Small hotel zoning
SmallHotel · geometric LOD study drop 5 · atlas inputs release 2.4.0 · BEMGen 99c0b0adcd44
- Prototype
- SmallHotel
- Cells
- 24: 6 climate zones × 2 vintages × 2 orientations
- Cells with a recommended zoning
- 24 of 24
- Robust across orientations
- 12 of 12 cell pairs: Semantic merge + Stack (6)
- Reference zoning
- No simplification + Stack
- Reference zones
- 67
- Most often recommended
- Conditioned merge + Stacked floor zone multiplier (13 of 24 cells)
- Serial cost (R5)
- timed in 2 of 24 cells (3C 90.1-2019 0°, 5A 90.1-2019 0°)
Robust across orientations
Robust across orientations in 12 of 12 cell pairs (0° and 45°).
| Climate zone | Vintage | Robust zoning | Zones | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Area change % | CPU ratio | Wall ratio | Memory ratio | Per orientation |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 2A | 90.1-2007 | Conditioned merge + Stack (tie: Conditioned merge + Stacked floor zone multiplier) | 8 | – | -5.5 | – | 5.7 | – | 5.5 | 0.00 | not timed | recommended at both orientations | ||
| 2A | 90.1-2019 | Conditioned merge + Stack (tie: Conditioned merge + Stacked floor zone multiplier) | 8 | – | -6.3 | – | 6.6 | – | 6.3 | 0.00 | not timed | recommended at both orientations | ||
| 2B | 90.1-2007 | Conditioned merge + Stack (tie: Conditioned merge + Stacked floor zone multiplier) | 8 | – | -5.9 | – | 6.1 | – | 5.9 | 0.00 | not timed | recommended at both orientations | ||
| 2B | 90.1-2019 | Conditioned merge + Stack (tie: Conditioned merge + Stacked floor zone multiplier) | 8 | – | -6.9 | – | 7.2 | – | 6.9 | 0.00 | not timed | recommended at both orientations | ||
| 3C | 90.1-2007 | Conditioned merge + Stack (tie: Conditioned merge + Stacked floor zone multiplier) | 8 | – | -8.4 | – | 8.7 | – | 8.4 | 0.00 | not timed | recommended at both orientations | ||
| 3C | 90.1-2019 | Conditioned merge + Stacked floor zone multiplier | 8 | – | -9.1 | – | 10.8 | – | 9.1 | 0.00 | 0.141 | 0.142 | 0.826 | recommended at both orientations |
| 4A | 90.1-2007 | Semantic merge + Stack | 43 | -13.4 | -0.3 | 35.1 | 1.4 | 13.4 | 0.3 | 0.00 | not timed | 0°: Semantic merge + Stack (43 zones) · 45°: Conditioned merge + Stack (8 zones), Conditioned merge + Stacked floor zone multiplier (8 zones) | ||
| 4A | 90.1-2019 | Semantic merge + Stack | 43 | -8.6 | -0.3 | 21.4 | 1.6 | 8.6 | 0.3 | 0.00 | not timed | recommended at both orientations | ||
| 5A | 90.1-2007 | Semantic merge + Stack | 43 | -7.8 | -0.5 | 17.8 | 1.5 | 7.8 | 0.5 | 0.00 | not timed | recommended at both orientations | ||
| 5A | 90.1-2019 | Semantic merge + Stack | 43 | -5.8 | -0.5 | 12.8 | 1.5 | 5.8 | 0.5 | 0.00 | 0.613 | 0.612 | 0.930 | recommended at both orientations |
| 7A | 90.1-2007 | Semantic merge + Stack | 43 | -4.0 | -0.5 | 8.7 | 1.5 | 4.0 | 0.5 | 0.00 | not timed | recommended at both orientations | ||
| 7A | 90.1-2019 | Semantic merge + Stack | 43 | -3.1 | -0.6 | 6.3 | 1.5 | 3.1 | 0.6 | 0.00 | not timed | recommended at both orientations | ||
For each prototype, climate zone and vintage, the robust zoning is the coarsest (fewest modelled zones) that meets the threshold at every orientation of the cell pair, by the writer's own verdict on each zoning at each orientation, with at most the reference's zone count, as the writer bounds a recommendation (D-220); a duplicate never meets, as the writer lists it. Ties at the fewest zones go to a zoning both orientations recommend, else to the first in the study's zoning order (simplifier, join pieces, perimeter depth, stacker, IWHT, FHT); the tied zonings are named. The errors reported are the worse of the orientations' values for each metric, so the row is a bound, not a mean; the cost ratios are the medians over the timed sites of that zoning in the pair. Where both orientations recommend the same zoning it is the robust one. A pair where no zoning meets the threshold at both orientations says so and names each orientation's own recommendation; the per-orientation rows below stay the reading for one orientation. The cost ratios are the median over the timed sites of the robust zoning in the pair (in this drop one orientation at most is timed, so the ratio is that site's); not timed where none is. The rule and its limits.
Recommended zonings
| Climate zone | Vintage | Orientation | Reference zones | Heating kWh/m² | Cooling kWh/m² | Recommended zoning | Zones | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Area change % | CPU ratio | Wall ratio | Memory ratio |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 2A | 90.1-2007 | 0° | 67 | 0.0 | 114.2 | Conditioned merge + Stack | 8 | – | -5.5 | – | 5.7 | – | 5.5 | 0.00 | not timed | ||
| 2A | 90.1-2007 | 0° | 67 | 0.0 | 114.2 | Conditioned merge + Stacked floor zone multiplier | 8 | – | -5.5 | – | 6.4 | – | 5.5 | 0.00 | not timed | ||
| 2A | 90.1-2007 | 45° | 67 | 0.0 | 110.4 | Conditioned merge + Stack | 8 | – | -4.4 | – | 4.6 | – | 4.4 | 0.00 | not timed | ||
| 2A | 90.1-2007 | 45° | 67 | 0.0 | 110.4 | Conditioned merge + Stacked floor zone multiplier | 8 | – | -4.5 | – | 5.6 | – | 4.5 | 0.00 | not timed | ||
| 2A | 90.1-2019 | 0° | 67 | 0.0 | 94.8 | Conditioned merge + Stack | 8 | – | -6.3 | – | 6.6 | – | 6.3 | 0.00 | not timed | ||
| 2A | 90.1-2019 | 0° | 67 | 0.0 | 94.8 | Conditioned merge + Stacked floor zone multiplier | 8 | – | -6.3 | – | 7.5 | – | 6.3 | 0.00 | not timed | ||
| 2A | 90.1-2019 | 45° | 67 | 0.0 | 90.7 | Conditioned merge + Stack | 8 | – | -5.7 | – | 5.9 | – | 5.7 | 0.00 | not timed | ||
| 2A | 90.1-2019 | 45° | 67 | 0.0 | 90.7 | Conditioned merge + Stacked floor zone multiplier | 8 | – | -5.7 | – | 7.2 | – | 5.7 | 0.00 | not timed | ||
| 2B | 90.1-2007 | 0° | 67 | 0.0 | 109.8 | Conditioned merge + Stack | 8 | – | -5.9 | – | 6.1 | – | 5.9 | 0.00 | not timed | ||
| 2B | 90.1-2007 | 0° | 67 | 0.0 | 109.8 | Conditioned merge + Stacked floor zone multiplier | 8 | – | -5.6 | – | 6.7 | – | 5.6 | 0.00 | not timed | ||
| 2B | 90.1-2007 | 45° | 67 | 0.0 | 106.5 | Conditioned merge + Stack | 8 | – | -4.7 | – | 5.0 | – | 4.7 | 0.00 | not timed | ||
| 2B | 90.1-2007 | 45° | 67 | 0.0 | 106.5 | Conditioned merge + Stacked floor zone multiplier | 8 | – | -4.7 | – | 5.9 | – | 4.7 | 0.00 | not timed | ||
| 2B | 90.1-2019 | 0° | 67 | 0.1 | 91.2 | Conditioned merge + Stack | 8 | – | -6.9 | – | 7.2 | – | 6.9 | 0.00 | not timed | ||
| 2B | 90.1-2019 | 0° | 67 | 0.1 | 91.2 | Conditioned merge + Stacked floor zone multiplier | 8 | – | -6.4 | – | 7.8 | – | 6.4 | 0.00 | not timed | ||
| 2B | 90.1-2019 | 45° | 67 | 0.0 | 87.0 | Conditioned merge + Stack | 8 | – | -6.2 | – | 6.5 | – | 6.2 | 0.00 | not timed | ||
| 2B | 90.1-2019 | 45° | 67 | 0.0 | 87.0 | Conditioned merge + Stacked floor zone multiplier | 8 | – | -5.7 | – | 7.5 | – | 5.7 | 0.00 | not timed | ||
| 3C | 90.1-2007 | 0° | 67 | 0.0 | 84.1 | Conditioned merge + Stack | 8 | – | -8.4 | – | 8.7 | – | 8.4 | 0.00 | not timed | ||
| 3C | 90.1-2007 | 0° | 67 | 0.0 | 84.1 | Conditioned merge + Stacked floor zone multiplier | 8 | – | -8.0 | – | 9.2 | – | 8.0 | 0.00 | not timed | ||
| 3C | 90.1-2007 | 45° | 67 | 0.0 | 86.4 | Conditioned merge + Stack | 8 | – | -6.7 | – | 6.9 | – | 6.7 | 0.00 | not timed | ||
| 3C | 90.1-2007 | 45° | 67 | 0.0 | 86.4 | Conditioned merge + Stacked floor zone multiplier | 8 | – | -6.6 | – | 7.9 | – | 6.6 | 0.00 | not timed | ||
| 3C | 90.1-2019 | 0° | 67 | 0.0 | 68.4 | Conditioned merge + Stacked floor zone multiplier | 8 | – | -9.1 | – | 10.8 | – | 9.1 | 0.00 | 0.141 | 0.142 | 0.826 |
| 3C | 90.1-2019 | 45° | 67 | 0.0 | 67.6 | Conditioned merge + Stack | 8 | – | -9.3 | – | 9.5 | – | 9.3 | 0.00 | not timed | ||
| 3C | 90.1-2019 | 45° | 67 | 0.0 | 67.6 | Conditioned merge + Stacked floor zone multiplier | 8 | – | -8.2 | – | 10.3 | – | 8.2 | 0.00 | not timed | ||
| 4A | 90.1-2007 | 0° | 67 | 1.3 | 82.1 | Semantic merge + Stack | 43 | -5.6 | -0.3 | 17.5 | 1.3 | 5.6 | 0.3 | 0.00 | not timed | ||
| 4A | 90.1-2007 | 45° | 67 | 0.8 | 80.4 | Conditioned merge + Stack | 8 | -78.3 | -8.7 | 211.7 | 9.1 | 78.3 | 8.7 | 0.00 | not timed | ||
| 4A | 90.1-2007 | 45° | 67 | 0.8 | 80.4 | Conditioned merge + Stacked floor zone multiplier | 8 | 111.9 | -5.6 | 310.0 | 7.7 | -111.9 | 5.6 | 0.00 | not timed | ||
| 4A | 90.1-2019 | 0° | 67 | 1.8 | 68.3 | Semantic merge + Stack | 43 | -6.8 | -0.3 | 17.9 | 1.6 | 6.8 | 0.3 | 0.00 | not timed | ||
| 4A | 90.1-2019 | 45° | 67 | 1.5 | 64.8 | Semantic merge + Stack | 43 | -8.6 | -0.2 | 21.4 | 1.6 | 8.6 | 0.2 | 0.00 | not timed | ||
| 5A | 90.1-2007 | 0° | 67 | 4.1 | 69.8 | Semantic merge + Stack | 43 | -4.1 | -0.5 | 10.4 | 1.5 | 4.1 | 0.5 | 0.00 | not timed | ||
| 5A | 90.1-2007 | 45° | 67 | 2.6 | 70.1 | Semantic merge + Stack | 43 | -7.8 | -0.5 | 17.8 | 1.5 | 7.8 | 0.5 | 0.00 | not timed | ||
| 5A | 90.1-2019 | 0° | 67 | 4.5 | 59.8 | Semantic merge + Stack | 43 | -4.4 | -0.5 | 10.2 | 1.5 | 4.4 | 0.5 | 0.00 | 0.613 | 0.612 | 0.930 |
| 5A | 90.1-2019 | 45° | 67 | 3.6 | 57.6 | Semantic merge + Stack | 43 | -5.8 | -0.5 | 12.8 | 1.4 | 5.8 | 0.5 | 0.00 | not timed | ||
| 7A | 90.1-2007 | 0° | 67 | 8.5 | 67.4 | Semantic merge + Stack | 43 | -2.4 | -0.5 | 5.6 | 1.4 | 2.4 | 0.5 | 0.00 | not timed | ||
| 7A | 90.1-2007 | 45° | 67 | 6.1 | 66.3 | Semantic merge + Stack | 43 | -4.0 | -0.5 | 8.7 | 1.5 | 4.0 | 0.5 | 0.00 | not timed | ||
| 7A | 90.1-2019 | 0° | 67 | 9.5 | 55.8 | Semantic merge + Stack | 43 | -2.5 | -0.6 | 5.4 | 1.5 | 2.5 | 0.6 | 0.00 | not timed | ||
| 7A | 90.1-2019 | 45° | 67 | 8.5 | 52.8 | Semantic merge + Stack | 43 | -3.1 | -0.6 | 6.3 | 1.4 | 3.1 | 0.6 | 0.00 | not timed | ||
The coarsest zonings (fewest modelled zones) meeting the threshold; ties are all listed. Errors are the test zoning against the reference: annual sensible load, hourly CV(RMSE) and NMBE, and the change of conditioned floor area. A muted value belongs to a load the threshold does not judge; a dash is a value the runner did not store; a flagged value carries the runner's own flag. The cost ratios are the serial timing pass (R5): the zoning's processor time, wall clock and peak committed memory over its reference's, each the median of its repeats; not timed marks a cell outside the timed ones. Cost protocol.
Every zoning by cell
2A · 90.1-2007 · 0°
Reference 090b1a61cc9e3e64/R: No simplification + Stack, 67 zones, 3,953 m² conditioned; annual sensible heating 0.0 and cooling 114.2 kWh/m²; peak heating 2.6 and cooling 109.3 kW. Sensible heating is below 1 kWh/m² and is not judged. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Single zone building | 1 | 1.52 | – | -4.9 | – | 14.8 | – | 4.9 | -100.0 | 8.3 | no |
| Perimeter core 3 m + Single zone building | 1 | 1.52 | – | -4.9 | – | 14.8 | – | 4.9 | -100.0 | 8.3 | no |
| Perimeter core 4.57 m + Single zone building | 1 | 1.52 | – | -4.9 | – | 14.8 | – | 4.9 | -100.0 | 8.3 | no |
| Conditioned merge + Single zone per floor type | 4 | 1.52 | – | -5.8 | – | 6.8 | – | 5.8 | -100.0 | -3.5 | no |
| Perimeter core 3 m + Single zone per floor type | 4 | 1.52 | – | -5.8 | – | 6.7 | – | 5.8 | -100.0 | -3.5 | no |
| Perimeter core 4.57 m + Single zone per floor type | 4 | 1.52 | – | -5.8 | – | 6.7 | – | 5.8 | -100.0 | -3.5 | no |
| Single zone per floor + Stacked floor zone multiplier | 4 | 1.52 | – | -5.9 | – | 7.5 | – | 5.9 | 154.4 | -1.9 | no |
| Conditioned merge + Stack | 8 | 0.00 | – | -5.5 | – | 5.7 | – | 5.5 | -100.0 | -2.8 | yes, recommended |
| Conditioned merge + Stacked floor zone multiplier | 8 | 0.00 | – | -5.5 | – | 6.4 | – | 5.5 | 151.3 | -1.3 | yes, recommended |
| Perimeter core 3 m + Stack | 20 | 1.52 | – | -3.5 | – | 4.5 | – | 3.5 | -11.1 | -3.0 | no |
| Perimeter core 3 m + Stacked floor zone multiplier | 20 | 1.52 | – | -3.5 | – | 5.2 | – | 3.5 | 148.3 | -1.5 | no |
| Perimeter core 4.57 m + Stack | 20 | 1.52 | – | -3.7 | – | 4.7 | – | 3.7 | -22.4 | -3.3 | no |
| Perimeter core 4.57 m + Stacked floor zone multiplier | 20 | 1.52 | – | -3.7 | – | 5.4 | – | 3.7 | 153.6 | -1.8 | no |
| Semantic merge + Stack | 43 | 0.00 | – | -0.0 | – | 1.2 | – | 0.0 | -4.0 | -1.2 | yes |
| Semantic merge + Stacked floor zone multiplier | 43 | 0.00 | – | -0.0 | – | 2.6 | – | 0.0 | 174.5 | 0.4 | yes |
| No simplification + Stacked floor zone multiplier | 67 | 0.00 | – | 0.0 | – | 2.1 | – | -0.0 | 176.1 | 1.5 | yes |
7 zonings write the same model as a listed one and are not shown
- No simplification + Single zone building → Conditioned merge + Single zone building
- No simplification + Single zone per floor type → Conditioned merge + Single zone per floor type
- Semantic merge + Single zone building → Conditioned merge + Single zone building
- Semantic merge + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Single zone building → Conditioned merge + Single zone building
- Single zone per floor + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Stack → Conditioned merge + Single zone per floor type
2A · 90.1-2007 · 45°
Reference 43a2bd175a92fcad/R: No simplification + Stack, 67 zones, 3,953 m² conditioned; annual sensible heating 0.0 and cooling 110.4 kWh/m²; peak heating 0.7 and cooling 102.4 kW. Sensible heating is below 1 kWh/m² and is not judged. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Single zone building | 1 | 1.52 | – | -3.8 | – | 13.4 | – | 3.8 | -100.0 | 6.7 | no |
| Perimeter core 3 m + Single zone building | 1 | 1.52 | – | -3.8 | – | 13.3 | – | 3.8 | -100.0 | 6.7 | no |
| Perimeter core 4.57 m + Single zone building | 1 | 1.52 | – | -3.8 | – | 13.3 | – | 3.8 | -100.0 | 6.7 | no |
| Conditioned merge + Single zone per floor type | 4 | 1.52 | – | -4.8 | – | 6.0 | – | 4.8 | -100.0 | -4.4 | no |
| Perimeter core 3 m + Single zone per floor type | 4 | 1.52 | – | -4.8 | – | 6.0 | – | 4.8 | -100.0 | -4.3 | no |
| Perimeter core 4.57 m + Single zone per floor type | 4 | 1.52 | – | -4.8 | – | 6.0 | – | 4.8 | -100.0 | -4.3 | no |
| Single zone per floor + Stacked floor zone multiplier | 4 | 1.52 | – | -5.0 | – | 6.9 | – | 5.0 | 275.8 | -3.2 | no |
| Conditioned merge + Stack | 8 | 0.00 | – | -4.4 | – | 4.6 | – | 4.4 | -100.0 | -2.7 | yes, recommended |
| Conditioned merge + Stacked floor zone multiplier | 8 | 0.00 | – | -4.5 | – | 5.6 | – | 4.5 | 261.1 | -2.2 | yes, recommended |
| Perimeter core 3 m + Stack | 20 | 1.52 | – | -3.0 | – | 4.4 | – | 3.0 | -100.0 | -3.7 | no |
| Perimeter core 3 m + Stacked floor zone multiplier | 20 | 1.52 | – | -3.2 | – | 5.0 | – | 3.2 | 400.9 | -2.6 | no |
| Perimeter core 4.57 m + Stack | 20 | 1.52 | – | -3.3 | – | 4.6 | – | 3.3 | -100.0 | -4.1 | no |
| Perimeter core 4.57 m + Stacked floor zone multiplier | 20 | 1.52 | – | -3.5 | – | 5.2 | – | 3.5 | 409.4 | -2.9 | no |
| Semantic merge + Stack | 43 | 0.00 | – | -0.0 | – | 1.3 | – | 0.0 | -39.5 | -0.7 | yes |
| Semantic merge + Stacked floor zone multiplier | 43 | 0.00 | – | -0.0 | – | 2.5 | – | 0.0 | 518.0 | -1.0 | yes |
| No simplification + Stacked floor zone multiplier | 67 | 0.00 | – | -0.1 | – | 2.1 | – | 0.1 | 511.2 | 0.0 | yes |
7 zonings write the same model as a listed one and are not shown
- No simplification + Single zone building → Conditioned merge + Single zone building
- No simplification + Single zone per floor type → Conditioned merge + Single zone per floor type
- Semantic merge + Single zone building → Conditioned merge + Single zone building
- Semantic merge + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Single zone building → Conditioned merge + Single zone building
- Single zone per floor + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Stack → Conditioned merge + Single zone per floor type
2A · 90.1-2019 · 0°
Reference c55aeaefae243cdf/R: No simplification + Stack, 67 zones, 3,953 m² conditioned; annual sensible heating 0.0 and cooling 94.8 kWh/m²; peak heating 3.1 and cooling 98.3 kW. Sensible heating is below 1 kWh/m² and is not judged. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Single zone building | 1 | 1.52 | – | -5.7 | – | 16.6 | – | 5.7 | -100.0 | 9.4 | no |
| Perimeter core 3 m + Single zone building | 1 | 1.52 | – | -5.7 | – | 16.6 | – | 5.7 | -100.0 | 9.4 | no |
| Perimeter core 4.57 m + Single zone building | 1 | 1.52 | – | -5.7 | – | 16.6 | – | 5.7 | -100.0 | 9.4 | no |
| Conditioned merge + Single zone per floor type | 4 | 1.52 | – | -6.9 | – | 8.1 | – | 6.9 | -100.0 | -3.8 | no |
| Perimeter core 3 m + Single zone per floor type | 4 | 1.52 | – | -6.8 | – | 8.0 | – | 6.8 | -100.0 | -3.8 | no |
| Perimeter core 4.57 m + Single zone per floor type | 4 | 1.52 | – | -6.8 | – | 8.0 | – | 6.8 | -100.0 | -3.8 | no |
| Single zone per floor + Stacked floor zone multiplier | 4 | 1.52 | – | -6.8 | – | 9.0 | – | 6.8 | 128.5 | -2.4 | no |
| Conditioned merge + Stack | 8 | 0.00 | – | -6.3 | – | 6.6 | – | 6.3 | -100.0 | -2.9 | yes, recommended |
| Conditioned merge + Stacked floor zone multiplier | 8 | 0.00 | – | -6.3 | – | 7.5 | – | 6.3 | 127.1 | -1.3 | yes, recommended |
| Perimeter core 3 m + Stack | 20 | 1.52 | – | -4.0 | – | 5.4 | – | 4.0 | -30.0 | -3.4 | no |
| Perimeter core 3 m + Stacked floor zone multiplier | 20 | 1.52 | – | -4.0 | – | 6.5 | – | 4.0 | 121.4 | -2.2 | no |
| Perimeter core 4.57 m + Stack | 20 | 1.52 | – | -4.1 | – | 5.4 | – | 4.1 | -33.3 | -4.1 | no |
| Perimeter core 4.57 m + Stacked floor zone multiplier | 20 | 1.52 | – | -4.1 | – | 6.5 | – | 4.1 | 119.9 | -2.6 | no |
| Semantic merge + Stack | 43 | 0.00 | – | 0.1 | – | 1.5 | – | -0.1 | -3.5 | -1.2 | yes |
| Semantic merge + Stacked floor zone multiplier | 43 | 0.00 | – | 0.2 | – | 3.3 | – | -0.2 | 130.5 | 0.3 | yes |
| No simplification + Stacked floor zone multiplier | 67 | 0.00 | – | 0.2 | – | 2.7 | – | -0.2 | 131.4 | 1.5 | yes |
7 zonings write the same model as a listed one and are not shown
- No simplification + Single zone building → Conditioned merge + Single zone building
- No simplification + Single zone per floor type → Conditioned merge + Single zone per floor type
- Semantic merge + Single zone building → Conditioned merge + Single zone building
- Semantic merge + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Single zone building → Conditioned merge + Single zone building
- Single zone per floor + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Stack → Conditioned merge + Single zone per floor type
2A · 90.1-2019 · 45°
Reference 84c4d582b8c98e7e/R: No simplification + Stack, 67 zones, 3,953 m² conditioned; annual sensible heating 0.0 and cooling 90.7 kWh/m²; peak heating 1.7 and cooling 92.2 kW. Sensible heating is below 1 kWh/m² and is not judged. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Single zone building | 1 | 1.52 | – | -5.1 | – | 15.4 | – | 5.1 | -100.0 | 9.0 | no |
| Perimeter core 3 m + Single zone building | 1 | 1.52 | – | -5.1 | – | 15.4 | – | 5.1 | -100.0 | 9.0 | no |
| Perimeter core 4.57 m + Single zone building | 1 | 1.52 | – | -5.1 | – | 15.4 | – | 5.1 | -100.0 | 9.0 | no |
| Conditioned merge + Single zone per floor type | 4 | 1.52 | – | -6.3 | – | 7.7 | – | 6.3 | -100.0 | -3.9 | no |
| Perimeter core 3 m + Single zone per floor type | 4 | 1.52 | – | -6.3 | – | 7.7 | – | 6.3 | -100.0 | -3.8 | no |
| Perimeter core 4.57 m + Single zone per floor type | 4 | 1.52 | – | -6.3 | – | 7.7 | – | 6.3 | -100.0 | -3.8 | no |
| Single zone per floor + Stacked floor zone multiplier | 4 | 1.52 | – | -6.3 | – | 8.8 | – | 6.3 | 239.0 | -3.0 | no |
| Conditioned merge + Stack | 8 | 0.00 | – | -5.7 | – | 5.9 | – | 5.7 | -100.0 | -2.7 | yes, recommended |
| Conditioned merge + Stacked floor zone multiplier | 8 | 0.00 | – | -5.7 | – | 7.2 | – | 5.7 | 235.4 | -1.4 | yes, recommended |
| Perimeter core 3 m + Stack | 20 | 1.52 | – | -3.7 | – | 5.3 | – | 3.7 | -49.5 | -2.9 | no |
| Perimeter core 3 m + Stacked floor zone multiplier | 20 | 1.52 | – | -3.8 | – | 6.4 | – | 3.8 | 232.8 | -1.8 | no |
| Perimeter core 4.57 m + Stack | 20 | 1.52 | – | -3.8 | – | 5.4 | – | 3.8 | -63.4 | -3.4 | no |
| Perimeter core 4.57 m + Stacked floor zone multiplier | 20 | 1.52 | – | -4.0 | – | 6.4 | – | 4.0 | 229.2 | -2.4 | no |
| Semantic merge + Stack | 43 | 0.00 | – | 0.1 | – | 1.5 | – | -0.1 | -4.7 | -1.1 | yes |
| Semantic merge + Stacked floor zone multiplier | 43 | 0.00 | – | 0.2 | – | 3.4 | – | -0.2 | 246.8 | 0.1 | yes |
| No simplification + Stacked floor zone multiplier | 67 | 0.00 | – | 0.1 | – | 2.9 | – | -0.1 | 251.7 | 1.1 | yes |
7 zonings write the same model as a listed one and are not shown
- No simplification + Single zone building → Conditioned merge + Single zone building
- No simplification + Single zone per floor type → Conditioned merge + Single zone per floor type
- Semantic merge + Single zone building → Conditioned merge + Single zone building
- Semantic merge + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Single zone building → Conditioned merge + Single zone building
- Single zone per floor + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Stack → Conditioned merge + Single zone per floor type
2B · 90.1-2007 · 0°
Reference 1596a7f8f7ff56d2/R: No simplification + Stack, 67 zones, 3,953 m² conditioned; annual sensible heating 0.0 and cooling 109.8 kWh/m²; peak heating 3.9 and cooling 114.1 kW. Sensible heating is below 1 kWh/m² and is not judged. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Single zone building | 1 | 1.52 | – | -5.5 | – | 16.6 | – | 5.5 | -100.0 | 9.0 | no |
| Perimeter core 3 m + Single zone building | 1 | 1.52 | – | -5.5 | – | 16.6 | – | 5.5 | -100.0 | 9.1 | no |
| Perimeter core 4.57 m + Single zone building | 1 | 1.52 | – | -5.5 | – | 16.6 | – | 5.5 | -100.0 | 9.1 | no |
| Conditioned merge + Single zone per floor type | 4 | 1.52 | – | -6.3 | – | 7.3 | – | 6.3 | -100.0 | -3.2 | no |
| Perimeter core 3 m + Single zone per floor type | 4 | 1.52 | – | -6.2 | – | 7.3 | – | 6.2 | -100.0 | -3.2 | no |
| Perimeter core 4.57 m + Single zone per floor type | 4 | 1.52 | – | -6.2 | – | 7.3 | – | 6.2 | -100.0 | -3.2 | no |
| Single zone per floor + Stacked floor zone multiplier | 4 | 1.52 | – | -6.0 | – | 8.0 | – | 6.0 | 107.6 | -1.2 | no |
| Conditioned merge + Stack | 8 | 0.00 | – | -5.9 | – | 6.1 | – | 5.9 | -100.0 | -2.7 | yes, recommended |
| Conditioned merge + Stacked floor zone multiplier | 8 | 0.00 | – | -5.6 | – | 6.7 | – | 5.6 | 106.6 | -0.7 | yes, recommended |
| Perimeter core 3 m + Stack | 20 | 1.52 | – | -3.4 | – | 4.8 | – | 3.4 | -11.2 | -2.5 | no |
| Perimeter core 3 m + Stacked floor zone multiplier | 20 | 1.52 | – | -3.2 | – | 5.6 | – | 3.2 | 106.0 | -0.6 | no |
| Perimeter core 4.57 m + Stack | 20 | 1.52 | – | -3.8 | – | 5.0 | – | 3.8 | -24.1 | -2.4 | no |
| Perimeter core 4.57 m + Stacked floor zone multiplier | 20 | 1.52 | – | -3.6 | – | 5.7 | – | 3.6 | 100.5 | -1.1 | no |
| Semantic merge + Stack | 43 | 0.00 | – | -0.2 | – | 1.1 | – | 0.2 | -3.8 | -1.1 | yes |
| Semantic merge + Stacked floor zone multiplier | 43 | 0.00 | – | 0.2 | – | 2.8 | – | -0.2 | 113.2 | 0.5 | yes |
| No simplification + Stacked floor zone multiplier | 67 | 0.00 | – | 0.3 | – | 2.4 | – | -0.3 | 114.5 | 1.7 | yes |
7 zonings write the same model as a listed one and are not shown
- No simplification + Single zone building → Conditioned merge + Single zone building
- No simplification + Single zone per floor type → Conditioned merge + Single zone per floor type
- Semantic merge + Single zone building → Conditioned merge + Single zone building
- Semantic merge + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Single zone building → Conditioned merge + Single zone building
- Single zone per floor + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Stack → Conditioned merge + Single zone per floor type
2B · 90.1-2007 · 45°
Reference 0aed37a18db40b14/R: No simplification + Stack, 67 zones, 3,953 m² conditioned; annual sensible heating 0.0 and cooling 106.5 kWh/m²; peak heating 1.1 and cooling 106.5 kW. Sensible heating is below 1 kWh/m² and is not judged. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Single zone building | 1 | 1.52 | – | -4.3 | – | 14.8 | – | 4.3 | -100.0 | 7.8 | no |
| Perimeter core 3 m + Single zone building | 1 | 1.52 | – | -4.3 | – | 14.8 | – | 4.3 | -100.0 | 7.8 | no |
| Perimeter core 4.57 m + Single zone building | 1 | 1.52 | – | -4.3 | – | 14.8 | – | 4.3 | -100.0 | 7.8 | no |
| Conditioned merge + Single zone per floor type | 4 | 1.52 | – | -5.2 | – | 6.5 | – | 5.2 | -100.0 | -2.4 | no |
| Perimeter core 3 m + Single zone per floor type | 4 | 1.52 | – | -5.1 | – | 6.4 | – | 5.1 | -100.0 | -2.3 | no |
| Perimeter core 4.57 m + Single zone per floor type | 4 | 1.52 | – | -5.1 | – | 6.4 | – | 5.1 | -100.0 | -2.3 | no |
| Single zone per floor + Stacked floor zone multiplier | 4 | 1.52 | – | -5.1 | – | 7.3 | – | 5.1 | 350.6 | -0.7 | no |
| Conditioned merge + Stack | 8 | 0.00 | – | -4.7 | – | 5.0 | – | 4.7 | -100.0 | -1.8 | yes, recommended |
| Conditioned merge + Stacked floor zone multiplier | 8 | 0.00 | – | -4.7 | – | 5.9 | – | 4.7 | 343.1 | -0.2 | yes, recommended |
| Perimeter core 3 m + Stack | 20 | 1.52 | – | -3.1 | – | 4.5 | – | 3.1 | -74.4 | -2.2 | no |
| Perimeter core 3 m + Stacked floor zone multiplier | 20 | 1.52 | – | -3.1 | – | 5.2 | – | 3.1 | 365.6 | -0.8 | no |
| Perimeter core 4.57 m + Stack | 20 | 1.52 | – | -3.5 | – | 4.7 | – | 3.5 | -98.7 | -2.2 | no |
| Perimeter core 4.57 m + Stacked floor zone multiplier | 20 | 1.52 | – | -3.4 | – | 5.4 | – | 3.4 | 363.5 | -0.8 | no |
| Semantic merge + Stack | 43 | 0.00 | – | -0.1 | – | 1.1 | – | 0.1 | -25.2 | -1.2 | yes |
| Semantic merge + Stacked floor zone multiplier | 43 | 0.00 | – | 0.0 | – | 2.7 | – | -0.0 | 399.8 | 0.4 | yes |
| No simplification + Stacked floor zone multiplier | 67 | 0.00 | – | 0.1 | – | 2.2 | – | -0.1 | 400.9 | 1.4 | yes |
7 zonings write the same model as a listed one and are not shown
- No simplification + Single zone building → Conditioned merge + Single zone building
- No simplification + Single zone per floor type → Conditioned merge + Single zone per floor type
- Semantic merge + Single zone building → Conditioned merge + Single zone building
- Semantic merge + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Single zone building → Conditioned merge + Single zone building
- Single zone per floor + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Stack → Conditioned merge + Single zone per floor type
2B · 90.1-2019 · 0°
Reference 0e54059c7ae5b293/R: No simplification + Stack, 67 zones, 3,953 m² conditioned; annual sensible heating 0.1 and cooling 91.2 kWh/m²; peak heating 4.3 and cooling 102.4 kW. Sensible heating is below 1 kWh/m² and is not judged. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Single zone building | 1 | 1.52 | – | -6.5 | – | 18.5 | – | 6.5 | -100.0 | 10.2 | no |
| Perimeter core 3 m + Single zone building | 1 | 1.52 | – | -6.5 | – | 18.5 | – | 6.5 | -100.0 | 10.3 | no |
| Perimeter core 4.57 m + Single zone building | 1 | 1.52 | – | -6.4 | – | 18.5 | – | 6.4 | -100.0 | 10.3 | no |
| Conditioned merge + Single zone per floor type | 4 | 1.52 | – | -7.4 | – | 8.7 | – | 7.4 | -87.3 | -3.2 | no |
| Perimeter core 3 m + Single zone per floor type | 4 | 1.52 | – | -7.3 | – | 8.6 | – | 7.3 | -86.2 | -3.2 | no |
| Perimeter core 4.57 m + Single zone per floor type | 4 | 1.52 | – | -7.3 | – | 8.6 | – | 7.3 | -86.1 | -3.2 | no |
| Single zone per floor + Stacked floor zone multiplier | 4 | 1.52 | – | -6.9 | – | 9.3 | – | 6.9 | 81.4 | -1.1 | no |
| Conditioned merge + Stack | 8 | 0.00 | – | -6.9 | – | 7.2 | – | 6.9 | -94.4 | -2.6 | yes, recommended |
| Conditioned merge + Stacked floor zone multiplier | 8 | 0.00 | – | -6.4 | – | 7.8 | – | 6.4 | 80.8 | -0.6 | yes, recommended |
| Perimeter core 3 m + Stack | 20 | 1.52 | – | -4.0 | – | 5.6 | – | 4.0 | -22.8 | -2.9 | no |
| Perimeter core 3 m + Stacked floor zone multiplier | 20 | 1.52 | – | -3.6 | – | 6.7 | – | 3.6 | 86.6 | -1.3 | no |
| Perimeter core 4.57 m + Stack | 20 | 1.52 | – | -4.2 | – | 5.6 | – | 4.2 | -26.2 | -3.4 | no |
| Perimeter core 4.57 m + Stacked floor zone multiplier | 20 | 1.52 | – | -3.8 | – | 6.7 | – | 3.8 | 75.7 | -1.5 | no |
| Semantic merge + Stack | 43 | 0.00 | – | -0.2 | – | 1.2 | – | 0.2 | -4.2 | -1.3 | yes |
| Semantic merge + Stacked floor zone multiplier | 43 | 0.00 | – | 0.4 | – | 3.5 | – | -0.4 | 83.8 | 0.6 | yes |
| No simplification + Stacked floor zone multiplier | 67 | 0.00 | – | 0.6 | – | 3.0 | – | -0.6 | 86.1 | 1.8 | yes |
7 zonings write the same model as a listed one and are not shown
- No simplification + Single zone building → Conditioned merge + Single zone building
- No simplification + Single zone per floor type → Conditioned merge + Single zone per floor type
- Semantic merge + Single zone building → Conditioned merge + Single zone building
- Semantic merge + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Single zone building → Conditioned merge + Single zone building
- Single zone per floor + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Stack → Conditioned merge + Single zone per floor type
2B · 90.1-2019 · 45°
Reference 27b090bb6bfe3e29/R: No simplification + Stack, 67 zones, 3,953 m² conditioned; annual sensible heating 0.0 and cooling 87.0 kWh/m²; peak heating 2.6 and cooling 96.8 kW. Sensible heating is below 1 kWh/m² and is not judged. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Single zone building | 1 | 1.52 | – | -5.8 | – | 17.3 | – | 5.8 | -100.0 | 8.9 | no |
| Perimeter core 3 m + Single zone building | 1 | 1.52 | – | -5.8 | – | 17.3 | – | 5.8 | -100.0 | 9.0 | no |
| Perimeter core 4.57 m + Single zone building | 1 | 1.52 | – | -5.8 | – | 17.3 | – | 5.8 | -100.0 | 9.0 | no |
| Conditioned merge + Single zone per floor type | 4 | 1.52 | – | -6.8 | – | 8.2 | – | 6.8 | -100.0 | -3.1 | no |
| Perimeter core 3 m + Single zone per floor type | 4 | 1.52 | – | -6.7 | – | 8.1 | – | 6.7 | -100.0 | -3.1 | no |
| Perimeter core 4.57 m + Single zone per floor type | 4 | 1.52 | – | -6.7 | – | 8.1 | – | 6.7 | -100.0 | -3.1 | no |
| Single zone per floor + Stacked floor zone multiplier | 4 | 1.52 | – | -6.3 | – | 9.0 | – | 6.3 | 141.8 | -1.7 | no |
| Conditioned merge + Stack | 8 | 0.00 | – | -6.2 | – | 6.5 | – | 6.2 | -100.0 | -2.4 | yes, recommended |
| Conditioned merge + Stacked floor zone multiplier | 8 | 0.00 | – | -5.7 | – | 7.5 | – | 5.7 | 140.9 | -0.9 | yes, recommended |
| Perimeter core 3 m + Stack | 20 | 1.52 | – | -3.8 | – | 5.4 | – | 3.8 | -47.3 | -2.8 | no |
| Perimeter core 3 m + Stacked floor zone multiplier | 20 | 1.52 | – | -3.5 | – | 6.5 | – | 3.5 | 134.9 | -1.9 | no |
| Perimeter core 4.57 m + Stack | 20 | 1.52 | – | -4.0 | – | 5.5 | – | 4.0 | -50.1 | -3.2 | no |
| Perimeter core 4.57 m + Stacked floor zone multiplier | 20 | 1.52 | – | -3.7 | – | 6.6 | – | 3.7 | 133.5 | -2.1 | no |
| Semantic merge + Stack | 43 | 0.00 | – | -0.1 | – | 1.2 | – | 0.1 | -7.3 | -1.1 | yes |
| Semantic merge + Stacked floor zone multiplier | 43 | 0.00 | – | 0.4 | – | 3.7 | – | -0.4 | 156.8 | 0.2 | yes |
| No simplification + Stacked floor zone multiplier | 67 | 0.00 | – | 0.5 | – | 3.2 | – | -0.5 | 163.0 | 1.2 | yes |
7 zonings write the same model as a listed one and are not shown
- No simplification + Single zone building → Conditioned merge + Single zone building
- No simplification + Single zone per floor type → Conditioned merge + Single zone per floor type
- Semantic merge + Single zone building → Conditioned merge + Single zone building
- Semantic merge + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Single zone building → Conditioned merge + Single zone building
- Single zone per floor + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Stack → Conditioned merge + Single zone per floor type
3C · 90.1-2007 · 0°
Reference 63389c00d6c8432d/R: No simplification + Stack, 67 zones, 3,953 m² conditioned; annual sensible heating 0.0 and cooling 84.1 kWh/m²; peak heating 0.5 and cooling 94.1 kW. Sensible heating is below 1 kWh/m² and is not judged. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Single zone building | 1 | 1.52 | – | -8.2 | – | 19.2 | – | 8.2 | -100.0 | 10.1 | no |
| Perimeter core 3 m + Single zone building | 1 | 1.52 | – | -8.2 | – | 19.2 | – | 8.2 | -100.0 | 10.1 | no |
| Perimeter core 4.57 m + Single zone building | 1 | 1.52 | – | -8.2 | – | 19.2 | – | 8.2 | -100.0 | 10.1 | no |
| Conditioned merge + Single zone per floor type | 4 | 1.52 | – | -9.2 | – | 10.4 | – | 9.2 | -100.0 | -4.3 | no |
| Perimeter core 3 m + Single zone per floor type | 4 | 1.52 | – | -9.1 | – | 10.3 | – | 9.1 | -100.0 | -4.3 | no |
| Perimeter core 4.57 m + Single zone per floor type | 4 | 1.52 | – | -9.1 | – | 10.3 | – | 9.1 | -100.0 | -4.3 | no |
| Single zone per floor + Stacked floor zone multiplier | 4 | 1.52 | – | -8.7 | – | 10.8 | – | 8.7 | 449.7 | -2.3 | no |
| Conditioned merge + Stack | 8 | 0.00 | – | -8.4 | – | 8.7 | – | 8.4 | -100.0 | -3.3 | yes, recommended |
| Conditioned merge + Stacked floor zone multiplier | 8 | 0.00 | – | -8.0 | – | 9.2 | – | 8.0 | 434.4 | -1.2 | yes, recommended |
| Perimeter core 3 m + Stack | 20 | 1.52 | – | -3.8 | – | 5.9 | – | 3.8 | 49.9 | -3.8 | no |
| Perimeter core 3 m + Stacked floor zone multiplier | 20 | 1.52 | – | -3.4 | – | 6.9 | – | 3.4 | 629.7 | -2.2 | no |
| Perimeter core 4.57 m + Stack | 20 | 1.52 | – | -4.5 | – | 6.2 | – | 4.5 | -32.3 | -4.4 | no |
| Perimeter core 4.57 m + Stacked floor zone multiplier | 20 | 1.52 | – | -4.2 | – | 7.2 | – | 4.2 | 694.4 | -2.8 | no |
| Semantic merge + Stack | 43 | 0.00 | – | 0.1 | – | 1.5 | – | -0.1 | -27.5 | -1.2 | yes |
| Semantic merge + Stacked floor zone multiplier | 43 | 0.00 | – | 0.5 | – | 3.6 | – | -0.5 | 905.5 | 0.8 | yes |
| No simplification + Stacked floor zone multiplier | 67 | 0.00 | – | 0.6 | – | 3.0 | – | -0.6 | 904.7 | 2.0 | yes |
7 zonings write the same model as a listed one and are not shown
- No simplification + Single zone building → Conditioned merge + Single zone building
- No simplification + Single zone per floor type → Conditioned merge + Single zone per floor type
- Semantic merge + Single zone building → Conditioned merge + Single zone building
- Semantic merge + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Single zone building → Conditioned merge + Single zone building
- Single zone per floor + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Stack → Conditioned merge + Single zone per floor type
3C · 90.1-2007 · 45°
Reference 3b5bfcf9f942c4fe/R: No simplification + Stack, 67 zones, 3,953 m² conditioned; annual sensible heating 0.0 and cooling 86.4 kWh/m²; peak heating 0.3 and cooling 89.1 kW. Sensible heating is below 1 kWh/m² and is not judged. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Single zone building | 1 | 1.52 | – | -6.5 | – | 16.5 | – | 6.5 | -100.0 | 8.8 | no |
| Perimeter core 3 m + Single zone building | 1 | 1.52 | – | -6.5 | – | 16.5 | – | 6.5 | -100.0 | 8.8 | no |
| Perimeter core 4.57 m + Single zone building | 1 | 1.52 | – | -6.5 | – | 16.5 | – | 6.5 | -100.0 | 8.8 | no |
| Conditioned merge + Single zone per floor type | 4 | 1.52 | – | -7.6 | – | 8.9 | – | 7.6 | -100.0 | -4.5 | no |
| Perimeter core 3 m + Single zone per floor type | 4 | 1.52 | – | -7.5 | – | 8.9 | – | 7.5 | -100.0 | -4.4 | no |
| Perimeter core 4.57 m + Single zone per floor type | 4 | 1.52 | – | -7.5 | – | 8.8 | – | 7.5 | -100.0 | -4.4 | no |
| Single zone per floor + Stacked floor zone multiplier | 4 | 1.52 | – | -7.4 | – | 9.6 | – | 7.4 | -100.0 | -3.2 | no |
| Conditioned merge + Stack | 8 | 0.00 | – | -6.7 | – | 6.9 | – | 6.7 | -100.0 | -2.9 | yes, recommended |
| Conditioned merge + Stacked floor zone multiplier | 8 | 0.00 | – | -6.6 | – | 7.9 | – | 6.6 | -100.0 | -1.7 | yes, recommended |
| Perimeter core 3 m + Stack | 20 | 1.52 | – | -3.6 | – | 5.5 | – | 3.6 | -100.0 | -3.7 | no |
| Perimeter core 3 m + Stacked floor zone multiplier | 20 | 1.52 | – | -3.4 | – | 6.3 | – | 3.4 | 174.6 | -2.6 | no |
| Perimeter core 4.57 m + Stack | 20 | 1.52 | – | -4.0 | – | 5.8 | – | 4.0 | -100.0 | -4.4 | no |
| Perimeter core 4.57 m + Stacked floor zone multiplier | 20 | 1.52 | – | -3.9 | – | 6.6 | – | 3.9 | 200.7 | -3.2 | no |
| Semantic merge + Stack | 43 | 0.00 | – | 0.0 | – | 1.4 | – | -0.0 | -53.7 | -0.7 | yes |
| Semantic merge + Stacked floor zone multiplier | 43 | 0.00 | – | 0.3 | – | 3.4 | – | -0.3 | 761.4 | -0.1 | yes |
| No simplification + Stacked floor zone multiplier | 67 | 0.00 | – | 0.4 | – | 2.8 | – | -0.4 | 723.5 | 1.0 | yes |
7 zonings write the same model as a listed one and are not shown
- No simplification + Single zone building → Conditioned merge + Single zone building
- No simplification + Single zone per floor type → Conditioned merge + Single zone per floor type
- Semantic merge + Single zone building → Conditioned merge + Single zone building
- Semantic merge + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Single zone building → Conditioned merge + Single zone building
- Single zone per floor + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Stack → Conditioned merge + Single zone per floor type
3C · 90.1-2019 · 0°
Reference 466c2fd553818a4f/R: No simplification + Stack, 67 zones, 3,953 m² conditioned; annual sensible heating 0.0 and cooling 68.4 kWh/m²; peak heating 1.3 and cooling 83.8 kW. Sensible heating is below 1 kWh/m² and is not judged. Serial cost (R5): processor time 26.2 s, wall clock 26.5 s, peak committed memory 233 MiB, each the median of 3 repeats (processor-time CV 0.4 %); a zoning's ratios are its own medians over the reference's.
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | CPU ratio | Wall ratio | Memory ratio | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Single zone building | 1 | 1.52 | – | -10.3 | – | 21.9 | – | 10.3 | -100.0 | 12.1 | 0.064 | 0.064 | 0.805 | no |
| Perimeter core 3 m + Single zone building | 1 | 1.52 | – | -10.2 | – | 21.9 | – | 10.2 | -100.0 | 12.2 | 0.064 | 0.064 | 0.803 | no |
| Perimeter core 4.57 m + Single zone building | 1 | 1.52 | – | -10.2 | – | 21.9 | – | 10.2 | -100.0 | 12.2 | 0.064 | 0.064 | 0.804 | no |
| Conditioned merge + Single zone per floor type | 4 | 1.52 | – | -11.1 | – | 12.5 | – | 11.1 | -100.0 | -4.8 | 0.082 | 0.087 | 0.812 | no |
| Perimeter core 3 m + Single zone per floor type | 4 | 1.52 | – | -11.1 | – | 12.4 | – | 11.1 | -100.0 | -4.8 | 0.082 | 0.082 | 0.808 | no |
| Perimeter core 4.57 m + Single zone per floor type | 4 | 1.52 | – | -11.1 | – | 12.4 | – | 11.1 | -100.0 | -4.8 | 0.082 | 0.087 | 0.811 | no |
| Single zone per floor + Stacked floor zone multiplier | 4 | 1.52 | – | -9.8 | – | 12.5 | – | 9.8 | 271.9 | -2.9 | 0.081 | 0.084 | 0.811 | no |
| Conditioned merge + Stack | 8 | 0.00 | – | -10.3 | – | 10.6 | – | 10.3 | -100.0 | -3.2 | 0.142 | 0.141 | 0.822 | no |
| Conditioned merge + Stacked floor zone multiplier | 8 | 0.00 | – | -9.1 | – | 10.8 | – | 9.1 | 269.5 | -1.1 | 0.141 | 0.142 | 0.826 | yes, recommended |
| Perimeter core 3 m + Stack | 20 | 1.52 | – | -4.6 | – | 6.8 | – | 4.6 | -26.5 | -4.4 | 0.242 | 0.243 | 0.851 | no |
| Perimeter core 3 m + Stacked floor zone multiplier | 20 | 1.52 | – | -3.6 | – | 8.0 | – | 3.6 | 263.6 | -3.3 | 0.237 | 0.241 | 0.852 | no |
| Perimeter core 4.57 m + Stack | 20 | 1.52 | – | -5.1 | – | 7.0 | – | 5.1 | -47.7 | -4.8 | 0.236 | 0.238 | 0.846 | no |
| Perimeter core 4.57 m + Stacked floor zone multiplier | 20 | 1.52 | – | -4.3 | – | 8.3 | – | 4.3 | 264.0 | -3.6 | 0.235 | 0.239 | 0.846 | no |
| Semantic merge + Stack | 43 | 0.00 | – | 0.0 | – | 1.4 | – | -0.0 | 0.9 | -1.2 | 0.614 | 0.612 | 0.930 | yes |
| Semantic merge + Stacked floor zone multiplier | 43 | 0.00 | – | 1.0 | – | 4.6 | – | -1.0 | 279.1 | 0.5 | 0.607 | 0.611 | 0.926 | yes |
| No simplification + Stacked floor zone multiplier | 67 | 0.00 | – | 1.0 | – | 4.2 | – | -1.0 | 280.3 | 1.7 | 0.989 | 0.985 | 0.996 | yes |
7 zonings write the same model as a listed one and are not shown
- No simplification + Single zone building → Conditioned merge + Single zone building
- No simplification + Single zone per floor type → Conditioned merge + Single zone per floor type
- Semantic merge + Single zone building → Conditioned merge + Single zone building
- Semantic merge + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Single zone building → Conditioned merge + Single zone building
- Single zone per floor + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Stack → Conditioned merge + Single zone per floor type
3C · 90.1-2019 · 45°
Reference ab74c3543b279510/R: No simplification + Stack, 67 zones, 3,953 m² conditioned; annual sensible heating 0.0 and cooling 67.6 kWh/m²; peak heating 0.8 and cooling 78.2 kW. Sensible heating is below 1 kWh/m² and is not judged. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Single zone building | 1 | 1.52 | – | -9.2 | – | 19.8 | – | 9.2 | -100.0 | 11.4 | no |
| Perimeter core 3 m + Single zone building | 1 | 1.52 | – | -9.2 | – | 19.8 | – | 9.2 | -100.0 | 11.5 | no |
| Perimeter core 4.57 m + Single zone building | 1 | 1.52 | – | -9.2 | – | 19.8 | – | 9.2 | -100.0 | 11.5 | no |
| Conditioned merge + Single zone per floor type | 4 | 1.52 | – | -10.2 | – | 11.6 | – | 10.2 | -100.0 | -4.9 | no |
| Perimeter core 3 m + Single zone per floor type | 4 | 1.52 | – | -10.1 | – | 11.5 | – | 10.1 | -100.0 | -4.9 | no |
| Perimeter core 4.57 m + Single zone per floor type | 4 | 1.52 | – | -10.1 | – | 11.5 | – | 10.1 | -100.0 | -4.9 | no |
| Single zone per floor + Stacked floor zone multiplier | 4 | 1.52 | – | -8.8 | – | 11.8 | – | 8.8 | 421.4 | -3.2 | no |
| Conditioned merge + Stack | 8 | 0.00 | – | -9.3 | – | 9.5 | – | 9.3 | -100.0 | -2.8 | yes, recommended |
| Conditioned merge + Stacked floor zone multiplier | 8 | 0.00 | – | -8.2 | – | 10.3 | – | 8.2 | 416.5 | -1.6 | yes, recommended |
| Perimeter core 3 m + Stack | 20 | 1.52 | – | -4.5 | – | 6.7 | – | 4.5 | -100.0 | -3.4 | no |
| Perimeter core 3 m + Stacked floor zone multiplier | 20 | 1.52 | – | -3.7 | – | 7.8 | – | 3.7 | 414.5 | -3.1 | no |
| Perimeter core 4.57 m + Stack | 20 | 1.52 | – | -4.9 | – | 6.9 | – | 4.9 | -100.0 | -3.9 | no |
| Perimeter core 4.57 m + Stacked floor zone multiplier | 20 | 1.52 | – | -4.2 | – | 8.1 | – | 4.2 | 411.2 | -3.8 | no |
| Semantic merge + Stack | 43 | 0.00 | – | 0.0 | – | 1.3 | – | -0.0 | -29.4 | -1.1 | yes |
| Semantic merge + Stacked floor zone multiplier | 43 | 0.00 | – | 0.8 | – | 4.9 | – | -0.8 | 422.1 | -0.1 | yes |
| No simplification + Stacked floor zone multiplier | 67 | 0.00 | – | 0.9 | – | 4.6 | – | -0.9 | 414.7 | 1.0 | yes |
7 zonings write the same model as a listed one and are not shown
- No simplification + Single zone building → Conditioned merge + Single zone building
- No simplification + Single zone per floor type → Conditioned merge + Single zone per floor type
- Semantic merge + Single zone building → Conditioned merge + Single zone building
- Semantic merge + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Single zone building → Conditioned merge + Single zone building
- Single zone per floor + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Stack → Conditioned merge + Single zone per floor type
4A · 90.1-2007 · 0°
Reference f419c04db47455c4/R: No simplification + Stack, 67 zones, 3,953 m² conditioned; annual sensible heating 1.3 and cooling 82.1 kWh/m²; peak heating 17.4 and cooling 107.8 kW. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Single zone building | 1 | 1.52 | -99.6 | -11.1 | 309.3 | 23.0 | 99.6 | 11.1 | -66.0 | 7.8 | no |
| Perimeter core 3 m + Single zone building | 1 | 1.52 | -99.6 | -11.0 | 309.1 | 22.9 | 99.6 | 11.0 | -64.7 | 7.8 | no |
| Perimeter core 4.57 m + Single zone building | 1 | 1.52 | -99.6 | -11.0 | 309.1 | 22.9 | 99.6 | 11.0 | -64.6 | 7.8 | no |
| Conditioned merge + Single zone per floor type | 4 | 1.52 | -63.3 | -9.8 | 161.8 | 11.1 | 63.3 | 9.8 | -19.1 | -4.0 | no |
| Perimeter core 3 m + Single zone per floor type | 4 | 1.52 | -63.0 | -9.7 | 160.9 | 11.0 | 63.0 | 9.7 | -18.9 | -4.0 | no |
| Perimeter core 4.57 m + Single zone per floor type | 4 | 1.52 | -63.0 | -9.7 | 160.8 | 11.0 | 63.0 | 9.7 | -18.9 | -4.0 | no |
| Single zone per floor + Stacked floor zone multiplier | 4 | 1.52 | 65.0 | -6.6 | 182.9 | 9.8 | -65.0 | 6.6 | 34.7 | -2.2 | no |
| Conditioned merge + Stack | 8 | 0.00 | -65.3 | -9.6 | 167.8 | 10.2 | 65.3 | 9.6 | -21.8 | -3.2 | no |
| Conditioned merge + Stacked floor zone multiplier | 8 | 0.00 | 68.4 | -6.4 | 190.0 | 8.7 | -68.4 | 6.4 | 34.0 | -1.5 | no |
| Perimeter core 3 m + Stack | 20 | 1.52 | -15.0 | -3.4 | 51.3 | 6.1 | 15.0 | 3.4 | -2.6 | -3.1 | no |
| Perimeter core 3 m + Stacked floor zone multiplier | 20 | 1.52 | 98.2 | -1.2 | 223.1 | 7.3 | -98.2 | 1.2 | 26.2 | -1.5 | no |
| Perimeter core 4.57 m + Stack | 20 | 1.52 | -23.0 | -4.2 | 56.3 | 6.2 | 23.0 | 4.2 | -5.0 | -3.5 | no |
| Perimeter core 4.57 m + Stacked floor zone multiplier | 20 | 1.52 | 93.0 | -2.0 | 211.8 | 7.1 | -93.0 | 2.0 | 26.2 | -1.7 | no |
| Semantic merge + Stack | 43 | 0.00 | -5.6 | -0.3 | 17.5 | 1.3 | 5.6 | 0.3 | -2.9 | -0.8 | yes, recommended |
| Semantic merge + Stacked floor zone multiplier | 43 | 0.00 | 118.7 | 2.1 | 242.4 | 5.0 | -118.7 | -2.1 | 34.7 | 0.5 | no |
| No simplification + Stacked floor zone multiplier | 67 | 0.00 | 120.3 | 2.3 | 246.3 | 4.8 | -120.3 | -2.3 | 35.9 | 1.6 | no |
7 zonings write the same model as a listed one and are not shown
- No simplification + Single zone building → Conditioned merge + Single zone building
- No simplification + Single zone per floor type → Conditioned merge + Single zone per floor type
- Semantic merge + Single zone building → Conditioned merge + Single zone building
- Semantic merge + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Single zone building → Conditioned merge + Single zone building
- Single zone per floor + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Stack → Conditioned merge + Single zone per floor type
4A · 90.1-2007 · 45°
Reference 7ac716dc6398bd86/R: No simplification + Stack, 67 zones, 3,953 m² conditioned; annual sensible heating 0.8 and cooling 80.4 kWh/m²; peak heating 11.2 and cooling 101.8 kW. Sensible heating is below 1 kWh/m² and is not judged. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Single zone building | 1 | 1.52 | -100.0 | -9.6 | 324.2 | 20.1 | 100.0 | 9.6 | -100.0 | 4.9 | no |
| Perimeter core 3 m + Single zone building | 1 | 1.52 | -100.0 | -9.5 | 324.2 | 20.1 | 100.0 | 9.5 | -100.0 | 4.9 | no |
| Perimeter core 4.57 m + Single zone building | 1 | 1.52 | -100.0 | -9.5 | 324.2 | 20.1 | 100.0 | 9.5 | -100.0 | 4.9 | no |
| Conditioned merge + Single zone per floor type | 4 | 1.52 | -76.4 | -9.0 | 204.5 | 10.2 | 76.4 | 9.0 | -27.9 | -5.5 | no |
| Perimeter core 3 m + Single zone per floor type | 4 | 1.52 | -76.1 | -8.9 | 203.6 | 10.2 | 76.1 | 8.9 | -27.8 | -5.5 | no |
| Perimeter core 4.57 m + Single zone per floor type | 4 | 1.52 | -76.1 | -8.9 | 203.5 | 10.2 | 76.1 | 8.9 | -27.8 | -5.5 | no |
| Single zone per floor + Stacked floor zone multiplier | 4 | 1.52 | 106.0 | -6.0 | 294.3 | 9.0 | -106.0 | 6.0 | 17.7 | -4.8 | no |
| Conditioned merge + Stack | 8 | 0.00 | -78.3 | -8.7 | 211.7 | 9.1 | 78.3 | 8.7 | -30.2 | -2.8 | yes, recommended |
| Conditioned merge + Stacked floor zone multiplier | 8 | 0.00 | 111.9 | -5.6 | 310.0 | 7.7 | -111.9 | 5.6 | 24.1 | -3.9 | yes, recommended |
| Perimeter core 3 m + Stack | 20 | 1.52 | -47.2 | -3.8 | 109.5 | 5.7 | 47.2 | 3.8 | -10.0 | -5.2 | no |
| Perimeter core 3 m + Stacked floor zone multiplier | 20 | 1.52 | 120.0 | -1.6 | 308.5 | 6.5 | -120.0 | 1.6 | 33.1 | -4.1 | no |
| Perimeter core 4.57 m + Stack | 20 | 1.52 | -49.3 | -4.4 | 114.3 | 6.0 | 49.3 | 4.4 | -11.1 | -5.7 | no |
| Perimeter core 4.57 m + Stacked floor zone multiplier | 20 | 1.52 | 119.6 | -2.2 | 307.0 | 6.6 | -119.6 | 2.2 | 34.0 | -4.5 | no |
| Semantic merge + Stack | 43 | 0.00 | -13.4 | -0.2 | 35.1 | 1.4 | 13.4 | 0.2 | -5.3 | -0.7 | yes |
| Semantic merge + Stacked floor zone multiplier | 43 | 0.00 | 161.4 | 2.0 | 346.7 | 4.8 | -161.4 | -2.0 | 31.0 | -0.9 | yes |
| No simplification + Stacked floor zone multiplier | 67 | 0.00 | 169.9 | 2.1 | 362.3 | 4.6 | -169.9 | -2.1 | 33.6 | -1.1 | yes |
7 zonings write the same model as a listed one and are not shown
- No simplification + Single zone building → Conditioned merge + Single zone building
- No simplification + Single zone per floor type → Conditioned merge + Single zone per floor type
- Semantic merge + Single zone building → Conditioned merge + Single zone building
- Semantic merge + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Single zone building → Conditioned merge + Single zone building
- Single zone per floor + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Stack → Conditioned merge + Single zone per floor type
4A · 90.1-2019 · 0°
Reference 315093166ad91f02/R: No simplification + Stack, 67 zones, 3,953 m² conditioned; annual sensible heating 1.8 and cooling 68.3 kWh/m²; peak heating 18.8 and cooling 96.2 kW. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Single zone building | 1 | 1.52 | -99.6 | -13.3 | 264.8 | 27.5 | 99.6 | 13.3 | -70.7 | 8.8 | no |
| Perimeter core 3 m + Single zone building | 1 | 1.52 | -99.6 | -13.3 | 264.6 | 27.5 | 99.6 | 13.3 | -69.7 | 8.8 | no |
| Perimeter core 4.57 m + Single zone building | 1 | 1.52 | -99.6 | -13.3 | 264.6 | 27.5 | 99.6 | 13.3 | -69.6 | 8.8 | no |
| Conditioned merge + Single zone per floor type | 4 | 1.52 | -62.5 | -10.7 | 134.8 | 12.3 | 62.5 | 10.7 | -26.1 | -4.3 | no |
| Perimeter core 3 m + Single zone per floor type | 4 | 1.52 | -62.3 | -10.7 | 134.1 | 12.2 | 62.3 | 10.7 | -25.9 | -4.2 | no |
| Perimeter core 4.57 m + Single zone per floor type | 4 | 1.52 | -62.3 | -10.7 | 134.1 | 12.2 | 62.3 | 10.7 | -25.9 | -4.2 | no |
| Single zone per floor + Stacked floor zone multiplier | 4 | 1.52 | 48.7 | -5.7 | 143.4 | 11.1 | -48.7 | 5.7 | 31.7 | -2.6 | no |
| Conditioned merge + Stack | 8 | 0.00 | -64.7 | -10.7 | 140.4 | 11.4 | 64.7 | 10.7 | -27.6 | -3.3 | no |
| Conditioned merge + Stacked floor zone multiplier | 8 | 0.00 | 52.8 | -5.4 | 152.0 | 9.6 | -52.8 | 5.4 | 45.6 | -1.5 | no |
| Perimeter core 3 m + Stack | 20 | 1.52 | -29.5 | -4.6 | 62.0 | 6.8 | 29.5 | 4.6 | -13.0 | -3.3 | no |
| Perimeter core 3 m + Stacked floor zone multiplier | 20 | 1.52 | 70.7 | -1.1 | 162.4 | 8.6 | -70.7 | 1.1 | 45.1 | -2.1 | no |
| Perimeter core 4.57 m + Stack | 20 | 1.52 | -31.5 | -4.9 | 63.5 | 6.8 | 31.5 | 4.9 | -12.7 | -3.8 | no |
| Perimeter core 4.57 m + Stacked floor zone multiplier | 20 | 1.52 | 69.5 | -1.4 | 159.7 | 8.4 | -69.5 | 1.4 | 44.4 | -2.4 | no |
| Semantic merge + Stack | 43 | 0.00 | -6.8 | -0.3 | 17.9 | 1.6 | 6.8 | 0.3 | -3.2 | -1.2 | yes, recommended |
| Semantic merge + Stacked floor zone multiplier | 43 | 0.00 | 98.5 | 3.2 | 190.0 | 6.7 | -98.5 | -3.2 | 44.8 | 0.6 | no |
| No simplification + Stacked floor zone multiplier | 67 | 0.00 | 101.1 | 3.3 | 195.7 | 6.5 | -101.1 | -3.3 | 47.8 | 1.7 | no |
7 zonings write the same model as a listed one and are not shown
- No simplification + Single zone building → Conditioned merge + Single zone building
- No simplification + Single zone per floor type → Conditioned merge + Single zone per floor type
- Semantic merge + Single zone building → Conditioned merge + Single zone building
- Semantic merge + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Single zone building → Conditioned merge + Single zone building
- Single zone per floor + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Stack → Conditioned merge + Single zone per floor type
4A · 90.1-2019 · 45°
Reference 2d90d6faeb72a52d/R: No simplification + Stack, 67 zones, 3,953 m² conditioned; annual sensible heating 1.5 and cooling 64.8 kWh/m²; peak heating 15.8 and cooling 90.0 kW. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Single zone building | 1 | 1.52 | -100.0 | -13.1 | 265.0 | 26.5 | 100.0 | 13.1 | -100.0 | 7.0 | no |
| Perimeter core 3 m + Single zone building | 1 | 1.52 | -100.0 | -13.0 | 265.0 | 26.5 | 100.0 | 13.0 | -100.0 | 7.1 | no |
| Perimeter core 4.57 m + Single zone building | 1 | 1.52 | -100.0 | -13.0 | 265.0 | 26.5 | 100.0 | 13.0 | -100.0 | 7.1 | no |
| Conditioned merge + Single zone per floor type | 4 | 1.52 | -67.1 | -10.5 | 143.3 | 12.0 | 67.1 | 10.5 | -31.1 | -5.7 | no |
| Perimeter core 3 m + Single zone per floor type | 4 | 1.52 | -66.8 | -10.4 | 142.5 | 11.9 | 66.8 | 10.4 | -31.0 | -5.6 | no |
| Perimeter core 4.57 m + Single zone per floor type | 4 | 1.52 | -66.8 | -10.4 | 142.5 | 11.9 | 66.8 | 10.4 | -30.9 | -5.6 | no |
| Single zone per floor + Stacked floor zone multiplier | 4 | 1.52 | 62.6 | -5.0 | 165.0 | 10.9 | -62.6 | 5.0 | 32.7 | -4.9 | no |
| Conditioned merge + Stack | 8 | 0.00 | -69.4 | -10.3 | 149.3 | 10.9 | 69.4 | 10.3 | -31.3 | -4.3 | no |
| Conditioned merge + Stacked floor zone multiplier | 8 | 0.00 | 68.4 | -4.7 | 178.4 | 9.3 | -68.4 | 4.7 | 48.6 | -3.2 | no |
| Perimeter core 3 m + Stack | 20 | 1.52 | -41.6 | -4.6 | 81.4 | 6.9 | 41.6 | 4.6 | -22.1 | -4.6 | no |
| Perimeter core 3 m + Stacked floor zone multiplier | 20 | 1.52 | 73.4 | -0.9 | 176.1 | 8.3 | -73.4 | 0.9 | 53.0 | -3.7 | no |
| Perimeter core 4.57 m + Stack | 20 | 1.52 | -41.5 | -4.9 | 80.4 | 6.9 | 41.5 | 4.9 | -20.8 | -5.1 | no |
| Perimeter core 4.57 m + Stacked floor zone multiplier | 20 | 1.52 | 73.4 | -1.3 | 176.9 | 8.4 | -73.4 | 1.3 | 53.5 | -4.3 | no |
| Semantic merge + Stack | 43 | 0.00 | -8.6 | -0.2 | 21.4 | 1.6 | 8.6 | 0.2 | -6.4 | -0.6 | yes, recommended |
| Semantic merge + Stacked floor zone multiplier | 43 | 0.00 | 107.9 | 3.3 | 205.7 | 7.1 | -107.9 | -3.3 | 42.8 | -1.3 | no |
| No simplification + Stacked floor zone multiplier | 67 | 0.00 | 112.5 | 3.3 | 213.8 | 6.8 | -112.5 | -3.3 | 40.9 | -0.4 | no |
7 zonings write the same model as a listed one and are not shown
- No simplification + Single zone building → Conditioned merge + Single zone building
- No simplification + Single zone per floor type → Conditioned merge + Single zone per floor type
- Semantic merge + Single zone building → Conditioned merge + Single zone building
- Semantic merge + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Single zone building → Conditioned merge + Single zone building
- Single zone per floor + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Stack → Conditioned merge + Single zone per floor type
5A · 90.1-2007 · 0°
Reference 6b0f21a3bf505d35/R: No simplification + Stack, 67 zones, 3,953 m² conditioned; annual sensible heating 4.1 and cooling 69.8 kWh/m²; peak heating 30.9 and cooling 104.9 kW. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Single zone building | 1 | 1.52 | -93.8 | -17.2 | 220.1 | 34.6 | 93.8 | 17.2 | 5.0 | 8.9 | no |
| Perimeter core 3 m + Single zone building | 1 | 1.52 | -93.7 | -17.1 | 219.7 | 34.6 | 93.7 | 17.1 | 5.2 | 8.9 | no |
| Perimeter core 4.57 m + Single zone building | 1 | 1.52 | -93.6 | -17.1 | 219.7 | 34.6 | 93.6 | 17.1 | 5.2 | 8.9 | no |
| Conditioned merge + Single zone per floor type | 4 | 1.52 | -40.5 | -11.9 | 80.6 | 13.6 | 40.5 | 11.9 | -20.5 | -4.1 | no |
| Perimeter core 3 m + Single zone per floor type | 4 | 1.52 | -40.2 | -11.8 | 80.1 | 13.5 | 40.2 | 11.8 | -20.4 | -4.1 | no |
| Perimeter core 4.57 m + Single zone per floor type | 4 | 1.52 | -40.2 | -11.8 | 80.1 | 13.5 | 40.2 | 11.8 | -20.4 | -4.1 | no |
| Single zone per floor + Stacked floor zone multiplier | 4 | 1.52 | 29.5 | -6.3 | 69.3 | 11.3 | -29.5 | 6.3 | 3.6 | -1.9 | no |
| Conditioned merge + Stack | 8 | 0.00 | -41.6 | -11.9 | 82.1 | 13.0 | 41.6 | 11.9 | -22.4 | -3.4 | no |
| Conditioned merge + Stacked floor zone multiplier | 8 | 0.00 | 32.2 | -6.2 | 73.5 | 9.8 | -32.2 | 6.2 | 3.5 | -1.3 | no |
| Perimeter core 3 m + Stack | 20 | 1.52 | -13.2 | -3.4 | 33.7 | 7.1 | 13.2 | 3.4 | -7.6 | -3.0 | no |
| Perimeter core 3 m + Stacked floor zone multiplier | 20 | 1.52 | 41.9 | 0.3 | 81.6 | 9.0 | -41.9 | -0.3 | 5.5 | -1.3 | no |
| Perimeter core 4.57 m + Stack | 20 | 1.52 | -16.6 | -4.4 | 35.3 | 7.1 | 16.6 | 4.4 | -8.5 | -3.7 | no |
| Perimeter core 4.57 m + Stacked floor zone multiplier | 20 | 1.52 | 39.7 | -0.7 | 77.6 | 8.7 | -39.7 | 0.7 | 4.6 | -1.7 | no |
| Semantic merge + Stack | 43 | 0.00 | -4.1 | -0.5 | 10.4 | 1.5 | 4.1 | 0.5 | -0.8 | -1.2 | yes, recommended |
| Semantic merge + Stacked floor zone multiplier | 43 | 0.00 | 55.0 | 3.6 | 96.7 | 6.8 | -55.0 | -3.6 | 8.5 | 0.8 | no |
| No simplification + Stacked floor zone multiplier | 67 | 0.00 | 56.0 | 3.8 | 98.6 | 6.6 | -56.0 | -3.8 | 9.1 | 2.0 | no |
7 zonings write the same model as a listed one and are not shown
- No simplification + Single zone building → Conditioned merge + Single zone building
- No simplification + Single zone per floor type → Conditioned merge + Single zone per floor type
- Semantic merge + Single zone building → Conditioned merge + Single zone building
- Semantic merge + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Single zone building → Conditioned merge + Single zone building
- Single zone per floor + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Stack → Conditioned merge + Single zone per floor type
5A · 90.1-2007 · 45°
Reference 975994b236e074a3/R: No simplification + Stack, 67 zones, 3,953 m² conditioned; annual sensible heating 2.6 and cooling 70.1 kWh/m²; peak heating 20.6 and cooling 97.1 kW. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Single zone building | 1 | 1.52 | -99.7 | -14.6 | 245.9 | 29.2 | 99.7 | 14.6 | -46.4 | 7.6 | no |
| Perimeter core 3 m + Single zone building | 1 | 1.52 | -99.7 | -14.6 | 245.8 | 29.1 | 99.7 | 14.6 | -45.5 | 7.6 | no |
| Perimeter core 4.57 m + Single zone building | 1 | 1.52 | -99.7 | -14.6 | 245.8 | 29.1 | 99.7 | 14.6 | -45.4 | 7.6 | no |
| Conditioned merge + Single zone per floor type | 4 | 1.52 | -51.4 | -11.0 | 103.8 | 12.4 | 51.4 | 11.0 | -27.7 | -4.6 | no |
| Perimeter core 3 m + Single zone per floor type | 4 | 1.52 | -51.2 | -10.9 | 103.2 | 12.4 | 51.2 | 10.9 | -27.6 | -4.6 | no |
| Perimeter core 4.57 m + Single zone per floor type | 4 | 1.52 | -51.1 | -10.9 | 103.2 | 12.4 | 51.1 | 10.9 | -27.5 | -4.6 | no |
| Single zone per floor + Stacked floor zone multiplier | 4 | 1.52 | 43.3 | -6.0 | 99.0 | 10.4 | -43.3 | 6.0 | 33.1 | -3.0 | no |
| Conditioned merge + Stack | 8 | 0.00 | -53.2 | -10.9 | 107.3 | 11.6 | 53.2 | 10.9 | -26.8 | -3.4 | no |
| Conditioned merge + Stacked floor zone multiplier | 8 | 0.00 | 46.4 | -5.8 | 104.9 | 8.8 | -46.4 | 5.8 | 29.1 | -1.9 | no |
| Perimeter core 3 m + Stack | 20 | 1.52 | -29.7 | -4.1 | 56.5 | 6.5 | 29.7 | 4.1 | -15.4 | -3.9 | no |
| Perimeter core 3 m + Stacked floor zone multiplier | 20 | 1.52 | 52.2 | -0.6 | 108.2 | 7.7 | -52.2 | 0.6 | 9.7 | -2.5 | no |
| Perimeter core 4.57 m + Stack | 20 | 1.52 | -30.5 | -4.8 | 58.1 | 6.8 | 30.5 | 4.8 | -17.9 | -4.6 | no |
| Perimeter core 4.57 m + Stacked floor zone multiplier | 20 | 1.52 | 51.0 | -1.4 | 106.3 | 7.6 | -51.0 | 1.4 | 16.5 | -3.1 | no |
| Semantic merge + Stack | 43 | 0.00 | -7.8 | -0.5 | 17.8 | 1.5 | 7.8 | 0.5 | -4.0 | -0.7 | yes, recommended |
| Semantic merge + Stacked floor zone multiplier | 43 | 0.00 | 73.1 | 3.1 | 131.4 | 6.1 | -73.1 | -3.1 | 26.3 | -0.2 | no |
| No simplification + Stacked floor zone multiplier | 67 | 0.00 | 78.0 | 3.4 | 139.4 | 6.0 | -78.0 | -3.4 | 25.1 | 0.9 | no |
7 zonings write the same model as a listed one and are not shown
- No simplification + Single zone building → Conditioned merge + Single zone building
- No simplification + Single zone per floor type → Conditioned merge + Single zone per floor type
- Semantic merge + Single zone building → Conditioned merge + Single zone building
- Semantic merge + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Single zone building → Conditioned merge + Single zone building
- Single zone per floor + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Stack → Conditioned merge + Single zone per floor type
5A · 90.1-2019 · 0°
Reference 12c9977c5b55ab04/R: No simplification + Stack, 67 zones, 3,953 m² conditioned; annual sensible heating 4.5 and cooling 59.8 kWh/m²; peak heating 27.3 and cooling 93.7 kW. Serial cost (R5): processor time 26.8 s, wall clock 27.2 s, peak committed memory 233 MiB, each the median of 3 repeats (processor-time CV 0.5 %); a zoning's ratios are its own medians over the reference's.
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | CPU ratio | Wall ratio | Memory ratio | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Single zone building | 1 | 1.52 | -96.3 | -19.5 | 213.7 | 39.7 | 96.3 | 19.5 | -4.7 | 9.7 | 0.064 | 0.064 | 0.807 | no |
| Perimeter core 3 m + Single zone building | 1 | 1.52 | -96.3 | -19.4 | 213.5 | 39.7 | 96.3 | 19.4 | -4.5 | 9.7 | 0.064 | 0.063 | 0.803 | no |
| Perimeter core 4.57 m + Single zone building | 1 | 1.52 | -96.3 | -19.4 | 213.5 | 39.7 | 96.3 | 19.4 | -4.5 | 9.7 | 0.062 | 0.063 | 0.804 | no |
| Conditioned merge + Single zone per floor type | 4 | 1.52 | -44.0 | -12.7 | 82.9 | 14.9 | 44.0 | 12.7 | -22.0 | -4.4 | 0.081 | 0.080 | 0.809 | no |
| Perimeter core 3 m + Single zone per floor type | 4 | 1.52 | -43.8 | -12.6 | 82.4 | 14.8 | 43.8 | 12.6 | -21.8 | -4.3 | 0.080 | 0.081 | 0.811 | no |
| Perimeter core 4.57 m + Single zone per floor type | 4 | 1.52 | -43.8 | -12.6 | 82.4 | 14.8 | 43.8 | 12.6 | -21.8 | -4.3 | 0.080 | 0.082 | 0.812 | no |
| Single zone per floor + Stacked floor zone multiplier | 4 | 1.52 | 32.1 | -5.1 | 77.7 | 12.6 | -32.1 | 5.1 | 7.9 | -2.6 | 0.078 | 0.082 | 0.808 | no |
| Conditioned merge + Stack | 8 | 0.00 | -45.0 | -12.7 | 83.8 | 14.2 | 45.0 | 12.7 | -23.9 | -3.4 | 0.139 | 0.144 | 0.824 | no |
| Conditioned merge + Stacked floor zone multiplier | 8 | 0.00 | 36.2 | -4.9 | 84.9 | 10.9 | -36.2 | 4.9 | 7.9 | -1.4 | 0.141 | 0.141 | 0.826 | no |
| Perimeter core 3 m + Stack | 20 | 1.52 | -23.8 | -5.3 | 45.7 | 7.9 | 23.8 | 5.3 | -12.7 | -3.2 | 0.235 | 0.234 | 0.846 | no |
| Perimeter core 3 m + Stacked floor zone multiplier | 20 | 1.52 | 40.6 | 0.3 | 82.2 | 10.2 | -40.6 | -0.3 | 5.8 | -1.8 | 0.253 | 0.253 | 0.851 | no |
| Perimeter core 4.57 m + Stack | 20 | 1.52 | -23.6 | -5.5 | 44.2 | 7.8 | 23.6 | 5.5 | -11.7 | -3.8 | 0.233 | 0.242 | 0.851 | no |
| Perimeter core 4.57 m + Stacked floor zone multiplier | 20 | 1.52 | 40.5 | -0.1 | 82.4 | 10.1 | -40.5 | 0.1 | 5.4 | -2.4 | 0.236 | 0.241 | 0.845 | no |
| Semantic merge + Stack | 43 | 0.00 | -4.4 | -0.5 | 10.2 | 1.5 | 4.4 | 0.5 | -0.6 | -1.2 | 0.613 | 0.612 | 0.930 | yes, recommended |
| Semantic merge + Stacked floor zone multiplier | 43 | 0.00 | 57.0 | 4.7 | 98.1 | 8.6 | -57.0 | -4.7 | 16.6 | 0.7 | 0.600 | 0.600 | 0.926 | no |
| No simplification + Stacked floor zone multiplier | 67 | 0.00 | 57.6 | 4.9 | 99.4 | 8.4 | -57.6 | -4.9 | 13.1 | 1.8 | 0.978 | 0.978 | 0.996 | no |
7 zonings write the same model as a listed one and are not shown
- No simplification + Single zone building → Conditioned merge + Single zone building
- No simplification + Single zone per floor type → Conditioned merge + Single zone per floor type
- Semantic merge + Single zone building → Conditioned merge + Single zone building
- Semantic merge + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Single zone building → Conditioned merge + Single zone building
- Single zone per floor + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Stack → Conditioned merge + Single zone per floor type
5A · 90.1-2019 · 45°
Reference d0e16d1871fd1436/R: No simplification + Stack, 67 zones, 3,953 m² conditioned; annual sensible heating 3.6 and cooling 57.6 kWh/m²; peak heating 23.6 and cooling 85.5 kW. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Single zone building | 1 | 1.52 | -99.6 | -18.6 | 223.9 | 37.5 | 99.6 | 18.6 | -41.7 | 8.3 | no |
| Perimeter core 3 m + Single zone building | 1 | 1.52 | -99.6 | -18.5 | 223.8 | 37.4 | 99.6 | 18.5 | -41.3 | 8.3 | no |
| Perimeter core 4.57 m + Single zone building | 1 | 1.52 | -99.6 | -18.5 | 223.8 | 37.4 | 99.6 | 18.5 | -41.2 | 8.3 | no |
| Conditioned merge + Single zone per floor type | 4 | 1.52 | -49.3 | -12.4 | 92.7 | 14.3 | 49.3 | 12.4 | -34.2 | -5.3 | no |
| Perimeter core 3 m + Single zone per floor type | 4 | 1.52 | -49.1 | -12.3 | 92.2 | 14.2 | 49.1 | 12.3 | -34.1 | -5.3 | no |
| Perimeter core 4.57 m + Single zone per floor type | 4 | 1.52 | -49.1 | -12.3 | 92.1 | 14.2 | 49.1 | 12.3 | -34.1 | -5.3 | no |
| Single zone per floor + Stacked floor zone multiplier | 4 | 1.52 | 41.3 | -4.5 | 93.5 | 12.3 | -41.3 | 4.5 | 10.9 | -4.1 | no |
| Conditioned merge + Stack | 8 | 0.00 | -51.1 | -12.3 | 95.4 | 13.5 | 51.1 | 12.3 | -26.7 | -3.4 | no |
| Conditioned merge + Stacked floor zone multiplier | 8 | 0.00 | 45.8 | -4.3 | 102.6 | 10.5 | -45.8 | 4.3 | 22.1 | -2.5 | no |
| Perimeter core 3 m + Stack | 20 | 1.52 | -31.1 | -5.5 | 56.1 | 7.9 | 31.1 | 5.5 | -10.7 | -4.2 | no |
| Perimeter core 3 m + Stacked floor zone multiplier | 20 | 1.52 | 47.7 | 0.4 | 101.1 | 9.9 | -47.7 | -0.4 | 17.1 | -3.2 | no |
| Perimeter core 4.57 m + Stack | 20 | 1.52 | -29.7 | -5.5 | 53.5 | 7.7 | 29.7 | 5.5 | -21.7 | -4.7 | no |
| Perimeter core 4.57 m + Stacked floor zone multiplier | 20 | 1.52 | 47.7 | 0.0 | 101.2 | 9.9 | -47.7 | -0.0 | 11.0 | -3.8 | no |
| Semantic merge + Stack | 43 | 0.00 | -5.8 | -0.5 | 12.8 | 1.4 | 5.8 | 0.5 | -2.9 | -0.6 | yes, recommended |
| Semantic merge + Stacked floor zone multiplier | 43 | 0.00 | 66.6 | 4.7 | 114.9 | 8.7 | -66.6 | -4.7 | 25.1 | -0.4 | no |
| No simplification + Stacked floor zone multiplier | 67 | 0.00 | 68.0 | 4.9 | 116.3 | 8.5 | -68.0 | -4.9 | 27.9 | 0.7 | no |
7 zonings write the same model as a listed one and are not shown
- No simplification + Single zone building → Conditioned merge + Single zone building
- No simplification + Single zone per floor type → Conditioned merge + Single zone per floor type
- Semantic merge + Single zone building → Conditioned merge + Single zone building
- Semantic merge + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Single zone building → Conditioned merge + Single zone building
- Single zone per floor + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Stack → Conditioned merge + Single zone per floor type
7A · 90.1-2007 · 0°
Reference 6d45b7d42ebf83f6/R: No simplification + Stack, 67 zones, 3,953 m² conditioned; annual sensible heating 8.5 and cooling 67.4 kWh/m²; peak heating 44.8 and cooling 105.9 kW. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Single zone building | 1 | 1.52 | -76.7 | -19.4 | 159.9 | 40.5 | 76.7 | 19.4 | 11.9 | 8.0 | no |
| Perimeter core 3 m + Single zone building | 1 | 1.52 | -76.6 | -19.3 | 159.7 | 40.5 | 76.6 | 19.3 | 11.9 | 8.0 | no |
| Perimeter core 4.57 m + Single zone building | 1 | 1.52 | -76.5 | -19.3 | 159.7 | 40.5 | 76.5 | 19.3 | 11.9 | 8.0 | no |
| Conditioned merge + Single zone per floor type | 4 | 1.52 | -29.6 | -11.4 | 53.5 | 13.9 | 29.6 | 11.4 | -13.4 | -3.6 | no |
| Perimeter core 3 m + Single zone per floor type | 4 | 1.52 | -29.4 | -11.4 | 53.2 | 13.8 | 29.4 | 11.4 | -13.4 | -3.6 | no |
| Perimeter core 4.57 m + Single zone per floor type | 4 | 1.52 | -29.4 | -11.4 | 53.1 | 13.8 | 29.4 | 11.4 | -13.3 | -3.6 | no |
| Single zone per floor + Stacked floor zone multiplier | 4 | 1.52 | 19.7 | -4.1 | 42.3 | 10.4 | -19.7 | 4.1 | 2.7 | -1.7 | no |
| Conditioned merge + Stack | 8 | 0.00 | -30.1 | -11.4 | 53.9 | 13.5 | 30.1 | 11.4 | -14.6 | -2.9 | no |
| Conditioned merge + Stacked floor zone multiplier | 8 | 0.00 | 21.7 | -3.8 | 44.9 | 8.5 | -21.7 | 3.8 | 2.5 | -1.1 | no |
| Perimeter core 3 m + Stack | 20 | 1.52 | -12.8 | -4.1 | 25.7 | 7.2 | 12.8 | 4.1 | -7.4 | -3.1 | no |
| Perimeter core 3 m + Stacked floor zone multiplier | 20 | 1.52 | 26.2 | 1.3 | 45.4 | 9.2 | -26.2 | -1.3 | 3.9 | -1.4 | no |
| Perimeter core 4.57 m + Stack | 20 | 1.52 | -14.0 | -4.7 | 26.5 | 7.0 | 14.0 | 4.7 | -6.8 | -3.5 | no |
| Perimeter core 4.57 m + Stacked floor zone multiplier | 20 | 1.52 | 25.3 | 0.6 | 44.1 | 8.8 | -25.3 | -0.6 | 2.6 | -1.8 | no |
| Semantic merge + Stack | 43 | 0.00 | -2.4 | -0.5 | 5.6 | 1.4 | 2.4 | 0.5 | -0.2 | -1.1 | yes, recommended |
| Semantic merge + Stacked floor zone multiplier | 43 | 0.00 | 35.1 | 4.8 | 55.8 | 7.9 | -35.1 | -4.8 | 5.1 | 0.7 | no |
| No simplification + Stacked floor zone multiplier | 67 | 0.00 | 35.7 | 5.0 | 56.8 | 7.8 | -35.7 | -5.0 | 6.0 | 1.8 | no |
7 zonings write the same model as a listed one and are not shown
- No simplification + Single zone building → Conditioned merge + Single zone building
- No simplification + Single zone per floor type → Conditioned merge + Single zone per floor type
- Semantic merge + Single zone building → Conditioned merge + Single zone building
- Semantic merge + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Single zone building → Conditioned merge + Single zone building
- Single zone per floor + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Stack → Conditioned merge + Single zone per floor type
7A · 90.1-2007 · 45°
Reference 4a235496869c6ad0/R: No simplification + Stack, 67 zones, 3,953 m² conditioned; annual sensible heating 6.1 and cooling 66.3 kWh/m²; peak heating 33.9 and cooling 95.8 kW. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Single zone building | 1 | 1.52 | -91.3 | -18.0 | 193.8 | 37.7 | 91.3 | 18.0 | 7.9 | 7.2 | no |
| Perimeter core 3 m + Single zone building | 1 | 1.52 | -91.2 | -17.9 | 193.7 | 37.6 | 91.2 | 17.9 | 8.0 | 7.2 | no |
| Perimeter core 4.57 m + Single zone building | 1 | 1.52 | -91.2 | -17.9 | 193.7 | 37.6 | 91.2 | 17.9 | 8.0 | 7.2 | no |
| Conditioned merge + Single zone per floor type | 4 | 1.52 | -33.8 | -10.6 | 60.7 | 12.5 | 33.8 | 10.6 | -15.6 | -3.4 | no |
| Perimeter core 3 m + Single zone per floor type | 4 | 1.52 | -33.6 | -10.6 | 60.3 | 12.5 | 33.6 | 10.6 | -15.4 | -3.4 | no |
| Perimeter core 4.57 m + Single zone per floor type | 4 | 1.52 | -33.6 | -10.6 | 60.3 | 12.5 | 33.6 | 10.6 | -15.4 | -3.4 | no |
| Single zone per floor + Stacked floor zone multiplier | 4 | 1.52 | 30.1 | -3.3 | 57.9 | 9.7 | -30.1 | 3.3 | 9.2 | -2.2 | no |
| Conditioned merge + Stack | 8 | 0.00 | -34.9 | -10.6 | 62.1 | 11.8 | 34.9 | 10.6 | -17.5 | -2.6 | no |
| Conditioned merge + Stacked floor zone multiplier | 8 | 0.00 | 32.3 | -2.9 | 61.4 | 7.6 | -32.3 | 2.9 | 9.0 | -1.3 | no |
| Perimeter core 3 m + Stack | 20 | 1.52 | -20.6 | -4.6 | 36.1 | 6.8 | 20.6 | 4.6 | -9.7 | -3.2 | no |
| Perimeter core 3 m + Stacked floor zone multiplier | 20 | 1.52 | 32.8 | 0.9 | 58.8 | 8.3 | -32.8 | -0.9 | 13.1 | -2.1 | no |
| Perimeter core 4.57 m + Stack | 20 | 1.52 | -20.1 | -4.9 | 35.4 | 6.9 | 20.1 | 4.9 | -7.2 | -3.7 | no |
| Perimeter core 4.57 m + Stacked floor zone multiplier | 20 | 1.52 | 32.6 | 0.4 | 58.6 | 8.3 | -32.6 | -0.4 | 9.5 | -2.6 | no |
| Semantic merge + Stack | 43 | 0.00 | -4.0 | -0.5 | 8.7 | 1.5 | 4.0 | 0.5 | -0.3 | -1.1 | yes, recommended |
| Semantic merge + Stacked floor zone multiplier | 43 | 0.00 | 44.6 | 4.6 | 71.7 | 7.5 | -44.6 | -4.6 | 10.8 | 0.3 | no |
| No simplification + Stacked floor zone multiplier | 67 | 0.00 | 46.7 | 4.9 | 74.6 | 7.5 | -46.7 | -4.9 | 11.7 | 1.3 | no |
7 zonings write the same model as a listed one and are not shown
- No simplification + Single zone building → Conditioned merge + Single zone building
- No simplification + Single zone per floor type → Conditioned merge + Single zone per floor type
- Semantic merge + Single zone building → Conditioned merge + Single zone building
- Semantic merge + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Single zone building → Conditioned merge + Single zone building
- Single zone per floor + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Stack → Conditioned merge + Single zone per floor type
7A · 90.1-2019 · 0°
Reference c1480c625c39e232/R: No simplification + Stack, 67 zones, 3,953 m² conditioned; annual sensible heating 9.5 and cooling 55.8 kWh/m²; peak heating 42.4 and cooling 93.0 kW. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Single zone building | 1 | 1.52 | -76.2 | -23.7 | 152.6 | 49.8 | 76.2 | 23.7 | 8.3 | 8.8 | no |
| Perimeter core 3 m + Single zone building | 1 | 1.52 | -76.1 | -23.7 | 152.4 | 49.8 | 76.1 | 23.7 | 8.4 | 8.9 | no |
| Perimeter core 4.57 m + Single zone building | 1 | 1.52 | -76.0 | -23.7 | 152.4 | 49.8 | 76.0 | 23.7 | 8.4 | 8.9 | no |
| Conditioned merge + Single zone per floor type | 4 | 1.52 | -33.6 | -14.2 | 58.3 | 18.5 | 33.6 | 14.2 | -17.1 | -4.0 | no |
| Perimeter core 3 m + Single zone per floor type | 4 | 1.52 | -33.4 | -14.1 | 58.1 | 18.4 | 33.4 | 14.1 | -17.1 | -4.0 | no |
| Perimeter core 4.57 m + Single zone per floor type | 4 | 1.52 | -33.4 | -14.1 | 58.0 | 18.4 | 33.4 | 14.1 | -17.1 | -4.0 | no |
| Single zone per floor + Stacked floor zone multiplier | 4 | 1.52 | 14.7 | -4.9 | 36.1 | 12.2 | -14.7 | 4.9 | -1.4 | -2.3 | no |
| Conditioned merge + Stack | 8 | 0.00 | -33.8 | -14.2 | 58.0 | 18.4 | 33.8 | 14.2 | -18.3 | -3.1 | no |
| Conditioned merge + Stacked floor zone multiplier | 8 | 0.00 | 17.6 | -4.6 | 39.9 | 10.2 | -17.6 | 4.6 | -1.6 | -1.4 | no |
| Perimeter core 3 m + Stack | 20 | 1.52 | -19.6 | -6.4 | 35.0 | 9.3 | 19.6 | 6.4 | -9.1 | -3.4 | no |
| Perimeter core 3 m + Stacked floor zone multiplier | 20 | 1.52 | 19.4 | 0.7 | 37.5 | 10.3 | -19.4 | -0.7 | -0.8 | -2.3 | no |
| Perimeter core 4.57 m + Stack | 20 | 1.52 | -19.0 | -6.3 | 33.5 | 8.8 | 19.0 | 6.3 | -8.0 | -4.0 | no |
| Perimeter core 4.57 m + Stacked floor zone multiplier | 20 | 1.52 | 18.9 | 0.4 | 36.6 | 10.1 | -18.9 | -0.4 | -1.8 | -2.7 | no |
| Semantic merge + Stack | 43 | 0.00 | -2.5 | -0.6 | 5.4 | 1.5 | 2.5 | 0.6 | -0.2 | -1.2 | yes, recommended |
| Semantic merge + Stacked floor zone multiplier | 43 | 0.00 | 30.3 | 5.3 | 47.8 | 9.0 | -30.3 | -5.3 | 2.4 | 0.6 | no |
| No simplification + Stacked floor zone multiplier | 67 | 0.00 | 31.0 | 5.6 | 48.7 | 8.9 | -31.0 | -5.6 | 2.8 | 1.7 | no |
7 zonings write the same model as a listed one and are not shown
- No simplification + Single zone building → Conditioned merge + Single zone building
- No simplification + Single zone per floor type → Conditioned merge + Single zone per floor type
- Semantic merge + Single zone building → Conditioned merge + Single zone building
- Semantic merge + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Single zone building → Conditioned merge + Single zone building
- Single zone per floor + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Stack → Conditioned merge + Single zone per floor type
7A · 90.1-2019 · 45°
Reference 2cda6771e889b07d/R: No simplification + Stack, 67 zones, 3,953 m² conditioned; annual sensible heating 8.5 and cooling 52.8 kWh/m²; peak heating 37.2 and cooling 84.2 kW. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Single zone building | 1 | 1.52 | -84.1 | -24.6 | 167.1 | 51.0 | 84.1 | 24.6 | 6.8 | 8.1 | no |
| Perimeter core 3 m + Single zone building | 1 | 1.52 | -84.0 | -24.6 | 167.0 | 50.9 | 84.0 | 24.6 | 6.9 | 8.1 | no |
| Perimeter core 4.57 m + Single zone building | 1 | 1.52 | -84.0 | -24.5 | 167.0 | 50.9 | 84.0 | 24.5 | 6.9 | 8.1 | no |
| Conditioned merge + Single zone per floor type | 4 | 1.52 | -36.0 | -14.3 | 62.4 | 18.4 | 36.0 | 14.3 | -16.5 | -4.3 | no |
| Perimeter core 3 m + Single zone per floor type | 4 | 1.52 | -35.8 | -14.2 | 62.1 | 18.3 | 35.8 | 14.2 | -16.4 | -4.2 | no |
| Perimeter core 4.57 m + Single zone per floor type | 4 | 1.52 | -35.8 | -14.2 | 62.1 | 18.3 | 35.8 | 14.2 | -16.4 | -4.2 | no |
| Single zone per floor + Stacked floor zone multiplier | 4 | 1.52 | 19.8 | -3.9 | 41.1 | 12.3 | -19.8 | 3.9 | -1.6 | -3.7 | no |
| Conditioned merge + Stack | 8 | 0.00 | -36.2 | -14.3 | 61.8 | 18.3 | 36.2 | 14.3 | -16.8 | -2.8 | no |
| Conditioned merge + Stacked floor zone multiplier | 8 | 0.00 | 23.0 | -3.7 | 45.7 | 10.1 | -23.0 | 3.7 | 2.9 | -2.0 | no |
| Perimeter core 3 m + Stack | 20 | 1.52 | -23.1 | -6.6 | 39.1 | 9.4 | 23.1 | 6.6 | -11.0 | -3.6 | no |
| Perimeter core 3 m + Stacked floor zone multiplier | 20 | 1.52 | 22.1 | 1.2 | 43.5 | 10.4 | -22.1 | -1.2 | -1.2 | -3.0 | no |
| Perimeter core 4.57 m + Stack | 20 | 1.52 | -21.5 | -6.3 | 36.4 | 8.8 | 21.5 | 6.3 | -10.0 | -4.1 | no |
| Perimeter core 4.57 m + Stacked floor zone multiplier | 20 | 1.52 | 21.7 | 0.9 | 42.7 | 10.3 | -21.7 | -0.9 | -2.2 | -3.7 | no |
| Semantic merge + Stack | 43 | 0.00 | -3.1 | -0.6 | 6.3 | 1.4 | 3.1 | 0.6 | -0.3 | -1.0 | yes, recommended |
| Semantic merge + Stacked floor zone multiplier | 43 | 0.00 | 33.9 | 5.7 | 53.4 | 9.6 | -33.9 | -5.7 | 6.3 | -0.1 | no |
| No simplification + Stacked floor zone multiplier | 67 | 0.00 | 34.7 | 5.9 | 54.2 | 9.4 | -34.7 | -5.9 | 7.3 | 0.9 | no |
7 zonings write the same model as a listed one and are not shown
- No simplification + Single zone building → Conditioned merge + Single zone building
- No simplification + Single zone per floor type → Conditioned merge + Single zone per floor type
- Semantic merge + Single zone building → Conditioned merge + Single zone building
- Semantic merge + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Single zone building → Conditioned merge + Single zone building
- Single zone per floor + Single zone per floor type → Conditioned merge + Single zone per floor type
- Single zone per floor + Stack → Conditioned merge + Single zone per floor type
Atlas programs
The atlas programs each program key of the prototype takes, as the suite's saved inputs name them (release 2.4.0 IDs); the prototype's geometry and glazing are BEMGen's DOE record. Method and caveats.