Supermarket zoning
Supermarket · geometric LOD study drop 5 · atlas inputs release 2.4.0 · BEMGen 99c0b0adcd44
- Prototype
- Supermarket
- Cells
- 24: 6 climate zones × 2 vintages × 2 orientations
- Cells with a recommended zoning
- 17 of 24
- Robust across orientations
- 8 of 12 cell pairs: Conditioned merge + Single zone building (6)
- Reference zoning
- No simplification + Stack
- Reference zones
- 6
- Most often recommended
- Conditioned merge + Single zone building (12 of 24 cells)
- Serial cost (R5)
- timed in 2 of 24 cells (3C 90.1-2019 0°, 5A 90.1-2019 0°)
Robust across orientations
Robust across orientations in 8 of 12 cell pairs (0° and 45°).
| Climate zone | Vintage | Robust zoning | Zones | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Area change % | CPU ratio | Wall ratio | Memory ratio | Per orientation |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 2A | 90.1-2007 | Conditioned merge + Single zone building | 1 | – | -1.4 | – | 3.0 | – | 1.4 | 0.00 | not timed | recommended at both orientations | ||
| 2A | 90.1-2019 | Conditioned merge + Single zone building (tie: No simplification + Single zone building, Perimeter core 3 m + Single zone building, Perimeter core 4.57 m + Single zone building) | 1 | – | -1.5 | – | 3.3 | – | 1.5 | 0.00 | not timed | recommended at both orientations | ||
| 2B | 90.1-2007 | Conditioned merge + Single zone building | 1 | – | -1.7 | – | 3.5 | – | 1.7 | 0.00 | not timed | recommended at both orientations | ||
| 2B | 90.1-2019 | Conditioned merge + Single zone building (tie: No simplification + Single zone building, Perimeter core 3 m + Single zone building, Perimeter core 4.57 m + Single zone building) | 1 | -100.0 | -2.2 | 901.6 | 4.6 | 100.0 | 2.2 | 0.00 | not timed | recommended at both orientations | ||
| 3C | 90.1-2007 | Conditioned merge + Single zone building | 1 | – | -2.7 | – | 5.0 | – | 2.7 | 0.00 | not timed | recommended at both orientations | ||
| 3C | 90.1-2019 | Conditioned merge + Single zone building (tie: No simplification + Single zone building, Perimeter core 3 m + Single zone building, Perimeter core 4.57 m + Single zone building) | 1 | – | -4.6 | – | 8.2 | – | 4.6 | 0.00 | 0.298 | 0.300 | 0.978 | recommended at both orientations |
| 4A | 90.1-2007 | none meets the threshold at both orientations | 0°: none · 45°: none | |||||||||||
| 4A | 90.1-2019 | none meets the threshold at both orientations | 0°: none · 45°: none | |||||||||||
| 5A | 90.1-2007 | none meets the threshold at both orientations | 0°: none · 45°: none | |||||||||||
| 5A | 90.1-2019 | none meets the threshold at both orientations | 0°: none · 45°: Perimeter core 4.57 m + Stack (5 zones) | |||||||||||
| 7A | 90.1-2007 | Perimeter core 3 m + Stack (tie: Perimeter core 4.57 m + Stack) | 5 | -4.4 | -2.3 | 21.7 | 7.7 | 4.4 | 2.3 | 0.00 | not timed | recommended at both orientations | ||
| 7A | 90.1-2019 | Perimeter core 3 m + Stack (tie: Perimeter core 4.57 m + Stack) | 5 | -4.1 | -3.1 | 21.0 | 10.9 | 4.1 | 3.1 | 0.00 | not timed | recommended at both orientations | ||
For each prototype, climate zone and vintage, the robust zoning is the coarsest (fewest modelled zones) that meets the threshold at every orientation of the cell pair, by the writer's own verdict on each zoning at each orientation, with at most the reference's zone count, as the writer bounds a recommendation (D-220); a duplicate never meets, as the writer lists it. Ties at the fewest zones go to a zoning both orientations recommend, else to the first in the study's zoning order (simplifier, join pieces, perimeter depth, stacker, IWHT, FHT); the tied zonings are named. The errors reported are the worse of the orientations' values for each metric, so the row is a bound, not a mean; the cost ratios are the medians over the timed sites of that zoning in the pair. Where both orientations recommend the same zoning it is the robust one. A pair where no zoning meets the threshold at both orientations says so and names each orientation's own recommendation; the per-orientation rows below stay the reading for one orientation. The cost ratios are the median over the timed sites of the robust zoning in the pair (in this drop one orientation at most is timed, so the ratio is that site's); not timed where none is. The rule and its limits.
Recommended zonings
| Climate zone | Vintage | Orientation | Reference zones | Heating kWh/m² | Cooling kWh/m² | Recommended zoning | Zones | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Area change % | CPU ratio | Wall ratio | Memory ratio |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 2A | 90.1-2007 | 0° | 6 | 0.0 | 147.3 | Conditioned merge + Single zone building | 1 | – | -1.2 | – | 2.8 | – | 1.2 | 0.00 | not timed | ||
| 2A | 90.1-2007 | 45° | 6 | 0.0 | 143.6 | Conditioned merge + Single zone building | 1 | – | -1.4 | – | 3.0 | – | 1.4 | 0.00 | not timed | ||
| 2A | 90.1-2019 | 0° | 6 | 0.0 | 119.6 | Conditioned merge + Single zone building | 1 | – | -1.4 | – | 2.9 | – | 1.4 | 0.00 | not timed | ||
| 2A | 90.1-2019 | 0° | 6 | 0.0 | 119.6 | No simplification + Single zone building | 1 | – | -1.3 | – | 2.9 | – | 1.3 | 0.00 | not timed | ||
| 2A | 90.1-2019 | 0° | 6 | 0.0 | 119.6 | Perimeter core 3 m + Single zone building | 1 | – | -1.4 | – | 2.9 | – | 1.4 | 0.00 | not timed | ||
| 2A | 90.1-2019 | 0° | 6 | 0.0 | 119.6 | Perimeter core 4.57 m + Single zone building | 1 | – | -1.4 | – | 2.9 | – | 1.4 | 0.00 | not timed | ||
| 2A | 90.1-2019 | 45° | 6 | 0.0 | 114.7 | Conditioned merge + Single zone building | 1 | – | -1.5 | – | 3.3 | – | 1.5 | 0.00 | not timed | ||
| 2A | 90.1-2019 | 45° | 6 | 0.0 | 114.7 | No simplification + Single zone building | 1 | – | -1.5 | – | 3.2 | – | 1.5 | 0.00 | not timed | ||
| 2A | 90.1-2019 | 45° | 6 | 0.0 | 114.7 | Perimeter core 3 m + Single zone building | 1 | – | -1.5 | – | 3.3 | – | 1.5 | 0.00 | not timed | ||
| 2A | 90.1-2019 | 45° | 6 | 0.0 | 114.7 | Perimeter core 4.57 m + Single zone building | 1 | – | -1.5 | – | 3.3 | – | 1.5 | 0.00 | not timed | ||
| 2B | 90.1-2007 | 0° | 6 | 0.0 | 138.5 | Conditioned merge + Single zone building | 1 | – | -1.5 | – | 2.8 | – | 1.5 | 0.00 | not timed | ||
| 2B | 90.1-2007 | 45° | 6 | 0.0 | 134.1 | Conditioned merge + Single zone building | 1 | – | -1.7 | – | 3.5 | – | 1.7 | 0.00 | not timed | ||
| 2B | 90.1-2019 | 0° | 6 | 0.1 | 112.1 | Conditioned merge + Single zone building | 1 | -100.0 | -2.1 | 841.4 | 4.2 | 100.0 | 2.1 | 0.00 | not timed | ||
| 2B | 90.1-2019 | 0° | 6 | 0.1 | 112.1 | No simplification + Single zone building | 1 | -100.0 | -2.0 | 841.4 | 4.2 | 100.0 | 2.0 | 0.00 | not timed | ||
| 2B | 90.1-2019 | 0° | 6 | 0.1 | 112.1 | Perimeter core 3 m + Single zone building | 1 | -100.0 | -2.1 | 841.4 | 4.2 | 100.0 | 2.1 | 0.00 | not timed | ||
| 2B | 90.1-2019 | 0° | 6 | 0.1 | 112.1 | Perimeter core 4.57 m + Single zone building | 1 | -100.0 | -2.1 | 841.4 | 4.2 | 100.0 | 2.1 | 0.00 | not timed | ||
| 2B | 90.1-2019 | 45° | 6 | 0.1 | 106.1 | Conditioned merge + Single zone building | 1 | -100.0 | -2.2 | 901.6 | 4.6 | 100.0 | 2.2 | 0.00 | not timed | ||
| 2B | 90.1-2019 | 45° | 6 | 0.1 | 106.1 | No simplification + Single zone building | 1 | -100.0 | -2.2 | 901.6 | 4.6 | 100.0 | 2.2 | 0.00 | not timed | ||
| 2B | 90.1-2019 | 45° | 6 | 0.1 | 106.1 | Perimeter core 3 m + Single zone building | 1 | -100.0 | -2.2 | 901.6 | 4.6 | 100.0 | 2.2 | 0.00 | not timed | ||
| 2B | 90.1-2019 | 45° | 6 | 0.1 | 106.1 | Perimeter core 4.57 m + Single zone building | 1 | -100.0 | -2.2 | 901.6 | 4.6 | 100.0 | 2.2 | 0.00 | not timed | ||
| 3C | 90.1-2007 | 0° | 6 | 0.0 | 89.2 | Conditioned merge + Single zone building | 1 | – | -2.4 | – | 4.6 | – | 2.4 | 0.00 | not timed | ||
| 3C | 90.1-2007 | 45° | 6 | 0.0 | 89.9 | Conditioned merge + Single zone building | 1 | – | -2.7 | – | 5.0 | – | 2.7 | 0.00 | not timed | ||
| 3C | 90.1-2019 | 0° | 6 | 0.1 | 67.0 | Conditioned merge + Single zone building | 1 | – | -4.3 | – | 7.4 | – | 4.3 | 0.00 | 0.298 | 0.300 | 0.978 |
| 3C | 90.1-2019 | 0° | 6 | 0.1 | 67.0 | No simplification + Single zone building | 1 | – | -4.3 | – | 7.4 | – | 4.3 | 0.00 | 0.597 | 0.602 | 0.983 |
| 3C | 90.1-2019 | 0° | 6 | 0.1 | 67.0 | Perimeter core 3 m + Single zone building | 1 | – | -4.3 | – | 7.4 | – | 4.3 | 0.00 | 0.335 | 0.333 | 0.975 |
| 3C | 90.1-2019 | 0° | 6 | 0.1 | 67.0 | Perimeter core 4.57 m + Single zone building | 1 | – | -4.3 | – | 7.4 | – | 4.3 | 0.00 | 0.335 | 0.332 | 0.975 |
| 3C | 90.1-2019 | 45° | 6 | 0.1 | 64.0 | Conditioned merge + Single zone building | 1 | – | -4.6 | – | 8.2 | – | 4.6 | 0.00 | not timed | ||
| 3C | 90.1-2019 | 45° | 6 | 0.1 | 64.0 | No simplification + Single zone building | 1 | – | -4.6 | – | 8.2 | – | 4.6 | 0.00 | not timed | ||
| 3C | 90.1-2019 | 45° | 6 | 0.1 | 64.0 | Perimeter core 3 m + Single zone building | 1 | – | -4.6 | – | 8.2 | – | 4.6 | 0.00 | not timed | ||
| 3C | 90.1-2019 | 45° | 6 | 0.1 | 64.0 | Perimeter core 4.57 m + Single zone building | 1 | – | -4.6 | – | 8.2 | – | 4.6 | 0.00 | not timed | ||
| 4A | 90.1-2007 | 0° | 6 | 3.9 | 82.5 | none meets the threshold | |||||||||||
| 4A | 90.1-2007 | 45° | 6 | 3.7 | 78.0 | none meets the threshold | |||||||||||
| 4A | 90.1-2019 | 0° | 6 | 5.2 | 65.3 | none meets the threshold | |||||||||||
| 4A | 90.1-2019 | 45° | 6 | 5.4 | 58.9 | none meets the threshold | |||||||||||
| 5A | 90.1-2007 | 0° | 6 | 9.8 | 61.7 | none meets the threshold | |||||||||||
| 5A | 90.1-2007 | 45° | 6 | 8.7 | 59.8 | none meets the threshold | |||||||||||
| 5A | 90.1-2019 | 0° | 6 | 11.6 | 48.7 | none meets the threshold | |||||||||||
| 5A | 90.1-2019 | 45° | 6 | 11.3 | 44.3 | Perimeter core 4.57 m + Stack | 5 | -8.7 | -2.1 | 26.5 | 6.3 | 8.7 | 2.1 | 0.00 | not timed | ||
| 7A | 90.1-2007 | 0° | 6 | 25.2 | 54.7 | Perimeter core 3 m + Stack | 5 | -3.6 | -1.6 | 21.7 | 7.5 | 3.6 | 1.6 | 0.00 | not timed | ||
| 7A | 90.1-2007 | 0° | 6 | 25.2 | 54.7 | Perimeter core 4.57 m + Stack | 5 | -3.2 | -1.4 | 18.4 | 6.3 | 3.2 | 1.4 | 0.00 | not timed | ||
| 7A | 90.1-2007 | 45° | 6 | 23.9 | 50.3 | Perimeter core 3 m + Stack | 5 | -4.4 | -2.3 | 19.7 | 7.7 | 4.4 | 2.3 | 0.00 | not timed | ||
| 7A | 90.1-2007 | 45° | 6 | 23.9 | 50.3 | Perimeter core 4.57 m + Stack | 5 | -3.5 | -2.0 | 14.9 | 6.3 | 3.5 | 2.0 | 0.00 | not timed | ||
| 7A | 90.1-2019 | 0° | 6 | 25.2 | 42.9 | Perimeter core 3 m + Stack | 5 | -4.1 | -3.1 | 21.0 | 10.9 | 4.1 | 3.1 | 0.00 | not timed | ||
| 7A | 90.1-2019 | 0° | 6 | 25.2 | 42.9 | Perimeter core 4.57 m + Stack | 5 | -3.6 | -2.8 | 17.3 | 9.2 | 3.6 | 2.8 | 0.00 | not timed | ||
| 7A | 90.1-2019 | 45° | 6 | 25.7 | 37.4 | Perimeter core 3 m + Stack | 5 | -3.8 | -2.9 | 15.1 | 9.6 | 3.8 | 2.9 | 0.00 | not timed | ||
| 7A | 90.1-2019 | 45° | 6 | 25.7 | 37.4 | Perimeter core 4.57 m + Stack | 5 | -3.0 | -2.7 | 11.4 | 8.0 | 3.0 | 2.7 | 0.00 | not timed | ||
The coarsest zonings (fewest modelled zones) meeting the threshold; ties are all listed. Errors are the test zoning against the reference: annual sensible load, hourly CV(RMSE) and NMBE, and the change of conditioned floor area. A muted value belongs to a load the threshold does not judge; a dash is a value the runner did not store; a flagged value carries the runner's own flag. The cost ratios are the serial timing pass (R5): the zoning's processor time, wall clock and peak committed memory over its reference's, each the median of its repeats; not timed marks a cell outside the timed ones. Cost protocol.
Every zoning by cell
2A · 90.1-2007 · 0°
Reference c69000833f88d380/R: No simplification + Stack, 6 zones, 4,181 m² conditioned; annual sensible heating 0.0 and cooling 147.3 kWh/m²; peak heating 0.5 and cooling 180.9 kW. Sensible heating is below 1 kWh/m² and is not judged. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Single zone building | 1 | 0.00 | – | -1.2 | – | 2.8 | – | 1.2 | -100.0 | -2.7 | yes, recommended |
| Perimeter core 3 m + Stack | 5 | 0.00 | – | 0.6 | – | 2.3 | – | -0.6 | 1,388.2 | 1.0 | yes |
| Perimeter core 4.57 m + Stack | 5 | 0.00 | – | 0.5 | – | 1.9 | – | -0.5 | 849.6 | 0.8 | yes |
20 zonings write the same model as a listed one and are not shown
- Conditioned merge + Single zone per floor type → Conditioned merge + Single zone building
- Conditioned merge + Stack → Conditioned merge + Single zone building
- Conditioned merge + Stacked floor zone multiplier → Conditioned merge + Single zone building
- No simplification + Single zone building → Conditioned merge + Single zone building
- No simplification + Single zone per floor type → Conditioned merge + Single zone building
- No simplification + Stacked floor zone multiplier → c69000833f88d380/R
- Perimeter core 3 m + Single zone building → Conditioned merge + Single zone building
- Perimeter core 3 m + Single zone per floor type → Conditioned merge + Single zone building
- Perimeter core 3 m + Stacked floor zone multiplier → Perimeter core 3 m + Stack
- Perimeter core 4.57 m + Single zone building → Conditioned merge + Single zone building
- Perimeter core 4.57 m + Single zone per floor type → Conditioned merge + Single zone building
- Perimeter core 4.57 m + Stacked floor zone multiplier → Perimeter core 4.57 m + Stack
- Semantic merge + Single zone building → Conditioned merge + Single zone building
- Semantic merge + Single zone per floor type → Conditioned merge + Single zone building
- Semantic merge + Stack → c69000833f88d380/R
- Semantic merge + Stacked floor zone multiplier → c69000833f88d380/R
- Single zone per floor + Single zone building → Conditioned merge + Single zone building
- Single zone per floor + Single zone per floor type → Conditioned merge + Single zone building
- Single zone per floor + Stack → Conditioned merge + Single zone building
- Single zone per floor + Stacked floor zone multiplier → Conditioned merge + Single zone building
2A · 90.1-2007 · 45°
Reference 1022f6e78942bd57/R: No simplification + Stack, 6 zones, 4,181 m² conditioned; annual sensible heating 0.0 and cooling 143.6 kWh/m²; peak heating 0.3 and cooling 183.5 kW. Sensible heating is below 1 kWh/m² and is not judged. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Single zone building | 1 | 0.00 | – | -1.4 | – | 3.0 | – | 1.4 | -100.0 | -1.3 | yes, recommended |
| Perimeter core 3 m + Stack | 5 | 0.00 | – | 0.2 | – | 2.0 | – | -0.2 | 294.1 | 1.3 | yes |
| Perimeter core 4.57 m + Stack | 5 | 0.00 | – | 0.1 | – | 1.8 | – | -0.1 | -1.5 | 0.8 | yes |
| Semantic merge + Stack | 6 | 0.00 | – | -0.0 | – | 0.0 | – | 0.0 | 0.0 | -0.0 | yes |
19 zonings write the same model as a listed one and are not shown
- Conditioned merge + Single zone per floor type → Conditioned merge + Single zone building
- Conditioned merge + Stack → Conditioned merge + Single zone building
- Conditioned merge + Stacked floor zone multiplier → Conditioned merge + Single zone building
- No simplification + Single zone building → Conditioned merge + Single zone building
- No simplification + Single zone per floor type → Conditioned merge + Single zone building
- No simplification + Stacked floor zone multiplier → 1022f6e78942bd57/R
- Perimeter core 3 m + Single zone building → Conditioned merge + Single zone building
- Perimeter core 3 m + Single zone per floor type → Conditioned merge + Single zone building
- Perimeter core 3 m + Stacked floor zone multiplier → Perimeter core 3 m + Stack
- Perimeter core 4.57 m + Single zone building → Conditioned merge + Single zone building
- Perimeter core 4.57 m + Single zone per floor type → Conditioned merge + Single zone building
- Perimeter core 4.57 m + Stacked floor zone multiplier → Perimeter core 4.57 m + Stack
- Semantic merge + Single zone building → Conditioned merge + Single zone building
- Semantic merge + Single zone per floor type → Conditioned merge + Single zone building
- Semantic merge + Stacked floor zone multiplier → Semantic merge + Stack
- Single zone per floor + Single zone building → Conditioned merge + Single zone building
- Single zone per floor + Single zone per floor type → Conditioned merge + Single zone building
- Single zone per floor + Stack → Conditioned merge + Single zone building
- Single zone per floor + Stacked floor zone multiplier → Conditioned merge + Single zone building
2A · 90.1-2019 · 0°
Reference 32ef8882e9af8a21/R: No simplification + Stack, 6 zones, 4,181 m² conditioned; annual sensible heating 0.0 and cooling 119.6 kWh/m²; peak heating 3.3 and cooling 151.8 kW. Sensible heating is below 1 kWh/m² and is not judged. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Single zone building | 1 | 0.00 | – | -1.4 | – | 2.9 | – | 1.4 | -100.0 | -9.4 | yes, recommended |
| No simplification + Single zone building | 1 | 0.00 | – | -1.3 | – | 2.9 | – | 1.3 | -100.0 | -9.2 | yes, recommended |
| Perimeter core 3 m + Single zone building | 1 | 0.00 | – | -1.4 | – | 2.9 | – | 1.4 | -100.0 | -9.3 | yes, recommended |
| Perimeter core 4.57 m + Single zone building | 1 | 0.00 | – | -1.4 | – | 2.9 | – | 1.4 | -100.0 | -9.3 | yes, recommended |
| Perimeter core 3 m + Stack | 5 | 0.00 | – | 0.0 | – | 1.9 | – | -0.0 | 90.2 | -7.5 | yes |
| Perimeter core 4.57 m + Stack | 5 | 0.00 | – | -0.0 | – | 1.8 | – | 0.0 | 24.6 | -8.0 | yes |
17 zonings write the same model as a listed one and are not shown
- Conditioned merge + Single zone per floor type → Conditioned merge + Single zone building
- Conditioned merge + Stack → Conditioned merge + Single zone building
- Conditioned merge + Stacked floor zone multiplier → Conditioned merge + Single zone building
- No simplification + Single zone per floor type → No simplification + Single zone building
- No simplification + Stacked floor zone multiplier → 32ef8882e9af8a21/R
- Perimeter core 3 m + Single zone per floor type → Perimeter core 3 m + Single zone building
- Perimeter core 3 m + Stacked floor zone multiplier → Perimeter core 3 m + Stack
- Perimeter core 4.57 m + Single zone per floor type → Perimeter core 4.57 m + Single zone building
- Perimeter core 4.57 m + Stacked floor zone multiplier → Perimeter core 4.57 m + Stack
- Semantic merge + Single zone building → No simplification + Single zone building
- Semantic merge + Single zone per floor type → No simplification + Single zone building
- Semantic merge + Stack → 32ef8882e9af8a21/R
- Semantic merge + Stacked floor zone multiplier → 32ef8882e9af8a21/R
- Single zone per floor + Single zone building → Conditioned merge + Single zone building
- Single zone per floor + Single zone per floor type → Conditioned merge + Single zone building
- Single zone per floor + Stack → Conditioned merge + Single zone building
- Single zone per floor + Stacked floor zone multiplier → Conditioned merge + Single zone building
2A · 90.1-2019 · 45°
Reference 72df8786efc653b9/R: No simplification + Stack, 6 zones, 4,181 m² conditioned; annual sensible heating 0.0 and cooling 114.7 kWh/m²; peak heating 2.8 and cooling 154.6 kW. Sensible heating is below 1 kWh/m² and is not judged. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Single zone building | 1 | 0.00 | – | -1.5 | – | 3.3 | – | 1.5 | -100.0 | -10.1 | yes, recommended |
| No simplification + Single zone building | 1 | 0.00 | – | -1.5 | – | 3.2 | – | 1.5 | -100.0 | -10.1 | yes, recommended |
| Perimeter core 3 m + Single zone building | 1 | 0.00 | – | -1.5 | – | 3.3 | – | 1.5 | -100.0 | -10.1 | yes, recommended |
| Perimeter core 4.57 m + Single zone building | 1 | 0.00 | – | -1.5 | – | 3.3 | – | 1.5 | -100.0 | -10.1 | yes, recommended |
| Perimeter core 3 m + Stack | 5 | 0.00 | – | 0.1 | – | 2.0 | – | -0.1 | 20.2 | -7.2 | yes |
| Perimeter core 4.57 m + Stack | 5 | 0.00 | – | 0.0 | – | 1.9 | – | -0.0 | 5.2 | -7.8 | yes |
17 zonings write the same model as a listed one and are not shown
- Conditioned merge + Single zone per floor type → Conditioned merge + Single zone building
- Conditioned merge + Stack → Conditioned merge + Single zone building
- Conditioned merge + Stacked floor zone multiplier → Conditioned merge + Single zone building
- No simplification + Single zone per floor type → No simplification + Single zone building
- No simplification + Stacked floor zone multiplier → 72df8786efc653b9/R
- Perimeter core 3 m + Single zone per floor type → Perimeter core 3 m + Single zone building
- Perimeter core 3 m + Stacked floor zone multiplier → Perimeter core 3 m + Stack
- Perimeter core 4.57 m + Single zone per floor type → Perimeter core 4.57 m + Single zone building
- Perimeter core 4.57 m + Stacked floor zone multiplier → Perimeter core 4.57 m + Stack
- Semantic merge + Single zone building → No simplification + Single zone building
- Semantic merge + Single zone per floor type → No simplification + Single zone building
- Semantic merge + Stack → 72df8786efc653b9/R
- Semantic merge + Stacked floor zone multiplier → 72df8786efc653b9/R
- Single zone per floor + Single zone building → Conditioned merge + Single zone building
- Single zone per floor + Single zone per floor type → Conditioned merge + Single zone building
- Single zone per floor + Stack → Conditioned merge + Single zone building
- Single zone per floor + Stacked floor zone multiplier → Conditioned merge + Single zone building
2B · 90.1-2007 · 0°
Reference a1f0c7296ac6ea86/R: No simplification + Stack, 6 zones, 4,181 m² conditioned; annual sensible heating 0.0 and cooling 138.5 kWh/m²; peak heating 8.4 and cooling 199.5 kW. Sensible heating is below 1 kWh/m² and is not judged. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Single zone building | 1 | 0.00 | – | -1.5 | – | 2.8 | – | 1.5 | -100.0 | -0.7 | yes, recommended |
| Perimeter core 3 m + Stack | 5 | 0.00 | – | 0.8 | – | 2.7 | – | -0.8 | 87.4 | -0.0 | yes |
| Perimeter core 4.57 m + Stack | 5 | 0.00 | – | 0.6 | – | 2.3 | – | -0.6 | 63.3 | 0.1 | yes |
20 zonings write the same model as a listed one and are not shown
- Conditioned merge + Single zone per floor type → Conditioned merge + Single zone building
- Conditioned merge + Stack → Conditioned merge + Single zone building
- Conditioned merge + Stacked floor zone multiplier → Conditioned merge + Single zone building
- No simplification + Single zone building → Conditioned merge + Single zone building
- No simplification + Single zone per floor type → Conditioned merge + Single zone building
- No simplification + Stacked floor zone multiplier → a1f0c7296ac6ea86/R
- Perimeter core 3 m + Single zone building → Conditioned merge + Single zone building
- Perimeter core 3 m + Single zone per floor type → Conditioned merge + Single zone building
- Perimeter core 3 m + Stacked floor zone multiplier → Perimeter core 3 m + Stack
- Perimeter core 4.57 m + Single zone building → Conditioned merge + Single zone building
- Perimeter core 4.57 m + Single zone per floor type → Conditioned merge + Single zone building
- Perimeter core 4.57 m + Stacked floor zone multiplier → Perimeter core 4.57 m + Stack
- Semantic merge + Single zone building → Conditioned merge + Single zone building
- Semantic merge + Single zone per floor type → Conditioned merge + Single zone building
- Semantic merge + Stack → a1f0c7296ac6ea86/R
- Semantic merge + Stacked floor zone multiplier → a1f0c7296ac6ea86/R
- Single zone per floor + Single zone building → Conditioned merge + Single zone building
- Single zone per floor + Single zone per floor type → Conditioned merge + Single zone building
- Single zone per floor + Stack → Conditioned merge + Single zone building
- Single zone per floor + Stacked floor zone multiplier → Conditioned merge + Single zone building
2B · 90.1-2007 · 45°
Reference 949bbe28220bf3ce/R: No simplification + Stack, 6 zones, 4,181 m² conditioned; annual sensible heating 0.0 and cooling 134.1 kWh/m²; peak heating 5.8 and cooling 202.5 kW. Sensible heating is below 1 kWh/m² and is not judged. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Single zone building | 1 | 0.00 | – | -1.7 | – | 3.5 | – | 1.7 | -100.0 | -1.0 | yes, recommended |
| Perimeter core 3 m + Stack | 5 | 0.00 | – | 0.3 | – | 2.3 | – | -0.3 | -8.6 | 0.6 | yes |
| Perimeter core 4.57 m + Stack | 5 | 0.00 | – | 0.1 | – | 2.0 | – | -0.1 | -11.7 | 0.2 | yes |
20 zonings write the same model as a listed one and are not shown
- Conditioned merge + Single zone per floor type → Conditioned merge + Single zone building
- Conditioned merge + Stack → Conditioned merge + Single zone building
- Conditioned merge + Stacked floor zone multiplier → Conditioned merge + Single zone building
- No simplification + Single zone building → Conditioned merge + Single zone building
- No simplification + Single zone per floor type → Conditioned merge + Single zone building
- No simplification + Stacked floor zone multiplier → 949bbe28220bf3ce/R
- Perimeter core 3 m + Single zone building → Conditioned merge + Single zone building
- Perimeter core 3 m + Single zone per floor type → Conditioned merge + Single zone building
- Perimeter core 3 m + Stacked floor zone multiplier → Perimeter core 3 m + Stack
- Perimeter core 4.57 m + Single zone building → Conditioned merge + Single zone building
- Perimeter core 4.57 m + Single zone per floor type → Conditioned merge + Single zone building
- Perimeter core 4.57 m + Stacked floor zone multiplier → Perimeter core 4.57 m + Stack
- Semantic merge + Single zone building → Conditioned merge + Single zone building
- Semantic merge + Single zone per floor type → Conditioned merge + Single zone building
- Semantic merge + Stack → 949bbe28220bf3ce/R
- Semantic merge + Stacked floor zone multiplier → 949bbe28220bf3ce/R
- Single zone per floor + Single zone building → Conditioned merge + Single zone building
- Single zone per floor + Single zone per floor type → Conditioned merge + Single zone building
- Single zone per floor + Stack → Conditioned merge + Single zone building
- Single zone per floor + Stacked floor zone multiplier → Conditioned merge + Single zone building
2B · 90.1-2019 · 0°
Reference eac873a284ed8443/R: No simplification + Stack, 6 zones, 4,181 m² conditioned; annual sensible heating 0.1 and cooling 112.1 kWh/m²; peak heating 12.7 and cooling 169.5 kW. Sensible heating is below 1 kWh/m² and is not judged. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Single zone building | 1 | 0.00 | -100.0 | -2.1 | 841.4 | 4.2 | 100.0 | 2.1 | -100.0 | -1.4 | yes, recommended |
| No simplification + Single zone building | 1 | 0.00 | -100.0 | -2.0 | 841.4 | 4.2 | 100.0 | 2.0 | -100.0 | -1.5 | yes, recommended |
| Perimeter core 3 m + Single zone building | 1 | 0.00 | -100.0 | -2.1 | 841.4 | 4.2 | 100.0 | 2.1 | -100.0 | -1.5 | yes, recommended |
| Perimeter core 4.57 m + Single zone building | 1 | 0.00 | -100.0 | -2.1 | 841.4 | 4.2 | 100.0 | 2.1 | -100.0 | -1.5 | yes, recommended |
| Perimeter core 3 m + Stack | 5 | 0.00 | -13.7 | -0.1 | 350.8 | 2.6 | 13.7 | 0.1 | 23.6 | -7.6 | yes |
| Perimeter core 4.57 m + Stack | 5 | 0.00 | -26.9 | -0.1 | 290.9 | 2.3 | 26.9 | 0.1 | 17.6 | -8.0 | yes |
17 zonings write the same model as a listed one and are not shown
- Conditioned merge + Single zone per floor type → Conditioned merge + Single zone building
- Conditioned merge + Stack → Conditioned merge + Single zone building
- Conditioned merge + Stacked floor zone multiplier → Conditioned merge + Single zone building
- No simplification + Single zone per floor type → No simplification + Single zone building
- No simplification + Stacked floor zone multiplier → eac873a284ed8443/R
- Perimeter core 3 m + Single zone per floor type → Perimeter core 3 m + Single zone building
- Perimeter core 3 m + Stacked floor zone multiplier → Perimeter core 3 m + Stack
- Perimeter core 4.57 m + Single zone per floor type → Perimeter core 4.57 m + Single zone building
- Perimeter core 4.57 m + Stacked floor zone multiplier → Perimeter core 4.57 m + Stack
- Semantic merge + Single zone building → No simplification + Single zone building
- Semantic merge + Single zone per floor type → No simplification + Single zone building
- Semantic merge + Stack → eac873a284ed8443/R
- Semantic merge + Stacked floor zone multiplier → eac873a284ed8443/R
- Single zone per floor + Single zone building → Conditioned merge + Single zone building
- Single zone per floor + Single zone per floor type → Conditioned merge + Single zone building
- Single zone per floor + Stack → Conditioned merge + Single zone building
- Single zone per floor + Stacked floor zone multiplier → Conditioned merge + Single zone building
2B · 90.1-2019 · 45°
Reference 8ef78755f5874573/R: No simplification + Stack, 6 zones, 4,181 m² conditioned; annual sensible heating 0.1 and cooling 106.1 kWh/m²; peak heating 12.1 and cooling 172.3 kW. Sensible heating is below 1 kWh/m² and is not judged. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Single zone building | 1 | 0.00 | -100.0 | -2.2 | 901.6 | 4.6 | 100.0 | 2.2 | -100.0 | -1.4 | yes, recommended |
| No simplification + Single zone building | 1 | 0.00 | -100.0 | -2.2 | 901.6 | 4.6 | 100.0 | 2.2 | -100.0 | -1.4 | yes, recommended |
| Perimeter core 3 m + Single zone building | 1 | 0.00 | -100.0 | -2.2 | 901.6 | 4.6 | 100.0 | 2.2 | -100.0 | -1.4 | yes, recommended |
| Perimeter core 4.57 m + Single zone building | 1 | 0.00 | -100.0 | -2.2 | 901.6 | 4.6 | 100.0 | 2.2 | -100.0 | -1.4 | yes, recommended |
| Perimeter core 3 m + Stack | 5 | 0.00 | -16.5 | 0.1 | 262.1 | 2.6 | 16.5 | -0.1 | -19.8 | -6.9 | yes |
| Perimeter core 4.57 m + Stack | 5 | 0.00 | -27.4 | -0.0 | 246.8 | 2.4 | 27.4 | 0.0 | -24.2 | -7.3 | yes |
17 zonings write the same model as a listed one and are not shown
- Conditioned merge + Single zone per floor type → Conditioned merge + Single zone building
- Conditioned merge + Stack → Conditioned merge + Single zone building
- Conditioned merge + Stacked floor zone multiplier → Conditioned merge + Single zone building
- No simplification + Single zone per floor type → No simplification + Single zone building
- No simplification + Stacked floor zone multiplier → 8ef78755f5874573/R
- Perimeter core 3 m + Single zone per floor type → Perimeter core 3 m + Single zone building
- Perimeter core 3 m + Stacked floor zone multiplier → Perimeter core 3 m + Stack
- Perimeter core 4.57 m + Single zone per floor type → Perimeter core 4.57 m + Single zone building
- Perimeter core 4.57 m + Stacked floor zone multiplier → Perimeter core 4.57 m + Stack
- Semantic merge + Single zone building → No simplification + Single zone building
- Semantic merge + Single zone per floor type → No simplification + Single zone building
- Semantic merge + Stack → 8ef78755f5874573/R
- Semantic merge + Stacked floor zone multiplier → 8ef78755f5874573/R
- Single zone per floor + Single zone building → Conditioned merge + Single zone building
- Single zone per floor + Single zone per floor type → Conditioned merge + Single zone building
- Single zone per floor + Stack → Conditioned merge + Single zone building
- Single zone per floor + Stacked floor zone multiplier → Conditioned merge + Single zone building
3C · 90.1-2007 · 0°
Reference b4a5ed58e89acb03/R: No simplification + Stack, 6 zones, 4,181 m² conditioned; annual sensible heating 0.0 and cooling 89.2 kWh/m²; peak heating 0.8 and cooling 119.3 kW. Sensible heating is below 1 kWh/m² and is not judged. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Single zone building | 1 | 0.00 | – | -2.4 | – | 4.6 | – | 2.4 | -100.0 | -0.8 | yes, recommended |
| Perimeter core 3 m + Stack | 5 | 0.00 | – | 2.8 | – | 4.4 | – | -2.8 | 344.9 | 1.7 | yes |
| Perimeter core 4.57 m + Stack | 5 | 0.00 | – | 2.0 | – | 3.6 | – | -2.0 | 87.8 | 1.3 | yes |
20 zonings write the same model as a listed one and are not shown
- Conditioned merge + Single zone per floor type → Conditioned merge + Single zone building
- Conditioned merge + Stack → Conditioned merge + Single zone building
- Conditioned merge + Stacked floor zone multiplier → Conditioned merge + Single zone building
- No simplification + Single zone building → Conditioned merge + Single zone building
- No simplification + Single zone per floor type → Conditioned merge + Single zone building
- No simplification + Stacked floor zone multiplier → b4a5ed58e89acb03/R
- Perimeter core 3 m + Single zone building → Conditioned merge + Single zone building
- Perimeter core 3 m + Single zone per floor type → Conditioned merge + Single zone building
- Perimeter core 3 m + Stacked floor zone multiplier → Perimeter core 3 m + Stack
- Perimeter core 4.57 m + Single zone building → Conditioned merge + Single zone building
- Perimeter core 4.57 m + Single zone per floor type → Conditioned merge + Single zone building
- Perimeter core 4.57 m + Stacked floor zone multiplier → Perimeter core 4.57 m + Stack
- Semantic merge + Single zone building → Conditioned merge + Single zone building
- Semantic merge + Single zone per floor type → Conditioned merge + Single zone building
- Semantic merge + Stack → b4a5ed58e89acb03/R
- Semantic merge + Stacked floor zone multiplier → b4a5ed58e89acb03/R
- Single zone per floor + Single zone building → Conditioned merge + Single zone building
- Single zone per floor + Single zone per floor type → Conditioned merge + Single zone building
- Single zone per floor + Stack → Conditioned merge + Single zone building
- Single zone per floor + Stacked floor zone multiplier → Conditioned merge + Single zone building
3C · 90.1-2007 · 45°
Reference 94870e41d6c8e503/R: No simplification + Stack, 6 zones, 4,181 m² conditioned; annual sensible heating 0.0 and cooling 89.9 kWh/m²; peak heating 0.6 and cooling 114.4 kW. Sensible heating is below 1 kWh/m² and is not judged. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Single zone building | 1 | 0.00 | – | -2.7 | – | 5.0 | – | 2.7 | -100.0 | -1.1 | yes, recommended |
| Perimeter core 3 m + Stack | 5 | 0.00 | – | 1.3 | – | 2.0 | – | -1.3 | -17.7 | 0.5 | yes |
| Perimeter core 4.57 m + Stack | 5 | 0.00 | – | 0.8 | – | 1.3 | – | -0.8 | -69.0 | 0.4 | yes |
| Semantic merge + Stack | 6 | 0.00 | – | -0.0 | – | 0.0 | – | 0.0 | -0.0 | -0.0 | yes |
19 zonings write the same model as a listed one and are not shown
- Conditioned merge + Single zone per floor type → Conditioned merge + Single zone building
- Conditioned merge + Stack → Conditioned merge + Single zone building
- Conditioned merge + Stacked floor zone multiplier → Conditioned merge + Single zone building
- No simplification + Single zone building → Conditioned merge + Single zone building
- No simplification + Single zone per floor type → Conditioned merge + Single zone building
- No simplification + Stacked floor zone multiplier → 94870e41d6c8e503/R
- Perimeter core 3 m + Single zone building → Conditioned merge + Single zone building
- Perimeter core 3 m + Single zone per floor type → Conditioned merge + Single zone building
- Perimeter core 3 m + Stacked floor zone multiplier → Perimeter core 3 m + Stack
- Perimeter core 4.57 m + Single zone building → Conditioned merge + Single zone building
- Perimeter core 4.57 m + Single zone per floor type → Conditioned merge + Single zone building
- Perimeter core 4.57 m + Stacked floor zone multiplier → Perimeter core 4.57 m + Stack
- Semantic merge + Single zone building → Conditioned merge + Single zone building
- Semantic merge + Single zone per floor type → Conditioned merge + Single zone building
- Semantic merge + Stacked floor zone multiplier → Semantic merge + Stack
- Single zone per floor + Single zone building → Conditioned merge + Single zone building
- Single zone per floor + Single zone per floor type → Conditioned merge + Single zone building
- Single zone per floor + Stack → Conditioned merge + Single zone building
- Single zone per floor + Stacked floor zone multiplier → Conditioned merge + Single zone building
3C · 90.1-2019 · 0°
Reference 1af77aa7a44f8aec/R: No simplification + Stack, 6 zones, 4,181 m² conditioned; annual sensible heating 0.1 and cooling 67.0 kWh/m²; peak heating 6.3 and cooling 99.9 kW. Sensible heating is below 1 kWh/m² and is not judged. Serial cost (R5): processor time 3.0 s, wall clock 3.1 s, peak committed memory 190 MiB, each the median of 3 repeats (processor-time CV 2.7 %); a zoning's ratios are its own medians over the reference's.
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | CPU ratio | Wall ratio | Memory ratio | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Single zone building | 1 | 0.00 | – | -4.3 | – | 7.4 | – | 4.3 | -100.0 | -1.2 | 0.298 | 0.300 | 0.978 | yes, recommended |
| No simplification + Single zone building | 1 | 0.00 | – | -4.3 | – | 7.4 | – | 4.3 | -100.0 | -1.0 | 0.597 | 0.602 | 0.983 | yes, recommended |
| Perimeter core 3 m + Single zone building | 1 | 0.00 | – | -4.3 | – | 7.4 | – | 4.3 | -100.0 | -1.1 | 0.335 | 0.333 | 0.975 | yes, recommended |
| Perimeter core 4.57 m + Single zone building | 1 | 0.00 | – | -4.3 | – | 7.4 | – | 4.3 | -100.0 | -1.1 | 0.335 | 0.332 | 0.975 | yes, recommended |
| Perimeter core 3 m + Stack | 5 | 0.00 | – | 1.4 | – | 3.1 | – | -1.4 | -37.3 | 1.4 | 0.634 | 0.621 | 0.989 | yes |
| Perimeter core 4.57 m + Stack | 5 | 0.00 | – | 0.9 | – | 2.4 | – | -0.9 | -59.9 | 1.1 | 0.639 | 0.622 | 0.992 | yes |
17 zonings write the same model as a listed one and are not shown
- Conditioned merge + Single zone per floor type → Conditioned merge + Single zone building
- Conditioned merge + Stack → Conditioned merge + Single zone building
- Conditioned merge + Stacked floor zone multiplier → Conditioned merge + Single zone building
- No simplification + Single zone per floor type → No simplification + Single zone building
- No simplification + Stacked floor zone multiplier → 1af77aa7a44f8aec/R
- Perimeter core 3 m + Single zone per floor type → Perimeter core 3 m + Single zone building
- Perimeter core 3 m + Stacked floor zone multiplier → Perimeter core 3 m + Stack
- Perimeter core 4.57 m + Single zone per floor type → Perimeter core 4.57 m + Single zone building
- Perimeter core 4.57 m + Stacked floor zone multiplier → Perimeter core 4.57 m + Stack
- Semantic merge + Single zone building → No simplification + Single zone building
- Semantic merge + Single zone per floor type → No simplification + Single zone building
- Semantic merge + Stack → 1af77aa7a44f8aec/R
- Semantic merge + Stacked floor zone multiplier → 1af77aa7a44f8aec/R
- Single zone per floor + Single zone building → Conditioned merge + Single zone building
- Single zone per floor + Single zone per floor type → Conditioned merge + Single zone building
- Single zone per floor + Stack → Conditioned merge + Single zone building
- Single zone per floor + Stacked floor zone multiplier → Conditioned merge + Single zone building
3C · 90.1-2019 · 45°
Reference fffe810829266b95/R: No simplification + Stack, 6 zones, 4,181 m² conditioned; annual sensible heating 0.1 and cooling 64.0 kWh/m²; peak heating 6.2 and cooling 94.5 kW. Sensible heating is below 1 kWh/m² and is not judged. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Single zone building | 1 | 0.00 | – | -4.6 | – | 8.2 | – | 4.6 | -100.0 | -1.1 | yes, recommended |
| No simplification + Single zone building | 1 | 0.00 | – | -4.6 | – | 8.2 | – | 4.6 | -100.0 | -1.0 | yes, recommended |
| Perimeter core 3 m + Single zone building | 1 | 0.00 | – | -4.6 | – | 8.2 | – | 4.6 | -100.0 | -1.1 | yes, recommended |
| Perimeter core 4.57 m + Single zone building | 1 | 0.00 | – | -4.6 | – | 8.2 | – | 4.6 | -100.0 | -1.0 | yes, recommended |
| Perimeter core 3 m + Stack | 5 | 0.00 | – | 1.1 | – | 2.7 | – | -1.1 | -53.2 | 0.6 | yes |
| Perimeter core 4.57 m + Stack | 5 | 0.00 | – | 0.6 | – | 1.9 | – | -0.6 | -50.7 | 0.4 | yes |
| Semantic merge + Stack | 6 | 0.00 | – | -0.0 | – | 0.0 | – | 0.0 | -0.0 | -0.0 | yes |
16 zonings write the same model as a listed one and are not shown
- Conditioned merge + Single zone per floor type → Conditioned merge + Single zone building
- Conditioned merge + Stack → Conditioned merge + Single zone building
- Conditioned merge + Stacked floor zone multiplier → Conditioned merge + Single zone building
- No simplification + Single zone per floor type → No simplification + Single zone building
- No simplification + Stacked floor zone multiplier → fffe810829266b95/R
- Perimeter core 3 m + Single zone per floor type → Perimeter core 3 m + Single zone building
- Perimeter core 3 m + Stacked floor zone multiplier → Perimeter core 3 m + Stack
- Perimeter core 4.57 m + Single zone per floor type → Perimeter core 4.57 m + Single zone building
- Perimeter core 4.57 m + Stacked floor zone multiplier → Perimeter core 4.57 m + Stack
- Semantic merge + Single zone building → No simplification + Single zone building
- Semantic merge + Single zone per floor type → No simplification + Single zone building
- Semantic merge + Stacked floor zone multiplier → Semantic merge + Stack
- Single zone per floor + Single zone building → Conditioned merge + Single zone building
- Single zone per floor + Single zone per floor type → Conditioned merge + Single zone building
- Single zone per floor + Stack → Conditioned merge + Single zone building
- Single zone per floor + Stacked floor zone multiplier → Conditioned merge + Single zone building
4A · 90.1-2007 · 0°
Reference b7bba2b72d0a926b/R: No simplification + Stack, 6 zones, 4,181 m² conditioned; annual sensible heating 3.9 and cooling 82.5 kWh/m²; peak heating 106.5 and cooling 165.1 kW. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Single zone building | 1 | 0.00 | -69.7 | -6.6 | 208.1 | 14.1 | 69.7 | 6.6 | 22.8 | -1.7 | no |
| Perimeter core 3 m + Stack | 5 | 0.00 | -19.9 | -0.3 | 74.0 | 4.9 | 19.9 | 0.3 | -3.5 | -0.4 | no |
| Perimeter core 4.57 m + Stack | 5 | 0.00 | -16.2 | -0.2 | 59.4 | 4.1 | 16.2 | 0.2 | -1.5 | 0.0 | no |
20 zonings write the same model as a listed one and are not shown
- Conditioned merge + Single zone per floor type → Conditioned merge + Single zone building
- Conditioned merge + Stack → Conditioned merge + Single zone building
- Conditioned merge + Stacked floor zone multiplier → Conditioned merge + Single zone building
- No simplification + Single zone building → Conditioned merge + Single zone building
- No simplification + Single zone per floor type → Conditioned merge + Single zone building
- No simplification + Stacked floor zone multiplier → b7bba2b72d0a926b/R
- Perimeter core 3 m + Single zone building → Conditioned merge + Single zone building
- Perimeter core 3 m + Single zone per floor type → Conditioned merge + Single zone building
- Perimeter core 3 m + Stacked floor zone multiplier → Perimeter core 3 m + Stack
- Perimeter core 4.57 m + Single zone building → Conditioned merge + Single zone building
- Perimeter core 4.57 m + Single zone per floor type → Conditioned merge + Single zone building
- Perimeter core 4.57 m + Stacked floor zone multiplier → Perimeter core 4.57 m + Stack
- Semantic merge + Single zone building → Conditioned merge + Single zone building
- Semantic merge + Single zone per floor type → Conditioned merge + Single zone building
- Semantic merge + Stack → b7bba2b72d0a926b/R
- Semantic merge + Stacked floor zone multiplier → b7bba2b72d0a926b/R
- Single zone per floor + Single zone building → Conditioned merge + Single zone building
- Single zone per floor + Single zone per floor type → Conditioned merge + Single zone building
- Single zone per floor + Stack → Conditioned merge + Single zone building
- Single zone per floor + Stacked floor zone multiplier → Conditioned merge + Single zone building
4A · 90.1-2007 · 45°
Reference a89dcb099594ab07/R: No simplification + Stack, 6 zones, 4,181 m² conditioned; annual sensible heating 3.7 and cooling 78.0 kWh/m²; peak heating 82.3 and cooling 161.8 kW. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Single zone building | 1 | 0.00 | -70.8 | -7.4 | 211.8 | 14.9 | 70.8 | 7.4 | 39.4 | -9.4 | no |
| Perimeter core 3 m + Stack | 5 | 0.00 | -30.7 | -1.3 | 91.9 | 5.3 | 30.7 | 1.3 | 6.9 | -6.8 | no |
| Perimeter core 4.57 m + Stack | 5 | 0.00 | -24.9 | -1.2 | 63.1 | 4.0 | 24.9 | 1.2 | 9.4 | 0.9 | no |
20 zonings write the same model as a listed one and are not shown
- Conditioned merge + Single zone per floor type → Conditioned merge + Single zone building
- Conditioned merge + Stack → Conditioned merge + Single zone building
- Conditioned merge + Stacked floor zone multiplier → Conditioned merge + Single zone building
- No simplification + Single zone building → Conditioned merge + Single zone building
- No simplification + Single zone per floor type → Conditioned merge + Single zone building
- No simplification + Stacked floor zone multiplier → a89dcb099594ab07/R
- Perimeter core 3 m + Single zone building → Conditioned merge + Single zone building
- Perimeter core 3 m + Single zone per floor type → Conditioned merge + Single zone building
- Perimeter core 3 m + Stacked floor zone multiplier → Perimeter core 3 m + Stack
- Perimeter core 4.57 m + Single zone building → Conditioned merge + Single zone building
- Perimeter core 4.57 m + Single zone per floor type → Conditioned merge + Single zone building
- Perimeter core 4.57 m + Stacked floor zone multiplier → Perimeter core 4.57 m + Stack
- Semantic merge + Single zone building → Conditioned merge + Single zone building
- Semantic merge + Single zone per floor type → Conditioned merge + Single zone building
- Semantic merge + Stack → a89dcb099594ab07/R
- Semantic merge + Stacked floor zone multiplier → a89dcb099594ab07/R
- Single zone per floor + Single zone building → Conditioned merge + Single zone building
- Single zone per floor + Single zone per floor type → Conditioned merge + Single zone building
- Single zone per floor + Stack → Conditioned merge + Single zone building
- Single zone per floor + Stacked floor zone multiplier → Conditioned merge + Single zone building
4A · 90.1-2019 · 0°
Reference 9ed380b22d4b179b/R: No simplification + Stack, 6 zones, 4,181 m² conditioned; annual sensible heating 5.2 and cooling 65.3 kWh/m²; peak heating 115.6 and cooling 140.1 kW. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Single zone building | 1 | 0.00 | -61.2 | -7.6 | 173.7 | 17.3 | 61.2 | 7.6 | 16.4 | -0.9 | no |
| No simplification + Single zone building | 1 | 0.00 | -61.2 | -7.5 | 173.7 | 17.3 | 61.2 | 7.5 | 16.4 | -0.8 | no |
| Perimeter core 3 m + Single zone building | 1 | 0.00 | -61.2 | -7.6 | 173.7 | 17.3 | 61.2 | 7.6 | 16.5 | -0.9 | no |
| Perimeter core 4.57 m + Single zone building | 1 | 0.00 | -61.2 | -7.6 | 173.8 | 17.3 | 61.2 | 7.6 | 16.5 | -0.9 | no |
| Perimeter core 3 m + Stack | 5 | 0.00 | -26.2 | -2.6 | 78.2 | 7.6 | 26.2 | 2.6 | 7.1 | 0.4 | no |
| Perimeter core 4.57 m + Stack | 5 | 0.00 | -21.8 | -2.2 | 60.5 | 6.4 | 21.8 | 2.2 | 4.6 | 0.2 | no |
17 zonings write the same model as a listed one and are not shown
- Conditioned merge + Single zone per floor type → Conditioned merge + Single zone building
- Conditioned merge + Stack → Conditioned merge + Single zone building
- Conditioned merge + Stacked floor zone multiplier → Conditioned merge + Single zone building
- No simplification + Single zone per floor type → No simplification + Single zone building
- No simplification + Stacked floor zone multiplier → 9ed380b22d4b179b/R
- Perimeter core 3 m + Single zone per floor type → Perimeter core 3 m + Single zone building
- Perimeter core 3 m + Stacked floor zone multiplier → Perimeter core 3 m + Stack
- Perimeter core 4.57 m + Single zone per floor type → Perimeter core 4.57 m + Single zone building
- Perimeter core 4.57 m + Stacked floor zone multiplier → Perimeter core 4.57 m + Stack
- Semantic merge + Single zone building → No simplification + Single zone building
- Semantic merge + Single zone per floor type → No simplification + Single zone building
- Semantic merge + Stack → 9ed380b22d4b179b/R
- Semantic merge + Stacked floor zone multiplier → 9ed380b22d4b179b/R
- Single zone per floor + Single zone building → Conditioned merge + Single zone building
- Single zone per floor + Single zone per floor type → Conditioned merge + Single zone building
- Single zone per floor + Stack → Conditioned merge + Single zone building
- Single zone per floor + Stacked floor zone multiplier → Conditioned merge + Single zone building
4A · 90.1-2019 · 45°
Reference f08276db4dc01604/R: No simplification + Stack, 6 zones, 4,181 m² conditioned; annual sensible heating 5.4 and cooling 58.9 kWh/m²; peak heating 112.7 and cooling 136.2 kW. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Single zone building | 1 | 0.00 | -54.3 | -7.3 | 155.1 | 16.3 | 54.3 | 7.3 | 13.6 | -9.6 | no |
| No simplification + Single zone building | 1 | 0.00 | -54.3 | -7.3 | 155.1 | 16.3 | 54.3 | 7.3 | 13.6 | -9.5 | no |
| Perimeter core 3 m + Single zone building | 1 | 0.00 | -54.3 | -7.3 | 155.0 | 16.3 | 54.3 | 7.3 | 13.7 | -9.6 | no |
| Perimeter core 4.57 m + Single zone building | 1 | 0.00 | -54.3 | -7.3 | 155.0 | 16.3 | 54.3 | 7.3 | 13.7 | -9.5 | no |
| Perimeter core 3 m + Stack | 5 | 0.00 | -25.9 | -2.3 | 72.6 | 7.1 | 25.9 | 2.3 | 4.1 | -8.7 | no |
| Perimeter core 4.57 m + Stack | 5 | 0.00 | -20.9 | -2.0 | 53.7 | 5.5 | 20.9 | 2.0 | 1.6 | -8.7 | no |
17 zonings write the same model as a listed one and are not shown
- Conditioned merge + Single zone per floor type → Conditioned merge + Single zone building
- Conditioned merge + Stack → Conditioned merge + Single zone building
- Conditioned merge + Stacked floor zone multiplier → Conditioned merge + Single zone building
- No simplification + Single zone per floor type → No simplification + Single zone building
- No simplification + Stacked floor zone multiplier → f08276db4dc01604/R
- Perimeter core 3 m + Single zone per floor type → Perimeter core 3 m + Single zone building
- Perimeter core 3 m + Stacked floor zone multiplier → Perimeter core 3 m + Stack
- Perimeter core 4.57 m + Single zone per floor type → Perimeter core 4.57 m + Single zone building
- Perimeter core 4.57 m + Stacked floor zone multiplier → Perimeter core 4.57 m + Stack
- Semantic merge + Single zone building → No simplification + Single zone building
- Semantic merge + Single zone per floor type → No simplification + Single zone building
- Semantic merge + Stack → f08276db4dc01604/R
- Semantic merge + Stacked floor zone multiplier → f08276db4dc01604/R
- Single zone per floor + Single zone building → Conditioned merge + Single zone building
- Single zone per floor + Single zone per floor type → Conditioned merge + Single zone building
- Single zone per floor + Stack → Conditioned merge + Single zone building
- Single zone per floor + Stacked floor zone multiplier → Conditioned merge + Single zone building
5A · 90.1-2007 · 0°
Reference f1842e677d088a42/R: No simplification + Stack, 6 zones, 4,181 m² conditioned; annual sensible heating 9.8 and cooling 61.7 kWh/m²; peak heating 186.4 and cooling 151.5 kW. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Single zone building | 1 | 0.00 | -27.4 | -5.8 | 91.1 | 13.9 | 27.4 | 5.8 | 3.6 | -0.6 | no |
| Perimeter core 3 m + Stack | 5 | 0.00 | -10.0 | 0.1 | 43.9 | 5.6 | 10.0 | -0.1 | -7.3 | 0.8 | no |
| Perimeter core 4.57 m + Stack | 5 | 0.00 | -7.5 | 0.2 | 36.6 | 4.6 | 7.5 | -0.2 | -6.8 | 0.5 | no |
20 zonings write the same model as a listed one and are not shown
- Conditioned merge + Single zone per floor type → Conditioned merge + Single zone building
- Conditioned merge + Stack → Conditioned merge + Single zone building
- Conditioned merge + Stacked floor zone multiplier → Conditioned merge + Single zone building
- No simplification + Single zone building → Conditioned merge + Single zone building
- No simplification + Single zone per floor type → Conditioned merge + Single zone building
- No simplification + Stacked floor zone multiplier → f1842e677d088a42/R
- Perimeter core 3 m + Single zone building → Conditioned merge + Single zone building
- Perimeter core 3 m + Single zone per floor type → Conditioned merge + Single zone building
- Perimeter core 3 m + Stacked floor zone multiplier → Perimeter core 3 m + Stack
- Perimeter core 4.57 m + Single zone building → Conditioned merge + Single zone building
- Perimeter core 4.57 m + Single zone per floor type → Conditioned merge + Single zone building
- Perimeter core 4.57 m + Stacked floor zone multiplier → Perimeter core 4.57 m + Stack
- Semantic merge + Single zone building → Conditioned merge + Single zone building
- Semantic merge + Single zone per floor type → Conditioned merge + Single zone building
- Semantic merge + Stack → f1842e677d088a42/R
- Semantic merge + Stacked floor zone multiplier → f1842e677d088a42/R
- Single zone per floor + Single zone building → Conditioned merge + Single zone building
- Single zone per floor + Single zone per floor type → Conditioned merge + Single zone building
- Single zone per floor + Stack → Conditioned merge + Single zone building
- Single zone per floor + Stacked floor zone multiplier → Conditioned merge + Single zone building
5A · 90.1-2007 · 45°
Reference b71831dc9e4a1e71/R: No simplification + Stack, 6 zones, 4,181 m² conditioned; annual sensible heating 8.7 and cooling 59.8 kWh/m²; peak heating 154.8 and cooling 135.8 kW. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Single zone building | 1 | 0.00 | -34.9 | -7.2 | 110.1 | 16.0 | 34.9 | 7.2 | 6.9 | -0.7 | no |
| Perimeter core 3 m + Stack | 5 | 0.00 | -17.9 | -1.9 | 53.9 | 7.5 | 17.9 | 1.9 | 1.9 | 0.1 | no |
| Perimeter core 4.57 m + Stack | 5 | 0.00 | -13.9 | -1.7 | 37.9 | 5.8 | 13.9 | 1.7 | 2.5 | 0.1 | no |
20 zonings write the same model as a listed one and are not shown
- Conditioned merge + Single zone per floor type → Conditioned merge + Single zone building
- Conditioned merge + Stack → Conditioned merge + Single zone building
- Conditioned merge + Stacked floor zone multiplier → Conditioned merge + Single zone building
- No simplification + Single zone building → Conditioned merge + Single zone building
- No simplification + Single zone per floor type → Conditioned merge + Single zone building
- No simplification + Stacked floor zone multiplier → b71831dc9e4a1e71/R
- Perimeter core 3 m + Single zone building → Conditioned merge + Single zone building
- Perimeter core 3 m + Single zone per floor type → Conditioned merge + Single zone building
- Perimeter core 3 m + Stacked floor zone multiplier → Perimeter core 3 m + Stack
- Perimeter core 4.57 m + Single zone building → Conditioned merge + Single zone building
- Perimeter core 4.57 m + Single zone per floor type → Conditioned merge + Single zone building
- Perimeter core 4.57 m + Stacked floor zone multiplier → Perimeter core 4.57 m + Stack
- Semantic merge + Single zone building → Conditioned merge + Single zone building
- Semantic merge + Single zone per floor type → Conditioned merge + Single zone building
- Semantic merge + Stack → b71831dc9e4a1e71/R
- Semantic merge + Stacked floor zone multiplier → b71831dc9e4a1e71/R
- Single zone per floor + Single zone building → Conditioned merge + Single zone building
- Single zone per floor + Single zone per floor type → Conditioned merge + Single zone building
- Single zone per floor + Stack → Conditioned merge + Single zone building
- Single zone per floor + Stacked floor zone multiplier → Conditioned merge + Single zone building
5A · 90.1-2019 · 0°
Reference c854e5d5c56b6862/R: No simplification + Stack, 6 zones, 4,181 m² conditioned; annual sensible heating 11.6 and cooling 48.7 kWh/m²; peak heating 183.6 and cooling 130.9 kW. Serial cost (R5): processor time 3.0 s, wall clock 3.0 s, peak committed memory 190 MiB, each the median of 3 repeats (processor-time CV 2.3 %); a zoning's ratios are its own medians over the reference's.
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | CPU ratio | Wall ratio | Memory ratio | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Single zone building | 1 | 0.00 | -20.8 | -6.6 | 75.1 | 16.7 | 20.8 | 6.6 | 2.4 | -1.0 | 0.297 | 0.329 | 0.973 | no |
| No simplification + Single zone building | 1 | 0.00 | -20.8 | -6.6 | 75.1 | 16.7 | 20.8 | 6.6 | 2.4 | -0.9 | 0.599 | 0.606 | 0.982 | no |
| Perimeter core 3 m + Single zone building | 1 | 0.00 | -20.8 | -6.6 | 75.2 | 16.7 | 20.8 | 6.6 | 2.4 | -1.0 | 0.339 | 0.337 | 0.973 | no |
| Perimeter core 4.57 m + Single zone building | 1 | 0.00 | -20.8 | -6.6 | 75.2 | 16.7 | 20.8 | 6.6 | 2.4 | -0.9 | 0.328 | 0.343 | 0.975 | no |
| Perimeter core 3 m + Stack | 5 | 0.00 | -11.4 | -2.1 | 38.9 | 7.9 | 11.4 | 2.1 | -2.8 | 0.4 | 0.625 | 0.641 | 0.989 | no |
| Perimeter core 4.57 m + Stack | 5 | 0.00 | -9.6 | -1.9 | 30.7 | 6.6 | 9.6 | 1.9 | -2.8 | 0.3 | 0.625 | 0.631 | 0.991 | no |
17 zonings write the same model as a listed one and are not shown
- Conditioned merge + Single zone per floor type → Conditioned merge + Single zone building
- Conditioned merge + Stack → Conditioned merge + Single zone building
- Conditioned merge + Stacked floor zone multiplier → Conditioned merge + Single zone building
- No simplification + Single zone per floor type → No simplification + Single zone building
- No simplification + Stacked floor zone multiplier → c854e5d5c56b6862/R
- Perimeter core 3 m + Single zone per floor type → Perimeter core 3 m + Single zone building
- Perimeter core 3 m + Stacked floor zone multiplier → Perimeter core 3 m + Stack
- Perimeter core 4.57 m + Single zone per floor type → Perimeter core 4.57 m + Single zone building
- Perimeter core 4.57 m + Stacked floor zone multiplier → Perimeter core 4.57 m + Stack
- Semantic merge + Single zone building → No simplification + Single zone building
- Semantic merge + Single zone per floor type → No simplification + Single zone building
- Semantic merge + Stack → c854e5d5c56b6862/R
- Semantic merge + Stacked floor zone multiplier → c854e5d5c56b6862/R
- Single zone per floor + Single zone building → Conditioned merge + Single zone building
- Single zone per floor + Single zone per floor type → Conditioned merge + Single zone building
- Single zone per floor + Stack → Conditioned merge + Single zone building
- Single zone per floor + Stacked floor zone multiplier → Conditioned merge + Single zone building
5A · 90.1-2019 · 45°
Reference 8882d5aa443401f1/R: No simplification + Stack, 6 zones, 4,181 m² conditioned; annual sensible heating 11.3 and cooling 44.3 kWh/m²; peak heating 169.4 and cooling 115.9 kW. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Single zone building | 1 | 0.00 | -18.9 | -7.1 | 73.0 | 17.4 | 18.9 | 7.1 | 2.2 | -1.0 | no |
| No simplification + Single zone building | 1 | 0.00 | -18.9 | -7.1 | 73.0 | 17.3 | 18.9 | 7.1 | 2.2 | -0.9 | no |
| Perimeter core 3 m + Single zone building | 1 | 0.00 | -18.9 | -7.1 | 73.0 | 17.4 | 18.9 | 7.1 | 2.2 | -0.9 | no |
| Perimeter core 4.57 m + Single zone building | 1 | 0.00 | -18.9 | -7.1 | 73.1 | 17.4 | 18.9 | 7.1 | 2.2 | -0.9 | no |
| Perimeter core 3 m + Stack | 5 | 0.00 | -11.0 | -2.3 | 35.5 | 7.7 | 11.0 | 2.3 | 0.3 | -0.3 | no |
| Perimeter core 4.57 m + Stack | 5 | 0.00 | -8.7 | -2.1 | 26.5 | 6.3 | 8.7 | 2.1 | 0.7 | -0.2 | yes, recommended |
17 zonings write the same model as a listed one and are not shown
- Conditioned merge + Single zone per floor type → Conditioned merge + Single zone building
- Conditioned merge + Stack → Conditioned merge + Single zone building
- Conditioned merge + Stacked floor zone multiplier → Conditioned merge + Single zone building
- No simplification + Single zone per floor type → No simplification + Single zone building
- No simplification + Stacked floor zone multiplier → 8882d5aa443401f1/R
- Perimeter core 3 m + Single zone per floor type → Perimeter core 3 m + Single zone building
- Perimeter core 3 m + Stacked floor zone multiplier → Perimeter core 3 m + Stack
- Perimeter core 4.57 m + Single zone per floor type → Perimeter core 4.57 m + Single zone building
- Perimeter core 4.57 m + Stacked floor zone multiplier → Perimeter core 4.57 m + Stack
- Semantic merge + Single zone building → No simplification + Single zone building
- Semantic merge + Single zone per floor type → No simplification + Single zone building
- Semantic merge + Stack → 8882d5aa443401f1/R
- Semantic merge + Stacked floor zone multiplier → 8882d5aa443401f1/R
- Single zone per floor + Single zone building → Conditioned merge + Single zone building
- Single zone per floor + Single zone per floor type → Conditioned merge + Single zone building
- Single zone per floor + Stack → Conditioned merge + Single zone building
- Single zone per floor + Stacked floor zone multiplier → Conditioned merge + Single zone building
7A · 90.1-2007 · 0°
Reference da283a14dd38347d/R: No simplification + Stack, 6 zones, 4,181 m² conditioned; annual sensible heating 25.2 and cooling 54.7 kWh/m²; peak heating 294.8 and cooling 154.6 kW. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Single zone building | 1 | 0.00 | -9.8 | -5.7 | 38.6 | 16.1 | 9.8 | 5.7 | -6.1 | -0.6 | no |
| Perimeter core 3 m + Stack | 5 | 0.00 | -3.6 | -1.6 | 21.7 | 7.5 | 3.6 | 1.6 | -3.9 | 0.6 | yes, recommended |
| Perimeter core 4.57 m + Stack | 5 | 0.00 | -3.2 | -1.4 | 18.4 | 6.3 | 3.2 | 1.4 | -4.8 | 0.4 | yes, recommended |
20 zonings write the same model as a listed one and are not shown
- Conditioned merge + Single zone per floor type → Conditioned merge + Single zone building
- Conditioned merge + Stack → Conditioned merge + Single zone building
- Conditioned merge + Stacked floor zone multiplier → Conditioned merge + Single zone building
- No simplification + Single zone building → Conditioned merge + Single zone building
- No simplification + Single zone per floor type → Conditioned merge + Single zone building
- No simplification + Stacked floor zone multiplier → da283a14dd38347d/R
- Perimeter core 3 m + Single zone building → Conditioned merge + Single zone building
- Perimeter core 3 m + Single zone per floor type → Conditioned merge + Single zone building
- Perimeter core 3 m + Stacked floor zone multiplier → Perimeter core 3 m + Stack
- Perimeter core 4.57 m + Single zone building → Conditioned merge + Single zone building
- Perimeter core 4.57 m + Single zone per floor type → Conditioned merge + Single zone building
- Perimeter core 4.57 m + Stacked floor zone multiplier → Perimeter core 4.57 m + Stack
- Semantic merge + Single zone building → Conditioned merge + Single zone building
- Semantic merge + Single zone per floor type → Conditioned merge + Single zone building
- Semantic merge + Stack → da283a14dd38347d/R
- Semantic merge + Stacked floor zone multiplier → da283a14dd38347d/R
- Single zone per floor + Single zone building → Conditioned merge + Single zone building
- Single zone per floor + Single zone per floor type → Conditioned merge + Single zone building
- Single zone per floor + Stack → Conditioned merge + Single zone building
- Single zone per floor + Stacked floor zone multiplier → Conditioned merge + Single zone building
7A · 90.1-2007 · 45°
Reference 37caae9d6680f7fd/R: No simplification + Stack, 6 zones, 4,181 m² conditioned; annual sensible heating 23.9 and cooling 50.3 kWh/m²; peak heating 266.4 and cooling 134.6 kW. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Single zone building | 1 | 0.00 | -9.1 | -6.0 | 40.5 | 16.2 | 9.1 | 6.0 | 5.8 | -0.7 | no |
| Perimeter core 3 m + Stack | 5 | 0.00 | -4.4 | -2.3 | 19.7 | 7.7 | 4.4 | 2.3 | 2.6 | -0.2 | yes, recommended |
| Perimeter core 4.57 m + Stack | 5 | 0.00 | -3.5 | -2.0 | 14.9 | 6.3 | 3.5 | 2.0 | 1.8 | -0.2 | yes, recommended |
20 zonings write the same model as a listed one and are not shown
- Conditioned merge + Single zone per floor type → Conditioned merge + Single zone building
- Conditioned merge + Stack → Conditioned merge + Single zone building
- Conditioned merge + Stacked floor zone multiplier → Conditioned merge + Single zone building
- No simplification + Single zone building → Conditioned merge + Single zone building
- No simplification + Single zone per floor type → Conditioned merge + Single zone building
- No simplification + Stacked floor zone multiplier → 37caae9d6680f7fd/R
- Perimeter core 3 m + Single zone building → Conditioned merge + Single zone building
- Perimeter core 3 m + Single zone per floor type → Conditioned merge + Single zone building
- Perimeter core 3 m + Stacked floor zone multiplier → Perimeter core 3 m + Stack
- Perimeter core 4.57 m + Single zone building → Conditioned merge + Single zone building
- Perimeter core 4.57 m + Single zone per floor type → Conditioned merge + Single zone building
- Perimeter core 4.57 m + Stacked floor zone multiplier → Perimeter core 4.57 m + Stack
- Semantic merge + Single zone building → Conditioned merge + Single zone building
- Semantic merge + Single zone per floor type → Conditioned merge + Single zone building
- Semantic merge + Stack → 37caae9d6680f7fd/R
- Semantic merge + Stacked floor zone multiplier → 37caae9d6680f7fd/R
- Single zone per floor + Single zone building → Conditioned merge + Single zone building
- Single zone per floor + Single zone per floor type → Conditioned merge + Single zone building
- Single zone per floor + Stack → Conditioned merge + Single zone building
- Single zone per floor + Stacked floor zone multiplier → Conditioned merge + Single zone building
7A · 90.1-2019 · 0°
Reference 331402cfb32ca853/R: No simplification + Stack, 6 zones, 4,181 m² conditioned; annual sensible heating 25.2 and cooling 42.9 kWh/m²; peak heating 257.7 and cooling 129.1 kW. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Single zone building | 1 | 0.00 | -9.8 | -7.1 | 36.8 | 20.0 | 9.8 | 7.1 | 6.4 | -1.0 | no |
| No simplification + Single zone building | 1 | 0.00 | -9.8 | -7.1 | 36.8 | 20.0 | 9.8 | 7.1 | 6.4 | -0.9 | no |
| Perimeter core 3 m + Single zone building | 1 | 0.00 | -9.8 | -7.1 | 36.8 | 20.0 | 9.8 | 7.1 | 6.4 | -1.0 | no |
| Perimeter core 4.57 m + Single zone building | 1 | 0.00 | -9.8 | -7.1 | 36.8 | 20.0 | 9.8 | 7.1 | 6.4 | -1.0 | no |
| Perimeter core 3 m + Stack | 5 | 0.00 | -4.1 | -3.1 | 21.0 | 10.9 | 4.1 | 3.1 | 2.7 | 0.4 | yes, recommended |
| Perimeter core 4.57 m + Stack | 5 | 0.00 | -3.6 | -2.8 | 17.3 | 9.2 | 3.6 | 2.8 | 1.7 | 0.1 | yes, recommended |
17 zonings write the same model as a listed one and are not shown
- Conditioned merge + Single zone per floor type → Conditioned merge + Single zone building
- Conditioned merge + Stack → Conditioned merge + Single zone building
- Conditioned merge + Stacked floor zone multiplier → Conditioned merge + Single zone building
- No simplification + Single zone per floor type → No simplification + Single zone building
- No simplification + Stacked floor zone multiplier → 331402cfb32ca853/R
- Perimeter core 3 m + Single zone per floor type → Perimeter core 3 m + Single zone building
- Perimeter core 3 m + Stacked floor zone multiplier → Perimeter core 3 m + Stack
- Perimeter core 4.57 m + Single zone per floor type → Perimeter core 4.57 m + Single zone building
- Perimeter core 4.57 m + Stacked floor zone multiplier → Perimeter core 4.57 m + Stack
- Semantic merge + Single zone building → No simplification + Single zone building
- Semantic merge + Single zone per floor type → No simplification + Single zone building
- Semantic merge + Stack → 331402cfb32ca853/R
- Semantic merge + Stacked floor zone multiplier → 331402cfb32ca853/R
- Single zone per floor + Single zone building → Conditioned merge + Single zone building
- Single zone per floor + Single zone per floor type → Conditioned merge + Single zone building
- Single zone per floor + Stack → Conditioned merge + Single zone building
- Single zone per floor + Stacked floor zone multiplier → Conditioned merge + Single zone building
7A · 90.1-2019 · 45°
Reference 4cbb0555423aa51f/R: No simplification + Stack, 6 zones, 4,181 m² conditioned; annual sensible heating 25.7 and cooling 37.4 kWh/m²; peak heating 255.8 and cooling 111.2 kW. This cell was not timed in the serial pass (R5).
| Zoning | Zones | Area change % | Heating error % | Cooling error % | Heating CV(RMSE) % | Cooling CV(RMSE) % | Heating NMBE % | Cooling NMBE % | Peak heating error % | Peak cooling error % | Meets the threshold |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conditioned merge + Single zone building | 1 | 0.00 | -7.4 | -6.9 | 31.1 | 19.0 | 7.4 | 6.9 | 6.0 | -1.0 | no |
| No simplification + Single zone building | 1 | 0.00 | -7.4 | -6.9 | 31.1 | 19.0 | 7.4 | 6.9 | 6.0 | -0.8 | no |
| Perimeter core 3 m + Single zone building | 1 | 0.00 | -7.4 | -6.9 | 31.1 | 19.0 | 7.4 | 6.9 | 6.1 | -0.9 | no |
| Perimeter core 4.57 m + Single zone building | 1 | 0.00 | -7.4 | -6.9 | 31.1 | 19.0 | 7.4 | 6.9 | 6.1 | -0.9 | no |
| Perimeter core 3 m + Stack | 5 | 0.00 | -3.8 | -2.9 | 15.1 | 9.6 | 3.8 | 2.9 | 1.9 | -0.5 | yes, recommended |
| Perimeter core 4.57 m + Stack | 5 | 0.00 | -3.0 | -2.7 | 11.4 | 8.0 | 3.0 | 2.7 | 1.4 | -0.6 | yes, recommended |
17 zonings write the same model as a listed one and are not shown
- Conditioned merge + Single zone per floor type → Conditioned merge + Single zone building
- Conditioned merge + Stack → Conditioned merge + Single zone building
- Conditioned merge + Stacked floor zone multiplier → Conditioned merge + Single zone building
- No simplification + Single zone per floor type → No simplification + Single zone building
- No simplification + Stacked floor zone multiplier → 4cbb0555423aa51f/R
- Perimeter core 3 m + Single zone per floor type → Perimeter core 3 m + Single zone building
- Perimeter core 3 m + Stacked floor zone multiplier → Perimeter core 3 m + Stack
- Perimeter core 4.57 m + Single zone per floor type → Perimeter core 4.57 m + Single zone building
- Perimeter core 4.57 m + Stacked floor zone multiplier → Perimeter core 4.57 m + Stack
- Semantic merge + Single zone building → No simplification + Single zone building
- Semantic merge + Single zone per floor type → No simplification + Single zone building
- Semantic merge + Stack → 4cbb0555423aa51f/R
- Semantic merge + Stacked floor zone multiplier → 4cbb0555423aa51f/R
- Single zone per floor + Single zone building → Conditioned merge + Single zone building
- Single zone per floor + Single zone per floor type → Conditioned merge + Single zone building
- Single zone per floor + Stack → Conditioned merge + Single zone building
- Single zone per floor + Stacked floor zone multiplier → Conditioned merge + Single zone building
Atlas programs
The atlas programs each program key of the prototype takes, as the suite's saved inputs name them (release 2.4.0 IDs); the prototype's geometry and glazing are BEMGen's DOE record. Method and caveats.