E2: binding detailed construction rules to BEMGen zones (design note)

Status: Superseded by D-142 (2026-10-16): BEMGen converts only unified building-scope sets, so detailed rules are never bound to zones. Kept as the record of the questions; the owner's answers are in D-142 · Date: 2026-10-16 · Decisions: D-137 to D-141; new: one entry for the owner's answers · Branch: feature/construction-json (proposed; see question 10) · Builds on: construction JSON note (E1), ADR-021, ADR-022, construction-json.md

This is one stage run as D-111 sets out: this note first, then one test-first build, a review by a second agent, the headless Rhino check, scripts/verify.ps1, a decision-log entry, and an ADR, because it decides how a source's construction rules meet BEMGen's geometry.

Stop line. The build ends verified, reviewed, and documented. It does not merge, tag, push, or release.

Problem

E1 reads a detailed construction_set 2.0.0 with every assignment rule, but Convert2IDF refuses it (ConstructionAssignmentUnavailable). E2 makes it convertible.

For each surface, window, and internal mass of a building, E2 chooses the one assignment whose condition (when) matches, as the source's policy says: space type, then storey, then the building default; a unique compatible rule; and an error when no rule matches or several do (unmatched_or_ambiguous: error). The unified path (C2) stays as it is. Detailed and unified are two explicit choices, never switched or blended automatically (handover).

What the packet's rules look like

From the five detailed documents (docs/residential-fixture-coverage.json and a census of when):

Document Rules Conditions used
Medium Office 3B one per component, plus InteriorFloor for space_type: Plenum building_default; window_operation fixed or operable
Warehouse 3B four per component: the default and space_type Office, Fine, Bulk building_default, space_type, window_operation
Residential 5A conditioned space to outside; attic to outside; conditioned space to attic (the ceiling); partitions whole_dwelling with interior_space_type, exterior_space_type
Residential 4A the above without the attic, plus conditioned space to garage (wall, floor) and an Adiabatic interstorey floor as above, and boundary_condition
Residential 1A conditioned space to outside, with an exposed floor; an Adiabatic interstorey floor as above

No packet document uses story rules. Every one declares the same policy (space_type_then_story_then_building_default, explicit_assignment_id_or_unique_compatible_rule, source_absent_override: inherit_building_default, unmatched_or_ambiguous: error).

What a BEMGen zone knows today

  • Space type. SpaceType, BEMGen's own: DwellingUnit, Corridor, Stair, Office, Core, Retail, …, Mixed.
  • Program. ProgramPreset.Source. For a Program JSON preset it names the atlas program (Source.ProgramId), its building type and template. Program JSON 2.0.0 has no field for the native space type; its name and evidence carry it as text (WholeBuilding - Md Office_MediumOffice).
  • Conditioning. Program.IsConditioned.
  • Origin. Its source zones before simplification (SourceZones, Mapping), its storey (parts' elevations), and its multiplier.
  • Each surface. Its kind, its boundary (outdoors, ground, interzone, adiabatic), and the zone across it; for an interzone surface, its partner.
  • Windows. A window has no operation: BEMGen has no operable windows.

The handover warns against inferring native contexts from labels such as Office or Mixed, from floor indices, or from text in provenance.

Proposal

Part A: a binding context, explicit and typed (Lod.Core)

Each zone gets a ConstructionBinding that says which source context it stands for:

  • its source space type: the native name the detailed rules use, such as Bulk or Plenum, or none;
  • its space category for residential rules: conditioned space, or an unconditioned category such as garage, attic - vented, unconditioned space.

Question 1 decides where these come from. The binding is carried through simplification and aggregation the way SourceZones is. A merged zone whose sources disagree has no single binding, which is question 6.

Part B: the surface context and the matcher (Lod.Core.Conversion)

For every written surface, window, and removed or added mass, the converter builds a context:

  • the detailed semantic, from ConstructionRoles and the boundary:
Surface Semantic
wall to outdoors ExteriorWall
roof ExteriorRoof
floor to outdoors ExteriorFloor
wall between zones InteriorWall
slab between storeys InteriorFloor, the ceiling side reversed
window ExteriorWindow
removed slab InteriorFloor
partition mass InteriorPartition
  • the zone's source space type, the interior space category (the zone's) and the exterior one (outside to outdoors, or the adjacent zone's category);
  • the boundary condition as written (Outdoors, Surface, Adiabatic), and the window operation (question 4).

The matcher keeps the assignments of that semantic whose every given condition equals the context, then applies the precedence: a space_type rule over a story rule over a building_default rule (or whole_dwelling rule). One rule left is the assignment. None left is ConstructionUnmatched, and more than one ConstructionAmbiguous. Each error names the surface, its context, and the rules that came closest.

A paired surface between two zones is bound once, from the zone that owns it as ConstructionRoles already decides, and its partner takes the reverse (paired_surface_policy: reverse_order). SourceReferenceReversed is evidence only.

Part C: constructions per surface and per window (Lod.Export)

  • Assemblies. The writer gives each surface the assembly its rule selects, not one construction per role. Every selected assembly is written once, with its reverse where a pair needs it.
  • Windows. A window's construction is chosen per window, so a building may have several window constructions. Each with an incident solar multiplier gets its own SurfaceProperty:IncidentSolarMultiplier.
  • Unsupported assemblies. Selecting one (E1's Unsupported) is an error that names it.
  • The header lists each assignment used, with its ID, condition, assembly, and number of surfaces, plus every rule that matched nothing in this building.

Part D: mass (ConstructionMassAccounting)

The detailed document has no capacity budgets and no FloorDistributedMass. Its mass rules are geometric:

  • InteriorPartition: area per conditioned floor area, by its area_convention;
  • the interstorey floor's source_ordinary_interstory_scaling: an area rule, a paired flag, an activation threshold.

Question 7 decides how they apply.

Part E: Grasshopper

Convert2IDF converts a detailed set. Question 1 decides whether the binding needs a new input, such as a Space Type Map. Construction JSON is unchanged, apart from its warning, which goes.

Open questions for the owner

  1. Where does a zone's source space type come from?
  2. (a) A new explicit map on Convert2IDF, from BEMGen space type (or zone name) to source space type and space category, such as Office → Office, Core → Bulk, Stair → unconditioned space.
  3. (b) The program preset: Program JSON would record the native space type, which needs a structured field from the atlas (program JSON v3 may have one).
  4. (c) Only building-default and whole-dwelling rules are bound, and a document with space_type rules is refused.

I lean to (a) now, with (b) when the atlas provides the field. 2. Residential categories. BEMGen's residential plans have dwellings, corridors, and stairs; the residential sources have conditioned space, garage, and attic. - Are unconditioned corridors and stairs "unconditioned space"? No source rule mentions it, so their walls would be unmatched. - Is a garage ever modelled, or is the garage rule only evidence? 3. Walls and floors between two conditioned zones, residential. No residential rule covers them: the sources are single dwellings, and the only InteriorWall rule faces a garage. Options: - (a) Unmatched, an error. - (b) Fill From Example, as for unified sets (D-140). - (c) Use the Adiabatic interstorey rule for floors written adiabatic only; walls by (a) or (b).

And with floor heat transfer on, does the Adiabatic rule match an interzone floor (D-140 accepted that with a warning for unified sets), or is it unmatched? 4. Window operation. BEMGen windows have no operation, and the commercial documents give separate fixed and operable rules. Choose one by default (fixed?), or an input? 5. The attic in detailed documents. For 5A, the conditioned zones' roof matches no rule: the roof rule's interior is the attic. Apply D-140's approximation, the attic ceiling as the roof, through the InteriorCeiling rule, as for unified sets? 6. Rezoned zones. A merging simplifier makes zones whose sources have different space types. Options: - (a) An ambiguity error; use the unified document, as the handover suggests. - (b) The space type with the largest floor share. - (c) Allow it only when every source agrees.

I lean to (c), with (a) otherwise. 7. Mass for detailed sets. - Add the partitions as internal mass at their area per conditioned floor area, by their area convention? - Apply the interstorey area rule to slabs BEMGen does not represent? - Or keep the detailed path to explicit surfaces only, with no added mass?

The unified ledger cannot be reused, because there are no budgets. 8. story rules. No packet document has them. Refuse a document that has them until a storey map exists, or design the map now? 9. Fill From Example. Should it also cover unmatched detailed surfaces, or only not-applicable roles as now? 10. Branch and order. Continue on feature/construction-json, or merge C2 and E1 first and start feature/construction-binding from main?

Tests and checks (planned)

  • Matcher unit tests on hand-built contexts: precedence, unique compatible rule, unmatched and ambiguous errors, paired reversal.
  • End to end on the packet documents:
  • the warehouse with its three space types, mapped onto Office Plate and a warehouse-like plan;
  • the medium office's plenum floor;
  • 4A's garage and adiabatic rules;
  • 1A's exposed floor;
  • 5A on one storey of one zone.
  • Checks on the result:
  • every surface's construction against its rule, read back from the IDF;
  • several window constructions and their multipliers;
  • an unsupported assembly selected is an error.
  • A unified-detailed pair converted on the same building, comparing the area-weighted U-values per semantic. This is a check, not an equivalence claim.
  • IDD check, EnergyPlus runs, and the headless Rhino spec.