.2 | 0.892 | 0.897 | 0.945 | yes |
8 zonings not generated: the generator refuses them by a documented limit, so they were never simulated
- Perimeter core 3 m + Single zone building: a wing is narrower than twice the perimeter depth
- Perimeter core 3 m + Single zone per floor type: a wing is narrower than twice the perimeter depth
- Perimeter core 3 m + Stack: a wing is narrower than twice the perimeter depth
- Perimeter core 3 m + Stacked floor zone multiplier: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Single zone building: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Single zone per floor type: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Stack: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Stacked floor zone multiplier: a wing is narrower than twice the perimeter depth
7 zonings write the same model as a listed one and are not shown
- Conditioned merge + Stack → Conditioned merge + Single zone per floor type
- No simplification + Single zone building → Conditioned merge + Single zone building
- No simplification + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Single zone building → Conditioned merge + Single zone building
- Single zone per floor + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Stack → Conditioned merge + Single zone per floor type
- Single zone per floor + Stacked floor zone multiplier → Conditioned merge + Stacked floor zone multiplier
3C · 90.1-2019 · 45°
Reference 02c419ab81d59876/R: No simplification + Stack, 126 zones, 3,915 m² conditioned; annual sensible heating 0.3 and cooling 130.6 kWh/m²; peak heating 5.2 and cooling 154.6 kW. Sensible heating is below 1 kWh/m² and is not judged. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Single zone building | 1 | 0.00 | -100.0 | -3.0 | 312.5 | 7.6 | 100.0 | 3.0 | -100.0 | 0.5 | yes, recommended |
| Semantic merge + Single zone building | 1 | 0.00 | -100.0 | -3.0 | 312.5 | 7.7 | 100.0 | 3.0 | -100.0 | 0.4 | yes, recommended |
| Conditioned merge + Single zone per floor type | 3 | 0.00 | -100.0 | -2.7 | 312.5 | 6.9 | 100.0 | 2.7 | -100.0 | 0.9 | yes |
| Conditioned merge + Stacked floor zone multiplier | 3 | 0.00 | -100.0 | -2.5 | 312.5 | 6.2 | 100.0 | 2.5 | -100.0 | 0.8 | yes |
| Semantic merge + Single zone per floor type | 3 | 0.00 | -100.0 | -2.7 | 312.5 | 6.9 | 100.0 | 2.7 | -100.0 | 0.9 | yes |
| Semantic merge + Stack | 104 | 0.00 | -4.6 | -0.1 | 15.6 | 0.2 | 4.6 | 0.1 | -4.6 | -0.0 | yes |
| Semantic merge + Stacked floor zone multiplier | 104 | 0.00 | 19.2 | 0.1 | 51.2 | 0.8 | -19.2 | -0.1 | 4.0 | 0.1 | yes |
| No simplification + Stacked floor zone multiplier | 126 | 0.00 | 31.7 | 0.2 | 84.3 | 0.9 | -31.7 | -0.2 | 21.5 | 0.1 | yes |
8 zonings not generated: the generator refuses them by a documented limit, so they were never simulated
- Perimeter core 3 m + Single zone building: a wing is narrower than twice the perimeter depth
- Perimeter core 3 m + Single zone per floor type: a wing is narrower than twice the perimeter depth
- Perimeter core 3 m + Stack: a wing is narrower than twice the perimeter depth
- Perimeter core 3 m + Stacked floor zone multiplier: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Single zone building: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Single zone per floor type: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Stack: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Stacked floor zone multiplier: a wing is narrower than twice the perimeter depth
7 zonings write the same model as a listed one and are not shown
- Conditioned merge + Stack → Conditioned merge + Single zone per floor type
- No simplification + Single zone building → Conditioned merge + Single zone building
- No simplification + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Single zone building → Conditioned merge + Single zone building
- Single zone per floor + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Stack → Conditioned merge + Single zone per floor type
- Single zone per floor + Stacked floor zone multiplier → Conditioned merge + Stacked floor zone multiplier
4A · 90.1-2007 · 0°
Reference f64f36bb55e73e9b/R: No simplification + Stack, 126 zones, 3,915 m² conditioned; annual sensible heating 2.9 and cooling 136.4 kWh/m²; peak heating 36.7 and cooling 172.1 kW. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Single zone building | 1 | 0.00 | -99.1 | -3.9 | 259.8 | 11.0 | 99.1 | 3.9 | -65.8 | 2.8 | no |
| Semantic merge + Single zone building | 1 | 0.00 | -99.1 | -3.9 | 259.8 | 11.0 | 99.1 | 3.9 | -65.7 | 2.7 | no |
| Conditioned merge + Single zone per floor type | 3 | 0.00 | -88.5 | -3.3 | 211.3 | 5.8 | 88.5 | 3.3 | -47.4 | -1.2 | no |
| Conditioned merge + Stacked floor zone multiplier | 3 | 0.00 | -55.3 | -2.2 | 154.6 | 4.4 | 55.3 | 2.2 | -19.7 | -0.0 | no |
| Semantic merge + Single zone per floor type | 3 | 0.00 | -88.5 | -3.3 | 211.3 | 5.8 | 88.5 | 3.3 | -47.4 | -1.2 | no |
| Semantic merge + Stack | 104 | 0.00 | -3.4 | -0.1 | 10.0 | 0.3 | 3.4 | 0.1 | -3.3 | -0.0 | yes, recommended |
| Semantic merge + Stacked floor zone multiplier | 104 | 0.00 | 42.2 | 1.2 | 106.0 | 2.4 | -42.2 | -1.2 | 11.6 | 1.1 | no |
| No simplification + Stacked floor zone multiplier | 126 | 0.00 | 45.9 | 1.3 | 112.6 | 2.5 | -45.9 | -1.3 | 15.6 | 1.1 | no |
8 zonings not generated: the generator refuses them by a documented limit, so they were never simulated
- Perimeter core 3 m + Single zone building: a wing is narrower than twice the perimeter depth
- Perimeter core 3 m + Single zone per floor type: a wing is narrower than twice the perimeter depth
- Perimeter core 3 m + Stack: a wing is narrower than twice the perimeter depth
- Perimeter core 3 m + Stacked floor zone multiplier: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Single zone building: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Single zone per floor type: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Stack: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Stacked floor zone multiplier: a wing is narrower than twice the perimeter depth
7 zonings write the same model as a listed one and are not shown
- Conditioned merge + Stack → Conditioned merge + Single zone per floor type
- No simplification + Single zone building → Conditioned merge + Single zone building
- No simplification + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Single zone building → Conditioned merge + Single zone building
- Single zone per floor + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Stack → Conditioned merge + Single zone per floor type
- Single zone per floor + Stacked floor zone multiplier → Conditioned merge + Stacked floor zone multiplier
4A · 90.1-2007 · 45°
Reference 24585b759fbb1acf/R: No simplification + Stack, 126 zones, 3,915 m² conditioned; annual sensible heating 2.6 and cooling 135.6 kWh/m²; peak heating 31.6 and cooling 164.6 kW. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Single zone building | 1 | 0.00 | -99.9 | -3.7 | 256.2 | 10.4 | 99.9 | 3.7 | -90.2 | 2.4 | no |
| Semantic merge + Single zone building | 1 | 0.00 | -99.9 | -3.8 | 256.2 | 10.4 | 99.9 | 3.8 | -90.1 | 2.4 | no |
| Conditioned merge + Single zone per floor type | 3 | 0.00 | -93.5 | -3.3 | 224.0 | 5.7 | 93.5 | 3.3 | -53.1 | -1.1 | no |
| Conditioned merge + Stacked floor zone multiplier | 3 | 0.00 | -66.8 | -2.4 | 171.7 | 4.5 | 66.8 | 2.4 | -19.3 | -0.2 | no |
| Semantic merge + Single zone per floor type | 3 | 0.00 | -93.5 | -3.3 | 224.0 | 5.7 | 93.5 | 3.3 | -53.1 | -1.2 | no |
| Semantic merge + Stack | 104 | 0.00 | -2.9 | -0.1 | 7.5 | 0.2 | 2.9 | 0.1 | -1.8 | -0.0 | yes, recommended |
| Semantic merge + Stacked floor zone multiplier | 104 | 0.00 | 40.7 | 1.1 | 104.4 | 2.1 | -40.7 | -1.1 | 16.3 | 0.9 | no |
| No simplification + Stacked floor zone multiplier | 126 | 0.00 | 43.8 | 1.2 | 108.8 | 2.2 | -43.8 | -1.2 | 20.7 | 1.0 | no |
8 zonings not generated: the generator refuses them by a documented limit, so they were never simulated
- Perimeter core 3 m + Single zone building: a wing is narrower than twice the perimeter depth
- Perimeter core 3 m + Single zone per floor type: a wing is narrower than twice the perimeter depth
- Perimeter core 3 m + Stack: a wing is narrower than twice the perimeter depth
- Perimeter core 3 m + Stacked floor zone multiplier: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Single zone building: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Single zone per floor type: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Stack: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Stacked floor zone multiplier: a wing is narrower than twice the perimeter depth
7 zonings write the same model as a listed one and are not shown
- Conditioned merge + Stack → Conditioned merge + Single zone per floor type
- No simplification + Single zone building → Conditioned merge + Single zone building
- No simplification + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Single zone building → Conditioned merge + Single zone building
- Single zone per floor + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Stack → Conditioned merge + Single zone per floor type
- Single zone per floor + Stacked floor zone multiplier → Conditioned merge + Stacked floor zone multiplier
4A · 90.1-2019 · 0°
Reference 3c48edec1939ad23/R: No simplification + Stack, 126 zones, 3,915 m² conditioned; annual sensible heating 1.7 and cooling 129.0 kWh/m²; peak heating 24.9 and cooling 185.8 kW. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Single zone building | 1 | 0.00 | -100.0 | -3.9 | 259.0 | 9.8 | 100.0 | 3.9 | -100.0 | -2.2 | no |
| Semantic merge + Single zone building | 1 | 0.00 | -100.0 | -3.9 | 259.0 | 9.8 | 100.0 | 3.9 | -100.0 | -2.2 | no |
| Conditioned merge + Single zone per floor type | 3 | 0.00 | -98.3 | -3.5 | 247.7 | 7.7 | 98.3 | 3.5 | -64.2 | -1.2 | no |
| Conditioned merge + Stacked floor zone multiplier | 3 | 0.00 | -80.8 | -3.0 | 204.8 | 7.2 | 80.8 | 3.0 | -23.0 | -1.4 | no |
| Semantic merge + Single zone per floor type | 3 | 0.00 | -98.3 | -3.6 | 247.7 | 7.7 | 98.3 | 3.6 | -64.2 | -1.2 | no |
| Semantic merge + Stack | 104 | 0.00 | -5.5 | -0.1 | 14.1 | 0.4 | 5.5 | 0.1 | -2.5 | -0.0 | yes, recommended |
| Semantic merge + Stacked floor zone multiplier | 104 | 0.00 | 29.6 | 0.6 | 113.0 | 1.7 | -29.6 | -0.6 | 23.8 | -0.3 | no |
| No simplification + Stacked floor zone multiplier | 126 | 0.00 | 36.3 | 0.8 | 121.5 | 1.9 | -36.3 | -0.8 | 27.4 | -0.3 | no |
8 zonings not generated: the generator refuses them by a documented limit, so they were never simulated
- Perimeter core 3 m + Single zone building: a wing is narrower than twice the perimeter depth
- Perimeter core 3 m + Single zone per floor type: a wing is narrower than twice the perimeter depth
- Perimeter core 3 m + Stack: a wing is narrower than twice the perimeter depth
- Perimeter core 3 m + Stacked floor zone multiplier: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Single zone building: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Single zone per floor type: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Stack: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Stacked floor zone multiplier: a wing is narrower than twice the perimeter depth
7 zonings write the same model as a listed one and are not shown
- Conditioned merge + Stack → Conditioned merge + Single zone per floor type
- No simplification + Single zone building → Conditioned merge + Single zone building
- No simplification + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Single zone building → Conditioned merge + Single zone building
- Single zone per floor + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Stack → Conditioned merge + Single zone per floor type
- Single zone per floor + Stacked floor zone multiplier → Conditioned merge + Stacked floor zone multiplier
4A · 90.1-2019 · 45°
Reference f93d860435820270/R: No simplification + Stack, 126 zones, 3,915 m² conditioned; annual sensible heating 1.7 and cooling 127.2 kWh/m²; peak heating 22.0 and cooling 178.7 kW. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Single zone building | 1 | 0.00 | -100.0 | -3.9 | 252.3 | 9.7 | 100.0 | 3.9 | -100.0 | -2.8 | no |
| Semantic merge + Single zone building | 1 | 0.00 | -100.0 | -3.9 | 252.3 | 9.7 | 100.0 | 3.9 | -100.0 | -2.8 | no |
| Conditioned merge + Single zone per floor type | 3 | 0.00 | -99.5 | -3.6 | 248.3 | 7.7 | 99.5 | 3.6 | -70.9 | -1.9 | no |
| Conditioned merge + Stacked floor zone multiplier | 3 | 0.00 | -86.8 | -3.1 | 213.2 | 7.3 | 86.8 | 3.1 | -29.6 | -2.2 | no |
| Semantic merge + Single zone per floor type | 3 | 0.00 | -99.5 | -3.6 | 248.3 | 7.8 | 99.5 | 3.6 | -70.9 | -1.9 | no |
| Semantic merge + Stack | 104 | 0.00 | -5.3 | -0.1 | 12.9 | 0.3 | 5.3 | 0.1 | -0.7 | -0.1 | yes, recommended |
| Semantic merge + Stacked floor zone multiplier | 104 | 0.00 | 27.0 | 0.6 | 105.5 | 1.5 | -27.0 | -0.6 | 31.2 | -0.5 | no |
| No simplification + Stacked floor zone multiplier | 126 | 0.00 | 34.0 | 0.7 | 110.6 | 1.7 | -34.0 | -0.7 | 32.4 | -0.4 | no |
8 zonings not generated: the generator refuses them by a documented limit, so they were never simulated
- Perimeter core 3 m + Single zone building: a wing is narrower than twice the perimeter depth
- Perimeter core 3 m + Single zone per floor type: a wing is narrower than twice the perimeter depth
- Perimeter core 3 m + Stack: a wing is narrower than twice the perimeter depth
- Perimeter core 3 m + Stacked floor zone multiplier: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Single zone building: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Single zone per floor type: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Stack: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Stacked floor zone multiplier: a wing is narrower than twice the perimeter depth
7 zonings write the same model as a listed one and are not shown
- Conditioned merge + Stack → Conditioned merge + Single zone per floor type
- No simplification + Single zone building → Conditioned merge + Single zone building
- No simplification + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Single zone building → Conditioned merge + Single zone building
- Single zone per floor + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Stack → Conditioned merge + Single zone per floor type
- Single zone per floor + Stacked floor zone multiplier → Conditioned merge + Stacked floor zone multiplier
5A · 90.1-2007 · 0°
Reference 9e05cfddcdba0a76/R: No simplification + Stack, 126 zones, 3,915 m² conditioned; annual sensible heating 6.5 and cooling 118.0 kWh/m²; peak heating 56.2 and cooling 167.3 kW. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Single zone building | 1 | 0.00 | -91.7 | -7.3 | 198.9 | 16.1 | 91.7 | 7.3 | -18.1 | 2.9 | no |
| Semantic merge + Single zone building | 1 | 0.00 | -91.7 | -7.4 | 198.8 | 16.1 | 91.7 | 7.4 | -17.9 | 2.9 | no |
| Conditioned merge + Single zone per floor type | 3 | 0.00 | -74.8 | -6.1 | 149.3 | 9.9 | 74.8 | 6.1 | -38.0 | -1.1 | no |
| Conditioned merge + Stacked floor zone multiplier | 3 | 0.00 | -43.9 | -4.1 | 108.0 | 6.8 | 43.9 | 4.1 | -30.2 | -0.0 | no |
| Semantic merge + Single zone per floor type | 3 | 0.00 | -74.8 | -6.2 | 149.2 | 9.9 | 74.8 | 6.2 | -37.9 | -1.1 | no |
| Semantic merge + Stack | 104 | 0.00 | -2.8 | -0.2 | 6.9 | 0.5 | 2.8 | 0.2 | -1.1 | -0.0 | yes, recommended |
| Semantic merge + Stacked floor zone multiplier | 104 | 0.00 | 30.3 | 2.0 | 61.5 | 3.3 | -30.3 | -2.0 | 6.2 | 1.2 | no |
| No simplification + Stacked floor zone multiplier | 126 | 0.00 | 33.0 | 2.2 | 65.8 | 3.7 | -33.0 | -2.2 | 7.6 | 1.2 | no |
8 zonings not generated: the generator refuses them by a documented limit, so they were never simulated
- Perimeter core 3 m + Single zone building: a wing is narrower than twice the perimeter depth
- Perimeter core 3 m + Single zone per floor type: a wing is narrower than twice the perimeter depth
- Perimeter core 3 m + Stack: a wing is narrower than twice the perimeter depth
- Perimeter core 3 m + Stacked floor zone multiplier: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Single zone building: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Single zone per floor type: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Stack: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Stacked floor zone multiplier: a wing is narrower than twice the perimeter depth
7 zonings write the same model as a listed one and are not shown
- Conditioned merge + Stack → Conditioned merge + Single zone per floor type
- No simplification + Single zone building → Conditioned merge + Single zone building
- No simplification + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Single zone building → Conditioned merge + Single zone building
- Single zone per floor + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Stack → Conditioned merge + Single zone per floor type
- Single zone per floor + Stacked floor zone multiplier → Conditioned merge + Stacked floor zone multiplier
5A · 90.1-2007 · 45°
Reference b19d35adf4e53040/R: No simplification + Stack, 126 zones, 3,915 m² conditioned; annual sensible heating 5.6 and cooling 118.9 kWh/m²; peak heating 48.7 and cooling 161.5 kW. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Single zone building | 1 | 0.00 | -96.0 | -6.9 | 208.7 | 15.0 | 96.0 | 6.9 | -31.5 | 2.0 | no |
| Semantic merge + Single zone building | 1 | 0.00 | -96.0 | -6.9 | 208.6 | 15.0 | 96.0 | 6.9 | -31.4 | 2.0 | no |
| Conditioned merge + Single zone per floor type | 3 | 0.00 | -82.2 | -5.9 | 164.9 | 9.4 | 82.2 | 5.9 | -42.4 | -1.2 | no |
| Conditioned merge + Stacked floor zone multiplier | 3 | 0.00 | -52.4 | -4.2 | 120.9 | 6.7 | 52.4 | 4.2 | -28.9 | -0.1 | no |
| Semantic merge + Single zone per floor type | 3 | 0.00 | -82.2 | -6.0 | 164.9 | 9.5 | 82.2 | 6.0 | -42.3 | -1.2 | no |
| Semantic merge + Stack | 104 | 0.00 | -2.2 | -0.1 | 5.3 | 0.3 | 2.2 | 0.1 | -1.4 | -0.0 | yes, recommended |
| Semantic merge + Stacked floor zone multiplier | 104 | 0.00 | 32.2 | 1.8 | 66.3 | 3.1 | -32.2 | -1.8 | 4.9 | 1.0 | no |
| No simplification + Stacked floor zone multiplier | 126 | 0.00 | 34.4 | 2.0 | 69.6 | 3.3 | -34.4 | -2.0 | 8.7 | 1.1 | no |
8 zonings not generated: the generator refuses them by a documented limit, so they were never simulated
- Perimeter core 3 m + Single zone building: a wing is narrower than twice the perimeter depth
- Perimeter core 3 m + Single zone per floor type: a wing is narrower than twice the perimeter depth
- Perimeter core 3 m + Stack: a wing is narrower than twice the perimeter depth
- Perimeter core 3 m + Stacked floor zone multiplier: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Single zone building: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Single zone per floor type: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Stack: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Stacked floor zone multiplier: a wing is narrower than twice the perimeter depth
7 zonings write the same model as a listed one and are not shown
- Conditioned merge + Stack → Conditioned merge + Single zone per floor type
- No simplification + Single zone building → Conditioned merge + Single zone building
- No simplification + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Single zone building → Conditioned merge + Single zone building
- Single zone per floor + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Stack → Conditioned merge + Single zone per floor type
- Single zone per floor + Stacked floor zone multiplier → Conditioned merge + Stacked floor zone multiplier
5A · 90.1-2019 · 0°
Reference 92c9bff9d9f5796f/R: No simplification + Stack, 126 zones, 3,915 m² conditioned; annual sensible heating 3.4 and cooling 114.3 kWh/m²; peak heating 40.8 and cooling 177.1 kW. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Single zone building | 1 | 0.00 | -99.1 | -5.9 | 239.0 | 13.3 | 99.1 | 5.9 | -53.3 | -0.5 | no |
| Semantic merge + Single zone building | 1 | 0.00 | -99.1 | -5.9 | 238.9 | 13.3 | 99.1 | 5.9 | -53.1 | -0.5 | no |
| Conditioned merge + Single zone per floor type | 3 | 0.00 | -90.5 | -5.3 | 201.2 | 10.3 | 90.5 | 5.3 | -57.2 | -0.3 | no |
| Conditioned merge + Stacked floor zone multiplier | 3 | 0.00 | -59.8 | -4.1 | 149.1 | 8.8 | 59.8 | 4.1 | -29.7 | -0.1 | no |
| Semantic merge + Single zone per floor type | 3 | 0.00 | -90.5 | -5.4 | 201.2 | 10.3 | 90.5 | 5.4 | -57.2 | -0.3 | no |
| Semantic merge + Stack | 104 | 0.00 | -4.5 | -0.2 | 10.9 | 0.5 | 4.5 | 0.2 | -2.0 | -0.0 | yes, recommended |
| Semantic merge + Stacked floor zone multiplier | 104 | 0.00 | 35.2 | 1.3 | 95.4 | 2.8 | -35.2 | -1.3 | 3.2 | 0.2 | no |
| No simplification + Stacked floor zone multiplier | 126 | 0.00 | 39.8 | 1.5 | 102.1 | 3.2 | -39.8 | -1.5 | 10.0 | 0.2 | no |
8 zonings not generated: the generator refuses them by a documented limit, so they were never simulated
- Perimeter core 3 m + Single zone building: a wing is narrower than twice the perimeter depth
- Perimeter core 3 m + Single zone per floor type: a wing is narrower than twice the perimeter depth
- Perimeter core 3 m + Stack: a wing is narrower than twice the perimeter depth
- Perimeter core 3 m + Stacked floor zone multiplier: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Single zone building: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Single zone per floor type: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Stack: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Stacked floor zone multiplier: a wing is narrower than twice the perimeter depth
7 zonings write the same model as a listed one and are not shown
- Conditioned merge + Stack → Conditioned merge + Single zone per floor type
- No simplification + Single zone building → Conditioned merge + Single zone building
- No simplification + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Single zone building → Conditioned merge + Single zone building
- Single zone per floor + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Stack → Conditioned merge + Single zone per floor type
- Single zone per floor + Stacked floor zone multiplier → Conditioned merge + Stacked floor zone multiplier
5A · 90.1-2019 · 45°
Reference 5ba06c1950095f70/R: No simplification + Stack, 126 zones, 3,915 m² conditioned; annual sensible heating 3.1 and cooling 113.7 kWh/m²; peak heating 36.0 and cooling 170.1 kW. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Single zone building | 1 | 0.00 | -99.8 | -5.7 | 236.3 | 12.8 | 99.8 | 5.7 | -81.4 | -1.6 | no |
| Semantic merge + Single zone building | 1 | 0.00 | -99.8 | -5.7 | 236.3 | 12.8 | 99.8 | 5.7 | -80.9 | -1.7 | no |
| Conditioned merge + Single zone per floor type | 3 | 0.00 | -94.5 | -5.3 | 210.3 | 10.2 | 94.5 | 5.3 | -61.7 | -1.0 | no |
| Conditioned merge + Stacked floor zone multiplier | 3 | 0.00 | -67.9 | -4.2 | 160.7 | 8.8 | 67.9 | 4.2 | -30.2 | -0.8 | no |
| Semantic merge + Single zone per floor type | 3 | 0.00 | -94.5 | -5.3 | 210.3 | 10.2 | 94.5 | 5.3 | -61.7 | -1.0 | no |
| Semantic merge + Stack | 104 | 0.00 | -4.3 | -0.2 | 10.3 | 0.4 | 4.3 | 0.2 | -1.8 | -0.1 | yes, recommended |
| Semantic merge + Stacked floor zone multiplier | 104 | 0.00 | 34.3 | 1.2 | 95.7 | 2.7 | -34.3 | -1.2 | 8.7 | 0.0 | no |
| No simplification + Stacked floor zone multiplier | 126 | 0.00 | 38.8 | 1.4 | 100.2 | 2.9 | -38.8 | -1.4 | 13.8 | 0.1 | no |
8 zonings not generated: the generator refuses them by a documented limit, so they were never simulated
- Perimeter core 3 m + Single zone building: a wing is narrower than twice the perimeter depth
- Perimeter core 3 m + Single zone per floor type: a wing is narrower than twice the perimeter depth
- Perimeter core 3 m + Stack: a wing is narrower than twice the perimeter depth
- Perimeter core 3 m + Stacked floor zone multiplier: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Single zone building: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Single zone per floor type: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Stack: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Stacked floor zone multiplier: a wing is narrower than twice the perimeter depth
7 zonings write the same model as a listed one and are not shown
- Conditioned merge + Stack → Conditioned merge + Single zone per floor type
- No simplification + Single zone building → Conditioned merge + Single zone building
- No simplification + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Single zone building → Conditioned merge + Single zone building
- Single zone per floor + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Stack → Conditioned merge + Single zone per floor type
- Single zone per floor + Stacked floor zone multiplier → Conditioned merge + Stacked floor zone multiplier
7A · 90.1-2007 · 0°
Reference aede1f70709c04db/R: No simplification + Stack, 126 zones, 3,915 m² conditioned; annual sensible heating 15.2 and cooling 109.2 kWh/m²; peak heating 111.5 and cooling 170.5 kW. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Single zone building | 1 | 0.00 | -66.1 | -10.8 | 130.7 | 21.8 | 66.1 | 10.8 | 4.2 | 2.6 | no |
| Semantic merge + Single zone building | 1 | 0.00 | -66.1 | -10.9 | 130.6 | 21.8 | 66.1 | 10.9 | 4.3 | 2.6 | no |
| Conditioned merge + Single zone per floor type | 3 | 0.00 | -53.7 | -9.1 | 95.0 | 15.1 | 53.7 | 9.1 | -13.7 | -1.0 | no |
| Conditioned merge + Stacked floor zone multiplier | 3 | 0.00 | -35.7 | -6.4 | 74.6 | 11.1 | 35.7 | 6.4 | -15.2 | -0.0 | no |
| Semantic merge + Single zone per floor type | 3 | 0.00 | -53.7 | -9.2 | 94.9 | 15.1 | 53.7 | 9.2 | -13.6 | -1.0 | no |
| Semantic merge + Stack | 104 | 0.00 | -1.7 | -0.3 | 3.5 | 0.5 | 1.7 | 0.3 | -0.0 | -0.0 | yes, recommended |
| Semantic merge + Stacked floor zone multiplier | 104 | 0.00 | 17.0 | 2.6 | 32.2 | 4.2 | -17.0 | -2.6 | 2.0 | 0.9 | no |
| No simplification + Stacked floor zone multiplier | 126 | 0.00 | 19.0 | 2.9 | 34.8 | 4.7 | -19.0 | -2.9 | 2.0 | 0.9 | no |
8 zonings not generated: the generator refuses them by a documented limit, so they were never simulated
- Perimeter core 3 m + Single zone building: a wing is narrower than twice the perimeter depth
- Perimeter core 3 m + Single zone per floor type: a wing is narrower than twice the perimeter depth
- Perimeter core 3 m + Stack: a wing is narrower than twice the perimeter depth
- Perimeter core 3 m + Stacked floor zone multiplier: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Single zone building: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Single zone per floor type: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Stack: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Stacked floor zone multiplier: a wing is narrower than twice the perimeter depth
7 zonings write the same model as a listed one and are not shown
- Conditioned merge + Stack → Conditioned merge + Single zone per floor type
- No simplification + Single zone building → Conditioned merge + Single zone building
- No simplification + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Single zone building → Conditioned merge + Single zone building
- Single zone per floor + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Stack → Conditioned merge + Single zone per floor type
- Single zone per floor + Stacked floor zone multiplier → Conditioned merge + Stacked floor zone multiplier
7A · 90.1-2007 · 45°
Reference 8fdd605e18be09d8/R: No simplification + Stack, 126 zones, 3,915 m² conditioned; annual sensible heating 13.4 and cooling 108.6 kWh/m²; peak heating 105.9 and cooling 166.7 kW. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Single zone building | 1 | 0.00 | -72.5 | -10.7 | 142.9 | 21.4 | 72.5 | 10.7 | -0.2 | 1.7 | no |
| Semantic merge + Single zone building | 1 | 0.00 | -72.5 | -10.8 | 142.8 | 21.4 | 72.5 | 10.8 | -0.1 | 1.6 | no |
| Conditioned merge + Single zone per floor type | 3 | 0.00 | -57.9 | -8.9 | 102.4 | 14.5 | 57.9 | 8.9 | -19.3 | -1.1 | no |
| Conditioned merge + Stacked floor zone multiplier | 3 | 0.00 | -37.8 | -6.3 | 78.1 | 10.3 | 37.8 | 6.3 | -21.6 | -0.2 | no |
| Semantic merge + Single zone per floor type | 3 | 0.00 | -57.9 | -9.0 | 102.4 | 14.5 | 57.9 | 9.0 | -19.2 | -1.1 | no |
| Semantic merge + Stack | 104 | 0.00 | -1.3 | -0.2 | 2.8 | 0.4 | 1.3 | 0.2 | 0.0 | -0.0 | yes, recommended |
| Semantic merge + Stacked floor zone multiplier | 104 | 0.00 | 19.2 | 2.6 | 35.8 | 4.1 | -19.2 | -2.6 | 2.3 | 0.9 | no |
| No simplification + Stacked floor zone multiplier | 126 | 0.00 | 20.8 | 2.9 | 37.9 | 4.5 | -20.8 | -2.9 | 2.2 | 0.9 | no |
8 zonings not generated: the generator refuses them by a documented limit, so they were never simulated
- Perimeter core 3 m + Single zone building: a wing is narrower than twice the perimeter depth
- Perimeter core 3 m + Single zone per floor type: a wing is narrower than twice the perimeter depth
- Perimeter core 3 m + Stack: a wing is narrower than twice the perimeter depth
- Perimeter core 3 m + Stacked floor zone multiplier: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Single zone building: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Single zone per floor type: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Stack: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Stacked floor zone multiplier: a wing is narrower than twice the perimeter depth
7 zonings write the same model as a listed one and are not shown
- Conditioned merge + Stack → Conditioned merge + Single zone per floor type
- No simplification + Single zone building → Conditioned merge + Single zone building
- No simplification + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Single zone building → Conditioned merge + Single zone building
- Single zone per floor + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Stack → Conditioned merge + Single zone per floor type
- Single zone per floor + Stacked floor zone multiplier → Conditioned merge + Stacked floor zone multiplier
7A · 90.1-2019 · 0°
Reference 20b532e49193b1e3/R: No simplification + Stack, 126 zones, 3,915 m² conditioned; annual sensible heating 8.4 and cooling 105.2 kWh/m²; peak heating 86.1 and cooling 180.2 kW. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Single zone building | 1 | 0.00 | -82.1 | -9.0 | 171.8 | 19.0 | 82.1 | 9.0 | -1.5 | -1.8 | no |
| Semantic merge + Single zone building | 1 | 0.00 | -82.1 | -9.1 | 171.7 | 19.0 | 82.1 | 9.1 | -1.4 | -1.8 | no |
| Conditioned merge + Single zone per floor type | 3 | 0.00 | -71.5 | -8.1 | 136.7 | 15.1 | 71.5 | 8.1 | -24.5 | -0.8 | no |
| Conditioned merge + Stacked floor zone multiplier | 3 | 0.00 | -48.0 | -6.2 | 106.3 | 11.7 | 48.0 | 6.2 | -24.7 | -0.9 | no |
| Semantic merge + Single zone per floor type | 3 | 0.00 | -71.5 | -8.2 | 136.7 | 15.1 | 71.5 | 8.2 | -24.4 | -0.9 | no |
| Semantic merge + Stack | 104 | 0.00 | -2.9 | -0.3 | 6.0 | 0.6 | 2.9 | 0.3 | 0.3 | -0.0 | yes, recommended |
| Semantic merge + Stacked floor zone multiplier | 104 | 0.00 | 22.4 | 2.0 | 49.2 | 3.7 | -22.4 | -2.0 | 5.4 | -0.3 | no |
| No simplification + Stacked floor zone multiplier | 126 | 0.00 | 25.7 | 2.3 | 53.5 | 4.3 | -25.7 | -2.3 | 5.0 | -0.3 | no |
8 zonings not generated: the generator refuses them by a documented limit, so they were never simulated
- Perimeter core 3 m + Single zone building: a wing is narrower than twice the perimeter depth
- Perimeter core 3 m + Single zone per floor type: a wing is narrower than twice the perimeter depth
- Perimeter core 3 m + Stack: a wing is narrower than twice the perimeter depth
- Perimeter core 3 m + Stacked floor zone multiplier: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Single zone building: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Single zone per floor type: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Stack: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Stacked floor zone multiplier: a wing is narrower than twice the perimeter depth
7 zonings write the same model as a listed one and are not shown
- Conditioned merge + Stack → Conditioned merge + Single zone per floor type
- No simplification + Single zone building → Conditioned merge + Single zone building
- No simplification + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Single zone building → Conditioned merge + Single zone building
- Single zone per floor + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Stack → Conditioned merge + Single zone per floor type
- Single zone per floor + Stacked floor zone multiplier → Conditioned merge + Stacked floor zone multiplier
7A · 90.1-2019 · 45°
Reference 823c8d754428ff88/R: No simplification + Stack, 126 zones, 3,915 m² conditioned; annual sensible heating 7.7 and cooling 103.7 kWh/m²; peak heating 80.6 and cooling 172.0 kW. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Single zone building | 1 | 0.00 | -86.0 | -8.9 | 179.4 | 18.6 | 86.0 | 8.9 | -5.0 | -2.3 | no |
| Semantic merge + Single zone building | 1 | 0.00 | -85.9 | -8.9 | 179.3 | 18.6 | 85.9 | 8.9 | -4.9 | -2.3 | no |
| Conditioned merge + Single zone per floor type | 3 | 0.00 | -75.3 | -8.0 | 143.9 | 14.7 | 75.3 | 8.0 | -28.4 | -1.5 | no |
| Conditioned merge + Stacked floor zone multiplier | 3 | 0.00 | -50.4 | -6.1 | 109.8 | 11.4 | 50.4 | 6.1 | -26.9 | -1.9 | no |
| Semantic merge + Single zone per floor type | 3 | 0.00 | -75.3 | -8.1 | 143.9 | 14.8 | 75.3 | 8.1 | -28.3 | -1.5 | no |
| Semantic merge + Stack | 104 | 0.00 | -2.5 | -0.2 | 5.3 | 0.5 | 2.5 | 0.2 | 0.2 | -0.0 | yes, recommended |
| Semantic merge + Stacked floor zone multiplier | 104 | 0.00 | 24.4 | 2.0 | 53.3 | 3.8 | -24.4 | -2.0 | 4.4 | -0.5 | no |
| No simplification + Stacked floor zone multiplier | 126 | 0.00 | 27.4 | 2.3 | 56.7 | 4.2 | -27.4 | -2.3 | 4.0 | -0.4 | no |
8 zonings not generated: the generator refuses them by a documented limit, so they were never simulated
- Perimeter core 3 m + Single zone building: a wing is narrower than twice the perimeter depth
- Perimeter core 3 m + Single zone per floor type: a wing is narrower than twice the perimeter depth
- Perimeter core 3 m + Stack: a wing is narrower than twice the perimeter depth
- Perimeter core 3 m + Stacked floor zone multiplier: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Single zone building: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Single zone per floor type: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Stack: a wing is narrower than twice the perimeter depth
- Perimeter core 4.57 m + Stacked floor zone multiplier: a wing is narrower than twice the perimeter depth
7 zonings write the same model as a listed one and are not shown
- Conditioned merge + Stack → Conditioned merge + Single zone per floor type
- No simplification + Single zone building → Conditioned merge + Single zone building
- No simplification + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Single zone building → Conditioned merge + Single zone building
- Single zone per floor + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Stack → Conditioned merge + Single zone per floor type
- Single zone per floor + Stacked floor zone multiplier → Conditioned merge + Stacked floor zone multiplier
Atlas programs
The atlas programs each program key of the prototype takes, as the suite's saved inputs name them (release 2.4.0 IDs); the prototype's geometry and glazing are BEMGen's DOE record. Method and caveats.